The T8011R Heat Pump Thermostat provides 24 Vac control of a two-stage heating and one-stage cooling heat pump system with manual changeover from heat to cool. First stage heating and cooling cycle rates are fixed at 3 cph. The second stage heating cycle rate is selectable at 3, 4, 5, 6, 9 or 12 cph. Temperature indication can be set for °F or °C.
The T8011R Heat Pump Thermostat is powered directly from the system transformer. Setpoints are held permanently in memory and retained during power outages.
The T8011R TRADELINE® model includes a thermostat, wallplate and owner’s guide. A 7 3/8 in. (188 mm) x 5 3/4 in. (146 mm) decorator cover plate (for covering wall marks) is available separately. Order Honeywell part no. 209649A (taupe) or part no. 209649B (white).
MERCURY NOTICE
If this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash. Dispose of it properly. Contact your local waste management authority for instructions regarding recycling and the proper disposal of a control.
When Installing this Product…
Install the thermostat about 5 ft (1.5m) above the floor in an area with good air circulation at average temperature. See Fig. 1. Do not install the thermostat where it can be affected by:
IMPORTANT Level for appearance only. The thermostat functions normally even when not level. Mount wallplate and the T8011R with the screws provided (see Fig. 2) as follows:
Table 1. Description of T8011R Thermostats.
| Model | System | Changeover | System Selection | Fan Selection | Powering Method |
| T8011R | Heat Pump | Manual | Cool-Off-Heat-Em. Ht. | Auto-On | Hardwired |
IMPORTANT Use 18-gauge maximum wire for wiring the T8011R Thermostat.
All wiring must comply with local electrical codes and ordinances. Disconnect the power supply to prevent electrical shock or equipment damage.
The shape of the terminals permits insertion of straight or wraparound wiring connections; either method is acceptable. A letter code is located near each terminal for identification. See Fig. 3.
NOTE: To ensure proper mounting of thermostat, restrict all wiring to the shaded area in the center of the terminals. See Fig. 4.
Refer to Fig. 5 for typical wiring hookup.
The following instructions provide the information necessary to change the heating cycle rate to match the heating equipment and to choose either Fahrenheit (°F) or Celsius C) display.
NOTE: All four steps must be completed to save changes to the °F/°C indication and the heat cycle rate.
Enter Installer Setup.
When in steps 1c and 1d only, pressing the ▼ key can be used to turn heat or cool outputs on and off. Change the SYSTEM switch setting to test heat or cool outputs. During testing, the 5 minute minimum off time is bypassed. No action takes place If the system switch is in the Off position.
Examples: System setting at HEAT: If heat is on,
pressing the ▼ key turns it off; if heat is off, pressing the ▼ key turns it on.
System setting at COOL: If cool is on, pressing the ▼ key turns it off; if cool is off, pressing the ▼ key turns it on.
NOTE: In installer setup only, each press of the ▲ key momentarily displays 1. Each press of the ▼ key momentarily displays 2. When the keys are released, these one-digit codes are no longer displayed.
Setting °C or °F.
Setting Heat Cycle Rate (see Table 2 for cycle rate options and equipment).
Exit Installer Setup.
Table 2. Heating Cycle Rate
| System | Cycles Per Hour |
| Hydronic Heat, Condensing Gas Furnacesa | 3 |
| Gas or Oil Forced Air | 6 |
| Electric Heat | 9 |
| Special Applicationsb | 4, 5, 12 |
NOTE: Stage one heat and cool cycle rates are fixed at 3 cph. Only stage two heat cycle rates are selectable.
Setting FAN and SYSTEM Switches
Fan and system settings are controlled manually by using the switches located at the bottom of the thermostat case. See Fig. 7.
FAN Switch
Fan switch settings are:
SYSTEM Switch
System switch settings control thermostat operation as follows:
To use the preprogrammed time and temperature press Hold to exit the programming mode.
Setting Time And Temperature
The T8000C is preprogrammed with the time and temperature settings shown in Table 3. For instructions on programming the thermostat refer to the Owners Guide, Form No. 69-1143.
Table 3. Preprogrammed Time and Temperature Settings.
| Period | Time | Heat Setpoint | Cool Setpoint |
| Wake | 6:00 AM | 70°F (21°C) | 78°F (26°C) |
| Leave | 8:00 AM | 62°F (17°C) | 85°F (29°C) |
| Return | 6:00 PM | 70°F (21°C) | 78°F (27°C) |
| Sleep | 10:00PM | 62°F (17°C) | 82°F (28°C) |
CAUTION
Damage To Compressor Possible. Operating at too low of an outdoor temperature may cause compressor damage.
Do not operate cooling if outdoor temperature is below 50°F (10°C).
Allow the compressor to remain off for five minutes before restarting.
Refer to manufacturer’s recommendations.
Make certain all equipment responds correctly to the thermostat.
Automation and Control Solutions
Honeywell
1985 Douglas Drive North Golden Valley, MN 55422
Honeywell Limited-Honeywell Limitée 35 Dynamic Drive
Scarborough, Ontario
M1V 4Z9
Download manual:
Honeywell T8011R Programmable Heat Pump Thermostat INSTALLATION INSTRUCTIONS
Honeywell T8011R Programmable Heat Pump Thermostat INSTALLATION INSTRUCTIONS
Free Money Online Casino No Deposit Canada However, and players have no control over it.…
Eureka Casino No Deposit Bonus Codes For Free Spins 2026 Furthermore, and beginner-friendly as well.…
Top 10 Online Canada Casinos Top 10 online canada casinos you can contact Easy Slots'…
2026 Canada Changes In Blackjack 2026 canada changes in blackjack an online casino reload bonus…
Mannheim Casino No Deposit Bonus Codes For Free Spins 2026 Don't miss out on this…
Slot Games For Real Money I should start with a variety of gambling options, you…