The T8112 Programmable Thermostat provides energy savings for single-stage heating and cooling applications while providing reliable, precise temperature control.
IMPORTANT The specifications given in this publication do not include normal manufacturing tolerances; therefore, an individual unit might not exactly match the listed specifications. Also, this product is tested and calibrated under closely controlled conditions, and some minor differences in performance can be expected if those conditions are changed.
When purchasing replacement and modernization products from your TRADELINE® wholesaler or your distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering information, or specify:
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
In Canada—Honeywell Controls Limited, 155 Gordon Baker Road, North York, Ontario M2H 2C9. International Sales and Service offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
Calibration:
Thermostat and thermometer self-calibrating to ±1.25°F.
Accessories:
When Installing this Product…
Compatibility
Check Table 1 to make sure the thermostat is compatible with the intended system.
Table 1. Compatibility Chart.
System Type | Compatible with T8112 |
Gas—Standing Pilot | Yes |
Gas—Electronic Ignition | Yes |
Gas-Fired Boilers | Yesa |
Gas—Millivolt | No |
Oil-Fired Boilers | Yesa |
Oil-Fired Furnace | Yes |
Electric Furnace | Yes |
Electric Air Conditioning | Yes |
Baseboard Electric (120/240 Line Volt) | No |
Heat pumps/Multistage Equipment | No |
a Compatible with 2-wire Honeywell zone valves.
All system types:
Not compatible with any 120/240 volt circuit.
Not designed for steam or gravity systems.
Not compatible with 2-wire White Rodgers no. 1361 Valves. Isolating relay required for 3-wire thermostats for zone valves.
WARNING
ELECTROCUTION HAZARD CAN CAUSE PROPERTY DAMAGE, SEVERE INJURY, OR DEATH.
Disconnect power supply before wiring to prevent electrical shock or equipment damage.
Locate the thermostat about 5 ft (1.5m) above the floor in an area with good air circulation at average temperature.
Do not mount the thermostat where it can be affected by:— drafts or dead spots behind doors and in corners.
(Fig. 2)
All wiring must comply with local electrical codes and ordinances. Refer to Fig. 5 through 8 for typical hookups. A letter code is located near each terminal for identification.
CAUTION Disconnect power before wiring to prevent electrical shock or equipment damage.
2-WIRE HEAT-ONLY (JUMPER INTACT)
Adjust Fan Operation Switch, as Required
The thermostat fan operation switch, labeled FUEL SWITCH (see Fig. 9) is factory set in the F position. This is the correct setting for most systems. If you have an electric heat system, set the switch to E. In systems with the G terminal connected, the E setting turns on the fan immediately with heating or cooling.
Adjust System On-Time as Required
The thermostat on-time is factory set for a warm air, gas or oil heating system. If you are installing it on another type of system, the system on-time must be adjusted by changing the setting of screws A and B on the back of the thermostat. Use the heating system table in Fig. 9 as a guide to minimize room temperature swings. The system on-time should be optimized according to the type of system. Setting the screw out one turn means turning the screw approximately 360°, or one complete turn.
NOTE: This thermostat does not have a setting for steam/ gravity air. Cycles would not be long enough for accurate temperature control.
NOTE: For condensing furnaces, follow manufacturer instructions.
IMPORTANT When using a high efficiency furnace such as a 90 percent or greater AFUE (Average Fuel Utilization Efficiency) unit, adjust screw A out one turn and screw B In one turn.
If you want a longer on-time, readjust screws A and B as follows (refer to Table 1 Compatibility Chart):
IMPORTANT Batteries must be installed for programming and operating the thermostat and heating/cooling system.
When the batteries are running low, a bAt Lo indicator will flash for one to two months before batteries run out completely. Replace the batteries as soon as possible after the indicator starts flashing. If the batteries are not replaced when the bAt Lo indicator is flashing, the indicator eventually stops flashing. When the batteries are almost completely dead, bAt Lo will stay on without flashing, indicating that the thermostat and heating/cooling system have stopped working. The thermostat will not function after the batteries are completely dead, and the bAt Lo indicator disappears, leaving a completely blank display.
To remove the batteries, press down on the left ends. When the new batteries are installed within 20 to 30 seconds of removing the old ones, the thermostat does not have to be reprogrammed. If the display is blank, the batteries are dead or incorrectly installed and the thermostat has to be reprogrammed. See Owner’s Manual for reprogramming instructions.
IMPORTANT
Although the thermostat has a low battery indicator, replace the batteries once a year to prevent the thermostat from losing time and programming due to lack of battery power.
To set the time:
To set the day:
To set the system switch to HEAT:
A Quick Guide for Operating or Making Changes
NOTE: The system switch must be set to Heat or Cool to perform the following.
To temporarily change the temperature for the current period only:
To hold a temperature indefinitely:
To check the current temperature setting:
Press the Run Program key. (When using TEMPORARILY CHANGE or HOLD, pressing this key will cancel the change or hold.)
To check the programs:
To cancel a program:
To permanently change a program:
Repeat the steps in the Heating Program or Cooling Program section as applicable.
To return to the normal program:
Press the Run Program key.
After the thermostat is mounted on the mounting plate, check operation as follows:
Heating | |
Do not check the heating system operation by jumpering the thermostat terminals at the primary control such as the gas valve, zone valve, or oil burner control. This will damage the thermostat. Instead, you could jumper R and Rc wires at the thermostat. | |
Move the system switch to HEAT and the fan switch to AUTO. |
|
Press the TEMP key until the setting is about 10°F (6°C) above the room temperature. After a short delay, the heating should start and the fan should run (immediately if fan operation switch is set in E position). | |
Press the TEMP key until the setting is about 10°F (6°C) below the room temperature. The heating equipment should shut off. | |
Cooling | Cool Off Heat |
To avoid possible compressor damage, do not operate the cooling system when the outside temperature is below 50°F (10°C). See the compressor manufacturer instructions for further information. NOTE: When the cooling setting is changed, the thermostat can delay up to five minutes before turning on the air conditioner to protect the compressor. | |
Move the system switch to COOL and the fan switch to AUTO. | |
Press the TEMP key until the setting is about 10°F (6°C) below room temperature. The cooling equipment and fan should start. | |
Press the TEMP key until the setting is about 10°F (6°C) above the room temperature. The cooling equipment and fan should stop. | |
Move the system switch to OFF with the fan switch remaining at AUTO. The system and fan should be off. |
|
FAN AUTO: Normal setting for most homes. A single-speed fan turns on automatically with the air conditioner or furnace. A two-speed fan usually runs on high with the air conditioner and on low with the furnace.
FAN ON: The fan runs continuously. Use for improved air circulation during special occasions or for more efficient electronic air cleaning.
COOL: The thermostat controls the air conditioning system.
OFF: Both the heating and air conditioning systems are off.
HEAT: The thermostat controls the heating system.
IF… | THEN… |
Display will not come on. | • Set the system switch to OFF; remove batteries; insert backward for at least five seconds to reset thermostat; replace batteries correctly. Display should come on. |
• Make sure batteries are fresh and installed correctly. | |
Temperature display will not go lower than 45°F (7°C) or higher than 88°F (31°C) during programming. | • The temperature setting limit has been reached. The setting range is 45°F to 88°F (7°C to 31°C). |
Heating will not come on. | • If the display is blank or displays bAt Lo, install fresh batteries. |
• Check that the switch on the thermostat is set to HEAT. | |
• Check the system fuse or circuit breaker and replace or reset if necessary. | |
• If the temperature setting is higher than the current temperature, and SYSTEM ON indicator is lit, see the furnace manufacturer instructions. | |
Cooling will not come on. | • If the display is blank or displays bAt Lo, install fresh batteries. |
• In 2- or 4-wire installations, verify that the R-Rc jumper is installed. | |
• Check that the switch on the thermostat is set to COOL. | |
• Check the system fuse or circuit breaker and replace or reset if necessary. | |
• The thermostat has a built-in time delay on cooling. Allow five to ten minutes after changing the setting before the air conditioner starts. | |
• If the temperature setting is lower than the current temperature, and the SYSTEM ON indicator is lit, move the system switch from COOL to OFF for ten minutes. | |
• After ten minutes, return the switch to the COOL position. If the air conditioner comes on, the compressor could have reached its high limit temperature protection and shut down. If the air conditioner does not come on after ten minutes and the SYSTEM ON indicator is lit, see the air conditioner manufacturer instructions. | |
SYSTEM ON indicator is lit, but no heat is coming from the registers. | • Allow time for the furnace to heat up and the fan to come on before checking for heat at the register. Check to make sure system on-time is set correctly according to the instructions in the Installation section. |
Furnace or air conditioner cycles too frequently. | • Check the system setting on the back of thermostat. |
The system on-time is too short or too long. | • Readjust according to the instructions in the Installation Section. |
The thermostat current setting does not match the display temperature. | • Check that the wiring hole in the wall behind the wallplate was plugged with insulation to prevent drafts that could adversely affect thermostat operation. |
• It is normal for the current setting and display temperature to differ occasionally. | |
bAt Lo remains on the display after fresh batteries have been installed. | • Remove batteries. Wait one hour. Install fresh alkaline batteries. |
Home and Building Control Honeywell Inc.
1985 Douglas Drive North Golden Valley, MN 55422
Home and Building Control Honeywell Limited-Honeywell Limitée 155 Gordon Baker Road
North York, Ontario
M2H 2C9
Printed on recycled paper containing at least 10% post-consumer paper fibers.
Download Manual:
HONEYWELL T8112C Electronic Programmable Thermostats Installational Instruction
HONEYWELL T8112C Electronic Programmable Thermostats Installational Instruction
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…