The T7351 Commercial Programmable Thermostat controls 24 Vac commercial single zone heating, ventilating and air conditioning (HVAC) equipment. The T7351 consists of a thermostat and subbase. The thermostat includes the display and keypad for 7-day programming. The subbase includes equipment control connections. The subbase mounts on the wall and the thermostat mounts to the subbase.
MERCURY NOTICE
If this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash. Dispose of properly.
Contact your local waste management authority for instructions regarding recycling and the proper disposal of an old control. If you have questions, call Honeywell Customer Care Center at 1-800-468-1502.
When Installing this Product…
Do not install the thermostat where it can be affected by:
WHEN USED TO SENSE ROOM TEMPERATURE Install the thermostat about 5 ft. (1.5m) above the floor in an area with good air circulation at average temperature. (See Fig. 1.)
WHEN NOT USED TO SENSE ROOM TEMPERATURE When using the remote-mounted temperature (and humidity) sensor(s) to sense ambient conditions, install the thermostat in an area that is accessible for setting and adjusting the temperature and settings.
Install the remote-mounted sensor(s) about 5 ft. (1.5m) above the floor in an area with good air circulation at average temperature (See Fig. 1).
If multiple remote sensors are required, they must be arranged in a temperature averaging network consisting of four sensors (See Fig. 2).
NOTE: Only TR21 models with no setpoint adjustment can be used for temperature averaging.
Mounting Subbase
The subbase mounts horizontally.
IMPORTANT
Wall mounting (using standard drywall screws) is standard. Mounting to a 2 in. by 4 in. (50.8 mm by 101.6 mm) wiring box can be accomplished:
Mount to European standard wall box (having 2.4 in. (60.3 mm) between mounting screws in a horizontal line) with or without adaptive hardware.
Mounting Thermostat on Subbase (Fig.4)
With the subbase installed, mount the thermostat:
A. ENGAGE TABS AT TOP OF THERMOSTAT AND SUBBASE OR WALLPLATE.
B. PRESS LOWER EDGE OF CASE TO LATCH.
Follow equipment manufacturer wiring instructions when available. Refer to the Wiring Diagram section for typical hookups. A letter code is located near each terminal for identification.
IMPORTANT All wiring must comply with local electrical codes and ordinances.
NOTE: Maximum (and recommended) wire size is 18-gauge. Do not use wire smaller than 22-gauge.
Using Thermostat Keys
The thermostat keys are used to:
NOTE: See Fig. 5 for keypad information.
Setting Temperature
Refer to Table 2 for the default temperature setpoints. To set the Occupied and Not Occupied Heat and Cool setpoints, simply press the Heat and Cool button under the Occupied or Not Occupied area of the keypad. To set the Standby Heat setpoint, press both the Occupied and Not Occupied Heat buttons simultaneous. To set the Standby Cool setpoint, press the Occupied Cool and Not Occupied Heat buttons simultaneously.
Setting System and Fan
System default setting is Auto. Fan default setting is On.
NOTE: Use System and Fan keys to change settings.
Fan Settings
Table 1. T7351 Intelligent™ Fan ON control logic
Occupancy | Call for Heat/Cool |
Notes | |||
Scheduled Period | Motion Sensor Signal | Effective Occupancy | Yes | No | |
Occupied | No Sensor Wired | Occupied | Fan On | Fan On | |
Occupied | Motion Sensed | Occupied | Fan On | Fan On | |
Occupied | No Motion Sensed | Standby | Fan On | Fan Offa | Effective Occupancy is Standby. Standby setpoints are used and it assumes that the space is unoccupied. Fan is on only when there is a call for heating or cooling. |
Not Occupied | No Sensor Wired | Not Occupied | Fan On | Fan Offa | Occupancy sensor will only be active during scheduled Occupied periods. During scheduled Not Occupied periods, the effective occupancy will always be Not Occupied. |
Not Occupied | Motion Sensed | Not Occupied | Fan On | Fan Offa | |
Not Occupied | No Motion Sensed | Not Occupied | Fan On | Fan Offa |
In heat mode, when set for conventional heat, the equipment (i.e. plenum switch) could power the fan despite the T7350
For most applications, the thermostat factory settings do not need to be changed. Review the factory settings in Table 2.
NOTE: When power is first applied to the thermostat, the display will show all segments (see Fig. 6).
Table 2. Default Setpoints.
Control | Occupied | Not Occupied | Standby |
Heating | 70° F (21° C) | 55° F (13° C) | 67° F (19° C) |
Cooling | 75° F (24° C) | 85° F (29° C) | 78° F (26° C) |
CAUTION
Setup Using Keypad
The installer uses the Installer Setup to customize the thermostat to specific systems
A combination of key presses are required to use the Installer Setup feature:
Configuration can be done with the keypad using the Installer Setup (ISU).
Table 3. Installer Setup.
Text | Default | Choices | Notes |
DEGREES | 0 | 0 -1 | Degree Temperature Format 0: Degrees F 1: Degrees C |
CLOCK | 0 | 0 – 1 | Clock Display Format 0: 12 hour 1: 24 hour |
KEYLOCK | 0 | 0 – 3 | Keypad Lockout Level 0: None 1: Lockout all keys except Set Day, Set Time, Set Date, Set Holidays, Temporary Occupied, Temporary Not Occupied, System, Fan, Up, Down and Information 2: Lockout all keys except Set Day, Set Time. Set Date, Set Holidays, Temporary Occupied, Temporary Not Occupied, Up, Down and Information 3: Lockout all keys except Information |
Text | Default | Choices | Notes |
HEATPMP | 0 | 0 – 2 | Application Type Selection 0: Conventional 1: Heat Pump – Cooling (Energize O/B on call for cool) 2: Heat Pump – Heating (Energize O/B on call for heat) |
COOLSTG | 1 | 0 – 4 | Number of Cooling Stages 0: 0 Stages of Cooling 1: 1 Stages of Cooling 2: 2 Stages of Cooling 3: 3 Stages of Cooling (Not available if Heat Pump is selected) 4: 4 Stages of Cooling (W3 will be used as 4th stage relay) (Not available if Heat Pump is selected) |
HEATSTG | 1 | 0 – 3 | Number of Heating Stages (Not available if Heat Pump is selected) 0: 0 Stages of Heating 1: 1 Stages of Heating 2: 2 Stages of Heating (This is the max if 4 cooling stages is selected) 3: 3 Stages of Heating |
AUX STG | 0 | 0 – 2 | Number of Heat Pump Heating Stages (Only shown when Heat Pump is selected) 0: 0 Aux Stages 1: 1 Aux Stages 2: 2 Aux Stages |
AUX CON | 0 | 0 – 3 | Aux Contact Functionality 0: Time of Day 1: Economizer 2: Dehumid – Hot Gas Bypass 3: Simple Dehumid |
WALLMOD | 0 | 0 – 3 | Remote Room Sensor Selection 0: Local sensor only 1: TR21/TR24 and T7770A/D (Remote Sensor, No Remote Setpoint, Bypass 0) 2: TR22/TR23 and T7770B/C (Remote Sensor, Remote Setpoint, Bypass 0) 3: T7771 (Remote sensor, Remote Setpoint, Bypass 1) (Bypass 0 means that by pressing the override button the thermostat goes from unoccupied to occupied and the LED will light up and the temporary occupied timer will begin. If the button is pressed again, the timer will restart.) (Bypass 1 means that by pressing the override button a second time the thermostat can return to the unoccupied period.) |
OATSENS | 0 | 0 – 1 | Outdoor Air Sensor Selection 0: None 1: Remote Outdoor Air Sensor |
DATSENS | 0 | 0 – 1 | Discharge Air Sensor Selection 0: None 1: Remote Discharge Air Sensor |
HUMSENS | 0 | 0 – 2 | Room Humidity Sensor selection 0: None 1: On Board Sensor 2: Remote Sensor |
OCCSENS | 0 | 0 – 1 | Occupancy Sensor Selection 0: None 1: Remote Occ Sensor |
FAN HT | 0 | 0 – 1 | Fan Operation on Heat 0: Conventional (Equipment controls Fan) 1: Electric (Thermostat turns on Fan with call for Heat) |
XFAN HT | YES | YES or NO | Extended Fan on Heat NO: None YES: 90 seconds |
XFAN CL | NO | YES or NO | Extended Fan on Cool NO: None YES: 40 seconds |
STRTDEL | 0 | 0 – 15 | Sequential Start Delay 0 to 150 seconds in 10 second increments |
ADVANCE | NO | YES or NO | Advanced Settings NO: Hide YES: Show |
Text | Default | Choices | Notes |
TMP LIM | 3 | 0 – 5 | Temporary Setpoint Adjustment 0: 0 Deg. F 1: 1 Deg. F 2: 2 Deg. F 3: 3 Deg. F 4: 4 Deg. F 5: 5 Deg. F |
TMP OCC | 3 | 1 – 8 | Temporary Occupied Duration 1 to 8 hours |
TMP CAL | 0 | -4 – 3 | Temporary Display Adjustment 0 – 3 = 0 to 3 DDF 4 – 7 = -4 to -1 DDF |
MINCOOL | 45° F (7° C) | 45° – 99° F (7° – 37° C) | Min Cool Setpoint |
MAXHEAT | 90° F (32° C) | 40° – 90° F (4° – 32°) | Max Heat Setpoint |
HEATLCK | NO | YES or NO | Heating Lockout (Only displayed if Outdoor Air Sensor is selected) NO: None YES: Enabled |
HTLCKSP | 70° F (21° C) | -40° – 120 ° F (-40° – 49° F) | Heating Lockout Temperature (Display only if Remote Outdoor Air Sensor is configured) |
COOLLCK | NO | YES or NO | Cooling Lockout (Only displayed if Outdoor Air Sensor is Selected) NO: None YES: Enabled |
CLLCKSP | 35° F (2° C) | -40° – 120° F (-40° – 49° C) | Cooling Lockout Temperature (Display only if Remote Outdoor Air Sensor is configured) |
DAT LL | NO | YES or NO | Discharge Low Limit (Only displayed if Discharge Air Sensor is Selected) NO: None YES: Enabled |
DATLLSP | 45° F (7° C) | 35° – 60° F (2° – 16° C) | Discharge Low Temp Limit (Display only if Discharge Sensor is configured) |
DAT HL | NO | YES or NO | Discharge High Limit (Only displayed if Discharge Air Sensor is Selected) NO: None YES: Enabled |
DATHLSP | 110° F (43° C) | 65° – 140° F (18° – 60° C) | Discharge High Temperature Limit (Display only if Discharge Sensor is configured) |
DEHUMID | 0 | 0 – 5 | Dehumidification 0: None 1: MinOn Time 2: Reset Temp Setpoint 3: Reset w/ MinOn 4: Reheat 5: Reheat w/ Min On |
DEH MIN | 5 | 5 – 15 | Dehumidify Minutes On |
DEH TMP | 2 | 1 – 5 | Dehumidify Temp Reset |
MINHTRT | 5 | 0 – 20 DDF/HR | Minimum Heat Recovery Ramp Rate |
MAXHTRT | 8 | 0 – 20 DDF/HR | Maximum Heat Recovery Ramp Rate (Only Displayed if Outdoor Sensor is Selected) |
MINHTOA | 0° F (-18° C) | -20° – 120° F (-29° – 49° C) | Minimum Heat Outdoor Air Temperature (Only Displayed if Outdoor Sensor is Selected) |
MAXHTOA | 40° F (4° C) | -20° – 120° F (-29° – 49° C) | Maximum Heat Outdoor Air Temperature (Only Displayed if Outdoor Sensor is Selected) |
MINCLRT | 3 | 0 – 20 DDF/HR | Minimum Cool Recovery Ramp Rate |
MAXCLRT | 6 | 0 – 20 DDF/HR | Maximum Cool Recovery Ramp Rate (Only Displayed if Outdoor Sensor is Selected) |
MINCLOA | 90° F (32° C) | -20° – 120° F (-29° – 49° C) | Minimum Cool Outdoor Air Temperature (Only Displayed if Outdoor Sensor is Selected) |
MAXCLOA | 70° F (21° C) | -20° – 120° F (-29° – 49° C) | Maximum Cool Outdoor Air Temperature (Only Displayed if Outdoor Sensor is Selected) |
Text | Default | Choices | Notes |
(DayLight Savings options only display when Date is valid) | |||
DSTMON1 | 3 | 0 – 12 | DLS Spring Month |
DSTDAY1 | 40 | 0 – 31, 32 – 74 | DLS Spring Day 0 – 31 = Day of Month 32 = Last Day of Month 33 = First Sunday etc… |
DSTMON2 | 11 | 0 – 12 | DLS Fall Month |
DSTDAY2 | 33 | 0 – 31, 32 – 74 | DLS Fall Day 0 – 31 = Day of Month 32 = Last Day of Month 33 = First Sunday etc… |
HT RESP | 1 | 0 – 3 | 0: Standard – 3 cph 1: Medium – 6 cph 2: Fast – 9 cph 3: Super Fast – 20 cph |
CL RESP | 0 | 0 – 1 | 0: Standard – 3 cph 1: Fast – 4 cph |
The T7351can be configured to schedule up to 10 separate holidays, each with a duration of up to 99 days. To enable this function, the user must set the date:
Holidays can be set in the following manner:
Table 4. Valid Day Values.
Value | Description | Value | Description | Value | Description | Value | Description |
1 to 31 | Day of month | 42 | Second Tuesday | 53 | Third Saturday | 64 | Fifth Wednesday |
32 | Last Day of Month | 43 | Second Wednesday | 54 | Fourth Sunday | 65 | Fifth Thursday |
33 | First Sunday | 44 | Second Thursday | 55 | Fourth Monday | 66 | Fifth Friday |
34 | First Monday | 45 | Second Friday | 56 | Fourth Tuesday | 67 | Fifth Saturday |
35 | First Tuesday | 46 | Second Saturday | 57 | Fourth Wednesday | 68 | Last Sunday |
36 | First Wednesday | 47 | Third Sunday | 58 | Fourth Thursday | 69 | Last Monday |
37 | First Thursday | 48 | Third Monday | 59 | Fourth Friday | 70 | Last Tuesday |
38 | First Friday | 49 | Third Tuesday | 60 | Fourth Saturday | 71 | Last Wednesday |
39 | First Saturday | 50 | Third Wednesday | 61 | Fifth Sunday | 72 | Last Thursday |
40 | Second Sunday | 51 | Third Thursday | 62 | Fifth Monday | 73 | Last Friday |
41 | Second Monday | 52 | Third Friday | 63 | Fifth Tuesday | 74 | Last Saturday |
Table 5. T7351 Key Function Summary.
Grouping | Button | Definition |
Information | Down Arrow | Lowers setpoint, day, or time. When setting times or temperatures, hold key down to continuously decrease value. Also can make temporary change in temperature setpoint. |
Information | Obtains information (where humidity “high-limit” can be set), cycles through setup options. | |
Up Arrow | Raises setpoint, day, or time. When setting times or temperatures, hold key down to continuously increase value. Also can make temporary change in temperature setpoint. |
On: Continuous fan operation during occupied periods. During not occupied periods and in standby mode when no motion is sensed, fan cycles with call for heat or cool.
Auto: Fan cycles with call for heat or cool during all periods. (See Product Data Sheet, form 63-2605, for more details).
NOTES: The display returns to default screen after pressing Run Schedule (or after a period of time without keypress):
Restore Factory Configuration (Run/Clear)
IMPORTANT This operation erases current configuration and restores factory defaults for all configuration, parameters, setpoints and schedules. To regain the old requires device reconfiguration.
Get Factory Schedule (Info/Clear)
Performing this operation reverts the schedules to the factory defaults:
(Occupied/Not Occupied/Schedule Day)
CAUTION Possible Equipment Damage.
Equipment damage can result if compressor is cycled too quickly.
The minimum off time for compressors is bypassed during Test Mode. Equipment damage can occur if the compressor is cycled too quickly. Use the Test Mode to check the thermostat configurations and operation. To start the system test:
NOTES:
Save User Schedule (Info/Copy)
Performing this operation saves the current schedule (including holidays) to memory, overwriting the old saved schedule:
Get User Schedule (Info/Run)
Getting the user schedule restores the schedule (including holidays) from saved memory, overwriting the schedule currently in use:
There are five methods through which the T7351 can control for dehumidification. Three of them modify the control algorithm, thus providing limited dehumidification through cooling. The other two use the auxiliary output to control another device.
NOTE: The dehumidification high limit can be set within the range of 10 to 90 percent relative humidity.
Control Through Cooling
Configure using some combination of the following:— Minimum On.
NOTES:
Min. ON Time
Dehumidifies by increasing the compressor minimum on time (normally 3 minutes) by a programmable amount. This is useful with oversized systems in that it forces the coils to cool to a point where dehumidification can occur.
NOTES:
Dehumidifies by operating cooling during typical off time. The T7351 maintains the proper setpoint by running the heat at the same time.
IMPORTANT At times during Reheat dehumidification, the T7351 operates heating and the cooling simultaneously. This is normal.
NOTES:
Reset Temp SetPt
The room temperature set point resets to a specified number of degrees below the actual set point when room relative humidity (RH) rises above humidity high limit set point.
Though this may not technically reduce relative humidity in the room, it reduces the dew point to provide the customer with a sense of comfort due to a lower temperature setting in the room.
As long as RH stays above humidity high limit set point, this set point is maintained.
NOTE: Hysteresis and a minimum timer prevent the set point from short interval alternation (between standard and reset set points).
Options Utilizing Auxiliary Output
There are two dehumidification options that utilize the auxiliary output. They are:
The auxiliary output:
NOTES:
The auxiliary output operates as shown in Table 6.
Table 6. Hot Gas Bypass Dehumidification Logic.
Humidity | Cooling Stages Active | Auxiliary Output |
High | more than one | De-energized |
High | one or less | Energized |
Low | more than one | De-energized |
Low | one or less | De-energized |
Auxiliary output during call for multiple cooling stages for two reasons:
Symptom | Possible Cause | Action |
Display will not come on. | Thermostat is not being powered. | Check that X terminal is connected to the system transformer. Check for 24 Vac between X and RH terminals. If missing 24 Vac: • Check if circuit breaker is tripped; if so, reset circuit breaker. • Check if system fuse is blown; if so, replace fuse. • Check if the HVAC equipment power switch is in the Off position; if so, set to the On position. • Check wiring between thermostat and HVAC equipment. Replace broken wires and tighten loose connections. If 24 Vac is present, proceed with troubleshooting. |
Temperature display is incorrect. | Thermostat is configured for °F or °C display. | Press both Run Schedule and Copy, then reconfigure the display. |
Bad thermostat location. | Relocate the thermostat. | |
Display shows three dashes and a degree sign (all systems shut down). | T7351 is set for remote sensing and sensor is missing or circuit is either open or shorted. | |
Temperature settings will not change. (Example: Cannot set heating higher or cooling lower.) | Upper or lower temperature limits were reached. | Check the temperature setpoints: • Heating limits are 40 to 90°F (7 to 31°C) • Cooling limits are 45 to 99°F (9 to 37°C) |
Occupied setpoint temperature range stops were configured. | Check setpoint stops. If necessary, reconfigure the stop(s). | |
Keypad is locked. When a locked key is pressed, LOCKED appears momentarily on the LCD. | Press both Run Schedule and Copy, then change keypad lock level. | |
Room temperature is out of control. | Remote temperature sensing is not working. | Check all remote sensors. |
Symptom | Possible Cause | Action |
Heat will not come on. | No power to the thermostat. | Check that X terminal is connected to the system transformer. Check for 24 Vac between X and RH terminals. If missing 24 Vac: • Check if circuit breaker is tripped; if so, reset circuit breaker. • Check if system fuse is blown; if so, replace fuse. • Check if the HVAC equipment power switch is in the Off position; if so, set to the On position. • Check wiring between thermostat and HVAC equipment. Replace broken wires and tighten loose connections. If 24 Vac is present, proceed with troubleshooting. |
Thermostat minimum off time is activated. | • Wait up to five minutes for the system to respond. • Configure heating response. | |
System selection is set to Off or Cool. | Set system selection to Heat or Auto. | |
Cooling will not come on. | No power to the thermostat. | Check that X terminal is connected to the system transformer. Check for 24 Vac between X and RH terminals. If missing 24 Vac: • Check if circuit breaker is tripped; if so, reset circuit breaker. • Check if system fuse is blown; if so, replace fuse. • Check if the HVAC equipment power switch is in the Off position; if so, set to the On position. • Check wiring between thermostat and HVAC equipment. Replace broken wires and tighten loose connections. If 24 Vac is present, proceed with troubleshooting. |
Thermostat minimum off time is activated. | • Wait up to five minutes for the system to respond. • Configure cooling response. | |
System selection is set to Off or Heat. | Set system selection to Cool or Auto. | |
System indicator (flame: heat, snowflake: cool) is displayed, but no warm or cool air is coming from the registers. | The call for heat or cool is not yet given. | Check if any stage indicators (dots next to the system indicator) are displayed. With no display of stage indicators, no call for cool/heat is yet given. |
Conventional heating equipment turns the fan on only after the furnace has warmed to a setpoint. | Wait one minute after seeing the on indicator and then check the registers. | |
Heating or cooling equipment is not operating. | Verify operation of heating or cooling equipment in self-test. |
Automation and Control Solutions Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
Honeywell Limited-Honeywell Limitée 35 Dynamic Drive
Toronto, Ontario M1V 4Z9
customer.honeywell.com
® U.S. Registered Trademark
© 2010 Honeywell International Inc. 62-0258—05 M.S. Rev. 09-10 Printed in U.S.A.
Download Manual:
Honeywell T7351F2010 Programmable Thermostat User Guide
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…