TH7000 Series
Touch-screen Programmable Thermostat
This manual covers the following models
(Pull thermostat from wallplate and turn over to find model number)
System Types
This thermostat contains a Lithium battery which may contain Perchlorate material. Perchlorate Material—special handling may apply, See www.dtsc.ca.gov/hazardouswaste/perchlorate
Grasp top and bottom of wallplate and pull to remove from thermostat.
Must be installed by a trained, experienced technician
CAUTION: ELECTRICAL HAZARD
Can cause electrical shock or equipment damage. Disconnect power before beginning installation.
MERCURY NOTICE
If this product is replacing a control that contains mercury in a sealed tube, do not place the old control in the trash. Contact your local waste management authority for instructions regarding recycling and proper disposal.
Push excess wire back into the wall opening. Plug wall opening with non-flammable insulation.
Shaded areas below apply only to TH7220.
Conventional Terminal Letters:
Heat Pump Terminal Letters:
Wiring guide—conventional systems
Shaded areas below apply only to TH7220.
See [notes] below
Wiring guide—heat pump systems
Shaded areas below apply only to TH7220.
See [notes] below
Align pins on back of thermostat with slots in wallplate, then push gently until thermostat snaps into place.
Installer setup
Settings & Options (factory default in bold)
Shaded areas below apply only to TH7220.
0120 | Year | 20 | (2000-2099) |
(first two digits) | 21 | (2101-2178) | |
0130 | Year(second two digits) | 12 | (2012) [Other options: 00-99] |
0140 | Month | 6 | [Other options: 1-12] |
0150 | Date | 15 | [Other options: 1-31] |
0160 | Schedule format | 4 | 7-day programming |
0 | Non-programmable | ||
0165 | Restore energy sav- | 0 | Continue using programmed schedule. |
ing schedule | 1 | Restore thermostat program to energy saving settings. | |
0170 | System type | 1 | 1 heat/1 cool conventional |
2 | 1 heat/1 cool heat pump (no aux. heat) | ||
3 | Heat only (2-wire systems) | ||
4 | Heat only with fan | ||
5 6 | Hot water Series 20 system (power to open & close zone valves/normally open zone valves)Cool only | ||
7 | 2 heat/1 cool heat pump (with aux. heat) | ||
8 | 2 heat/2 cool multistage conventional | ||
9 | 2 heat/1 cool multistage conventional | ||
10 | 1 heat/2 cool multistage conventional | ||
0180 | Fan control | 0 | Gas/Oil heat (equipment controls heating fan) |
(heating) | 1 | Electric furnace (thermostat controls heating fan) | |
0190 | Changeover valve | 0 | O/B terminal controls valve in cooling |
(O/B terminal) | 1 | O/B terminal controls valve in heating | |
0200 | Auxiliary heat | 0 | Electric backup heat |
1 | Fossil fuel backup heat | ||
0210 | External fossil | 1 | External fossil fuel kit controls backup heat |
fuel kit | 0 | Thermostat controls backup heat (outdoor sensor required) | |
0220 | 1st stage com- pressor cycle rate | 3 | Recommended for most compressors [Other options: 1, 2, 4, 5 or 6 CPH] |
0230 | 2nd stage com- pressor cycle rate | 3 | Recommended for most compressors [Other options: 1, 2, 4, 5 or 6 CPH] |
0240 | First stage heat | 5 | Gas or oil furnaces of less than 90% efficiency |
cycle rate (CPH= | 1 | Steam or gravity systems | |
cycles per hour) | 3 | Hot water systems & furnaces of 90%+ efficiency | |
9 | Electric furnaces [Other options: 2, 4, 6, 7, 8, 10, 11, 12 CPH] | ||
0250 | Second stage heat | 5 | Gas or oil furnaces of less than 90% efficiency |
cycle rate (CPH) | 1 | Steam or gravity systems | |
3 | Hot water systems & furnaces of 90%+ efficiency | ||
9 | Electric furnaces [Other options: 2, 4, 6, 7, 8, 10, 11, 12 CPH] | ||
0270 | Emergency heat | 9 | Electric emergency heat |
cycle rate (CPH) | 1 | Steam or gravity systems | |
3 | Hot water systems & furnaces of 90%+ efficiency | ||
5 | Gas or oil furnaces of less than 90% efficiency [Other options: 2, 4, 6, 7, 8, 10, 11, 12 CPH] | ||
0280 | Backlight | 0 | Backlight on for approx. 8 seconds after keypress |
1 | Backlight always on low intensity, full bright after keypress(requires 24VAC connection) | ||
0300 | Manual/Auto | 0 | Manual changeover (Heat/Cool/Off) |
changeover | 1 | Automatic changeover (Heat/Cool/Auto/Off) | |
0310 | Auto changeover deadband | 3 | Heat/cool temperature 3 °F apart (1.5 °C) ** See page 11 [Other options: 2-9 (2 °F to 9 °F/1 °C to 5 °C)] |
0320 | Temperature | 0 | Fahrenheit |
display | 1 | Celsius | |
0330 | Daylight savings | 2 1 | Auto-change to daylight savings time (2007 and be- yond, for areas that use the new 2007 DST calendar) Auto-change to daylight savings time (through 2006, and |
0 | for areas that do not use the new 2007 DST calendar) Daylight savings time is turned off | ||
0340 | Remote sensor | 0 | No remote sensor |
1 | Outdoor sensor (display only) | ||
2 | Outdoor control sensor (select heat pumps) ** See page 11 | ||
3 | Indoor sensor | ||
0350 | Heat pump compressor lockout | 0 | No heat pump compressor lockoutOther options: 5, 10, 15, 20, 25, 30, 35, 40, 45, 50, 55, 60 °F (-15 °C to 15.5 °C) |
0360 | Heat pump auxiliary lockout | 0 | No heat pump auxiliary lockoutOther options: 5, 10, 15, 20, 25, 30, 35, 40, 45, 50, 55, 60, 65 °F (-15 °C to 18.5 °C) |
0500 | Furnace filter | 0 | Off |
change reminder | 1 | 10-day run time (about 1 month) | |
2 | 30-day run time (about 3 months) | ||
3 | 60-day run time (about 6 months) | ||
4 | 90-day run time (about 9 months) | ||
5 | 120-day run time (about 1 year) | ||
6 | 365-day run time (about 3 years) | ||
0510 | Humidifier pad | 0 | Off |
change reminder | 1 | 90 calendar days | |
2 | 180 calendar days | ||
3 | 365 calendar days | ||
0520 | UV lamp change | 0 | Off |
reminder | 1 | 365 calendar days | |
0530 | Adaptive Intelligent | 1 | On ** See page 11 |
Recovery™ | 0 | Off | |
0540 | Program periods | 4 | 4 program periods (Wake, Leave, Return, Sleep) |
2 | 2 program periods (Wake, Sleep) | ||
0580 | Compressor protection | 5 | 5 minute compressor off time ** See page 11 [Other options: 0, 1, 2, 3 or 4-minute off time] |
0600 | Heat temperature range stop | 90 | Max. heat temperature setting is 90°F (32°C) [Other options: 40-89°F (4°C to 32°C)] |
0610 | Cool temperature range stop | 50 | Min. cool temperature setting is 50°F (10°C) [Other options: 51-99°F (11°C to 37°C)] |
0640 | Clock format | 12 | 12-hour time (i.e., “3:30 pm”) |
24 | 24-hour time (i.e., “15:30”) | ||
0650 | Extended fan | 0 | Off |
timer (heat) | 90 | Fan runs for 90 seconds after call for heat ends | |
0660 | Extended fan | 0 | Off |
timer (cool) | 90 | Fan runs for 90 seconds after call for cooling ends | |
0670 | Keypad lock | 0 | Keypad unlocked (fully functional) |
1 | Partially locked (access to temperature settings only) | ||
2 | Fully locked | ||
0680 | Heat temperature | 2 | Standard temperature control (recommended) |
control | 1 | Choose if room is warmer than set temperature | |
3 | Choose if room does not reach set temperature | ||
0690 | Cool temperature | 2 | Standard temperature control (recommended) |
control | 1 | Choose if room is cooler than set temperature | |
3 | Choose if room does not reach set temperature | ||
0700 | Temperature display offset | 0 | Thermostat displays actual room temperature [Other options: -3, -2, -1, 1, 2, 3°F offset (-1.5°C to 1.5°C)] |
0710 | RESET | 0 | No reset |
1 | Reset installer options & program schedule to factorydefault (only date and time settings are retained) |
Shaded areas below apply only to TH7220.
CAUTION: EQUIPMENT DAMAGE HAZARD. Compressor protection is bypassed during testing. To prevent equipment damage, avoid cycling the compressor quickly.
Shaded areas below apply only to TH7220.
Please contact your distributor to order replacement parts.
Need Help?
For assistance with this product please visit http://honeywellhome.com or call Customer Care toll-free at 1-800-468-1502
Resideo Inc., 1985 Douglas Drive North
Golden Valley, MN 55422
www.resideo.com
69-2668ES—05 M.S. Rev. 04-19 | Printed in United States
This product is manufactured by Resideo Technologies, Inc., Golden Valley, MN, 1-800-468-1502
© 2019 Resideo Technologies, Inc. The Honeywell Home trademark is used under license from Honeywell International Inc. All rights reserved.
DOWNLOAD MANUAL:
Honeywell Home TH7220U Touch-screen Programmable Thermostat Installation Guide
Honeywell Home TH7220U Touch-screen Programmable Thermostat Installation Guide
Honeywell Home TH7220U Touch-screen Programmable Thermostat Installation Guide
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…