The TH5110D Non-programmable Thermostat provides electronic control of 24 Vac, single-stage heating and cooling systems or 750 mV heating systems. See Table 1 for a description.
Table 1. TH5110D Thermostat description.
Feature | Description |
Powering Methods | • Battery only • Common wire only • Common wire with battery backup |
System Types (Up to 1 Heat, 1 Cool) | • Gas, oil or electric heat with air conditioning • Warm air, hot water, high efficiency furnaces, heat pumps, steam and gravity • Heat only- includes power to open and power to close zone valves (Series 20) and normally-open zone valves • Heat only with fan • Cool only • 750 mV heating systems |
Changeover | Manual or auto changeover selectable |
System Setting | Heat-Off-Cool-Auto |
Fan Setting | Auto-On |
MERCURY NOTICE
If this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash. Contact your local waste management authority for instructions regarding recycling and the proper disposal of the old thermostat.
When installing this product
CAUTION: Electrical Hazard.
Can cause electrical shock or equipment damage.
Disconnect power before beginning installation.
Select Thermostat Location
Select a location for the thermostat about 5ft (1.5m) above the floor in an area with good air circulation at average temperature. See Fig. 1.
Separate Wallplate from Thermostat
Install Wallplate (See Fig. 3.)
Mount the thermostat horizontally on the wall:
All wiring must comply with local electrical codes and ordinances. Refer to Table 2 for descriptions of terminal designations. See Fig. 6-13 for wiring diagrams for specific equipment applications.
CAUTION Electrical Hazard.
Can cause electrical shock or equipment damage.
Disconnect power before wiring.
IMPORTANT Use 18-22 gauge thermostat wire. Shielded cable is not required.
Table 2. Terminal designation descriptions.
Terminal Designation | Description |
Rc (see Note 1) | Power for cooling-connect to secondary side of cooling system transformer |
R (see Note 1) | Power for heating-connect to secondary side of heating system transformer |
y | Compressor contactor |
C (see Note 2) | Common wire from secondary side of cooling system transformer |
O/B W (see Note 3) | Heat relay or changeover valve terminal for heat pumps |
G | Fan relay |
NOTES:
You can choose from three methods to power the thermostat:
Wiring 24 Vac Common
Installing Batteries
Install two AAA alkaline batteries on the back of the thermostat as marked on the battery holder. See Fig. 14.
NOTE: After the thermostat is mounted on the wallplate, the thermostat does not require removal from the wallplate to replace the batteries. Refer to the enclosed Operating Instructions, 69-1713, for more information on the removable battery holder.
Mount Thermostat to Wallplate
Configure Installer Setup
Table 3. Installer setup numbers and settings.
Installer Setup Number | Installer Setup Name | Settings |
1 | System Type | O-gas, oil or electric heat with air conditioning (Factory Setting) 1-Heat pump 2- Heat only (two-wire systems or power to open and power to close zone valves or normally-open zone valves) 3- Heat only with fan 4- Cool only |
2 May not appear. See Note a | Changeover Valve-O/B Terminal Energized in Heating or Cooling (Heat Pumps only) | O-Changeover valve–O/B terminal energized in cooling (Factory Setting 1-Changeover valve–O/B terminal energized in heating |
3 May not appear. See Note b | Fan Control in Heating | O- Gas or oil furnace– equipment controls fan in heating (Factory Setting) 1- Electric furnace– thermostat controls fan in heating |
5 May not appear. See Note c | Heating Cycle Rate in cycles per hour (cph) | 5-5 cph used for gas or oil furnaces (less than 90% efficient) (Factory Setting) 1-1 cph used for steam and gravity 3 –3 cph used for hot water and high efficiency furnaces (90%+) 9-9 cph used for electric furnaces 2, 4, 6, 7, 8, 1O, 11, 12–Other cycle rate settings |
9 May not appear. See Note d | Compressor Cycle Rate in cycles per hour (cph) | 3-3 cph recommended for compressors (Factory Setting) 1, 2, 4, 5, 6–Other cycle rate settings |
12 May not appear. See Note e | System Setting Adjustment | O-Manual changeover (Factory Setting) (Heat, Off, Cool) 1- Auto changeover (Heat, Off, Cool, Auto) 2- Auto changeover only (Auto) |
14 | Temperature Display | O-Fahrenheit temperature display (Factory Setting) 1-Celsius temperature display |
15 May not appear. See Note f | Compressor Protection– Minimum-Off Timer in minutes | 5-Five-minute compressor off-time setting (Factory Setting) O, 1, 2, 3, 4–Other compressor off-time settings |
Press the Next button to go to the beginning of the Installer Setup or press the Done button to exit the Installer Setup and save your settings. |
Installer Setup Notes:
Use the Installer System Test to test the heating, cooling and fan.
CAUTION Equipment Damage Hazard.
Minimum compressor off time is bypassed during Installer System Test
Avoid cycling compressor quickly.
How to Use the Installer System Test
IMPORTANT Use the Installer System Test to test the heating, cooling and fan. The setting you choose for System Type (Installer Setup Number 1) may prevent some System Test Numbers from appearing.
Table 4. Installer System Tests.
System Test Number | Test Type | System Status Number and Description |
1O | Heating System Test | 1-Heat turns on. When nstaller Setup Number 1 is set to 1 or nstaller Setup Number 3 is set to 1, the fan turns on immediately. O-Heat and fan turns off. |
3O | Cooling System Test | 1-Compressor and fan turns on. O-Compressor and fan turns off. |
4O | Fan System Test | 1-Fan turns on. O-Fan turns off. |
7O | Thermostat nformation (For reference only) | 71- Software revision number (Major) 72- Software revision number (Minor) 73- Configuration identification code (Major) 74-Configuration identification code (Minor) 75-Production configuration date code (Week) 76-Production configuration date code (year) |
Press the Next button to go to the beginning of the Installer System Test or press the Done button to exit the Installer System Test. |
Thermostat Buttons and Battery Holder
See Fig. 21 for description of thermostat buttons and battery holder.
See Fig. 22 for description of display.
System
Fan
Protection
The TH5110 has an adjustable Minimum-Off Timer that can be set from zero to five minutes (Factory Setting five minutes). The Minimum-Off Timer can be bypassed through the Installer System Test or it can be bypassed permanently by setting the Minimum-Off Timer to 0 minutes in the Installer Setup.
The Minimum-Off Timer is activated after the compressor turns off.
If the thermostat is system powered (common wire), the Minimum-Off Timer is also activated upon initial startup and after power interruptions.
If there is a call for cooling or heating during the Minimum-Off Time, the thermostat flashes ”Cool On” or “Heat On”a. When the Minimum Off Timer expires, ”Cool On” or “Heat On” a appears solid in the display and the compressor and fan turn on.
______________
aHeat Pumps only.
Cover Plates (see Fig. 23):
Replacement Battery Holder (see Fig. 24): 50000951-001 Battery Holder.
Table 5.
Symptom | Possible Cause | Action |
Display is blank. | Thermostat is not powered. | Check for 24 Vac between Rc and C.
Check that fresh AAA alkaline batteries are installed as marked on the battery holder. |
Temperature settings do not change. | The highest or lowest temperature setting was reached. | Temperature setting range: Heating: 40°Fto 90 °F(4.5 °C to 32 °C) Cooling: 50° F to 99°F (10°C to 37°C) |
Heat does not turn on (Heat On is solid in the display). | Heating equipment failure. | Check for 24 Vac at the equipment on the secondary side of the transformer between power and common. f voltage is not present, check the heating equipment to find the cause of the problem.
Check for 24 Vac between the heat terminal (W) and transformer common. f 24 Vac is present, the thermostat is functional. Check the heating equipment to find the cause of the problem. |
Loose or broken wire connection between thermostat and heating equipment. | Check for 24 Vac between the heat terminal (W) and transformer common. f voltage is not present, check wire connection (loose or broken) between the thermostat and the heating equipment. | |
Cooling does not turn on (Cool On is solid in the display). | Cooling equipment failure. | Check for 24 Vac at the equipment on the secondary side of the transformer between power and common. f voltage is not present, check the cooling equipment to find the cause of the problem.
Check for 24 Vac between the cool terminal (y) and transformer common. f 24 Vac is present, the thermostat is functional. Check the cooling equipment to find the cause of the problem. |
Loose or broken wire connection between thermostat and cooling equipment. | Check for 24 Vac between the cool terminal (y) and transformer common. f voltage is not present, check the wire connection (loose or broken) between the thermostat and the cooling equipment. | |
The fan does not turn on in a call for heat (electric furnace). | Fan Control in Heating (installer Setup Number 3) is set to Gas or Oil Furnace (Setting 0). | Set Fan Control in Heating (installer Setup Number 3) to Electric Furnace (Setting 1). |
The heat pump puts out cool air in the heat mode and warm air in the cool mode. | Changeover Valve (installer Setup Number 2) is not configured to match the changeover required by the installed heat pump. | Set Changeover Valve (installer Setup Number 2) to match the changeover required by the installed heat pump. |
Both the heating and cooling equipment are running at the same time. | The heating equipment is not a heat pump but the System Type (installer Setup Number 1) is set to Heat Pump (Setting 1). | Set System Type (installer Setup Number 1) to match the installed heating and/or cooling equipment. |
The heating and cooling wires are shorted together. | Separate the shorted heating and cooling wires. |
Symptom | Possible Cause | Action |
The heating equipment is running in cool mode. | The heating equipment is not a heat pump but System Type (installer Setup Number 1) is set to Heat Pump (Setting 1). | Set System Type (installer Setup Number 1) to match the installed heating and/or cooling equipment. |
The heating equipment does not turn off and the heat temperature setting is set below the room temperature (Heat On is not in the display). | The heating equipment is not a heat pump but System Type (installer Setup Number 1) is set to Heat Pump (Setting 1). | Set System Type (installer Setup Number 1) to match the installed heating and/or cooling equipment. |
Cannot set the system setting to Heat. | System Type (installer Setup Number 1) is set to Cool Only (Setting 4). | Set System Type (installer Setup Number 1) to match the installed heating and/or cooling equipment. |
System Setting Adjustment (installer Setup Number 12) is set to Auto Changeover Only (Setting 2). | Set System Setting Adjustment (installer Setup Number 12) to Manual Changeover (Setting 0) or Auto Changeover (Setting 1). | |
Cannot set the system setting to Cool. | System Type (installer Setup Number 1) is set to Heat Only (Setting 2) or Heat Only with Fan (Setting 3). | Set System Type (installer Setup Number 1) to match the installed heating and/or cooling equipment. |
System Setting Adjustment (installer Setup Number 12) is set to Auto Changeover Only (Setting 2). | Set System Setting Adjustment (installer Setup Number 12) to Manual Changeover (Setting 0) or Auto Changeover (Setting 1). | |
Heat On is not in the display. | The system setting is not set to Heat and/or the temperature setting is not set above the room temperature. | Set the system setting to Heat and set the temperature setting above the room temperature. |
Cool On is not in the display. | The system setting is not set to Cool and/or the temperature setting is not set below the room temperature. | Set the system setting to Cool and set the temperature setting below the room temperature. |
Heat On is flashing in the display (Heat pumps only). | The compressor minimum off-timer is active. | Wait up to five minutes for the heating equipment to turn on. |
Cool On is flashing in the display. | The compressor minimum off-timer is active. | Wait up to five minutes for the cooling equipment to turn on. |
Electrical Ratings:
Terminal | Voltage (5O/6O Hz) | Running Current |
W Heating | 20 – 30 Vac | .02 – 1.0A |
W Heating (Powerpile) | 750 mV dc | 100 mA dc |
y Cooling | 20 – 30 Vac | .02 – 1.0A |
G Fan | 20 – 30 Vac | .02 – .60A |
Automation and Control Solutions
Honeywell International Inc. 1985 Douglas Drive North Golden Valley, MN 55422
Honeywell Limited-Honeywell Limitée 35 Dynamic Drive
Scarborough, Ontario
M1V 4Z9
www.honeywell.com/yourhome
Download manual:
Honeywell FocusPro TH5110D Non-Programmable Thermostat Installation Guide
Other manuals:
Honeywell FocusPro TH5110D Non-Programmable Thermostat Instruction Guide
Honeywell FocusPro TH5110D Non-Programmable Thermostat Installation Guide
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…