Hexa Controls RT226-J29 modulating digital thermostats are designed to provide Proportional- Integral (PI) modulating control in 2-pipe fan coil units. This thermostat can provide modulating analog 0-10V or 0-20mA control signal.
IMPORTANT SAFETY INFORMATION:
Thermostat Buttons and Switches
The Display
Cooling mode (Proportional-Integral(PI) control cooling)
Example: P-band is 2 °C
The valve cooling output PI and the temperature differential(room temperature and setting temperature) as following picture.
Fan speed instruction
Continuously press
External sensor
When external sensor connected, thermostat will show temperature detected by external sensor. When external sensor removed or open circuit, thermostat will show temperature detected by ambient sensor.
Key lock
In power on status,long press
Room card
If room card is not present, it could set default setting temperature from configuration menu by parameter 9. If room card activate, it could set energy saving temperature from configuration menu by parameter 10.
The configuration menu allows you to set certain thermostat operating characteristics to your system or personal requirements. Switch off the thermostat, long press buttons
Programmable Setting
Long press
Command frame 1: Read the thermostat ON/OFF state
Byte l | Byte 2 | Byte 3 | Byte 4 | Byte 5 | Byte 6 | Byte 7 | Byte 8 |
Thermostat address | 03(reado ut | 00(start address) | 00(start address) | 00(regist er count) | 0l(regist er count) | CRC low | CRC high |
comman | High | Low byte | High byte | Low byte | |||
d code) | byte |
Response Franme Given By Thermostat
Thermostat address | 03 (command code) | 02 (Bytes) | 00(ON/OFF state high byte) | xx(ON/OFF state low byte) | CRC low | CRC high |
Command frame 2: Read the thermostat mode state
Byte l | Byte 2 | Byte 3 | Byte 4 | Byte 5 | Byte 6 | Byte 7 | Byte 8 |
Thermostat | 03(readou | 00(start | 0l(start | 00(register | 0l(registe | CRC | CRC high |
address | t | address) | address) | count) | r count) | low | |
command | High byte | Low byte | High byte | Low byte | |||
code) |
Response Franme Given By Thermostat
Byte l | Byte 2 | Byte 3 | Byte 4 | Byte 5 | Byte 6 | Byte 7 |
Thermostat address | 03 (command code) | 02 (Bytes) | 00(Mode status High byte) | xx(Mode status Low byte) | CRC low | CRC high |
Command frame 3: Read the thermostat fan speed state
Byte l | Byte 2 | Byte 3 | Byte 4 | Byte 5 | Byte 6 | Byte 7 | Byte 8 |
Thermostat | 03(readou | 00(start | 02(start | 00(register | 0l(registe | CRC | CRC high |
address | t | address) | address) | count) | r count) | low | |
command | High byte | Low byte | High byte | Low byte | |||
code) |
Response Frame Given By Thermostat
Byte l | Byte 2 | Byte 3 | Byte 4 | Byte 5 | Byte 6 | Byte 7 |
Thermostat address | 03 (command code) | 02 (Bytes) | 00 Fan speed High byte | xx Fan speed Low byte | CRC low | CRC high |
Command frame 4: Read the thermostat setting temperature
Byte l | Byte 2 | Byte 3 | Byte 4 | Byte 5 | Byte 6 | Byte 7 | Byte 8 |
Thermostat | 03(comman | 00(start | 03(start | 00(register | 0l(registe | CRC low | CRC high |
address | d code) | address) | address) | count) | r count) | ||
High | Low byte | High byte | Low byte | ||||
byte |
Response Frame Given By Thermostat
Byte l | Byte 2 | Byte 3 | Byte 4 | Byte 5 | Byte 6 | Byte 7 |
Thermostat | 03 | 02 | xx (Setting | YY (Setting | CRC low | CRC high |
address | (command | (Bytes | temperature) | temperature) | ||
code) | ) | High byte | Low byte |
Command frame 5: Read the thermostat proportional valve position
Byte l | Byte 2 | Byte 3 | Byte 4 | Byte 5 | Byte 6 | Byte 7 | Byte 8 |
Thermostat address | 03(command code) | 00(start address) High byte | 04(start address) Low byte | 00(registe r count) High byte | 0l(registe r count) Low byte | CRC low | CRC high |
Response Frame Given By Thermostat
Byte l | Byte 2 | Byte 3 | Byte 4 | Byte 5 | Byte 6 | Byte 7 |
Thermostat address | 03 (command | 02 (Bytes) | 05(Proportional valve position) | xx(Proportion al valve | CRC low | CRC high |
code) | High byte | position) | ||||
Low byte |
Command frame 6: Read the thermostat current temperature value
Byte l | Byte 2 | Byte 3 | Byte 4 | Byte 5 | Byte 6 | Byt e 7 | Byte 8 |
Thermostat address | 03(command code) | 00(start address) High byte | 05(start address) Low byte | 00(registe r count) High byte | 0l(registe r count) Low byte | CRC low | CRC high |
Response Frame Given By Thermostat
Byte l | Byte 2 | Byte 3 | Byte 4 | Byte 5 | Byte 6 | Byte 7 |
Thermostat | 03 | 02 | xx(current | YY( current | CRC low | CRC high |
address | (command | (Bytes) | temperature | temperature t | ||
code) | value) | value ) | ||||
High byte | Low byte |
Command frame 7: Read the thermostat external sensor’s temperature
Byte l | Byte 2 | Byte 3 | Byte 4 | Byte 5 | Byte 6 | Byte 7 | Byte 8 |
Thermostat address | 03(command code) | 00(start address) High byte | 06(start address) Low byte | 00(register count) High byte | 0l(register count) Low byte | CRC low | CRC high |
Response Frame Given By Thermostat
Byte l | Byte 2 | Byte 3 | Byte 4 | Byte 5 | Byte 6 | Byte 7 |
Thermostat | 03 | 02 | xx(external | YY( external | CRC low | CRC high |
address | (command | (Bytes) | sensor’s | sensor’s | ||
code) | temperature ) | temperature) | ||||
High byte | Low byte |
Command frame 8: Read the thermostat room card status (DC is 0)
Byte l | Byte 2 | Byte 3 | Byte 4 | Byte 5 | Byte 6 | Byte 7 | Byte 8 |
Thermostat | 03(command | 00(start | 07(start | 00(register | 0l(register | CRC | CRC |
address | code) | address) High byte | address) Low byte | count) High byte | count) Low byte | low | high |
Response Frame Given By Thermostat
Byte l | Byte 2 | Byte 3 | Byte 4 | Byte 5 | Byte 6 | Byte 7 |
Thermostat address | 03 (command code) | 02 (Bytes) | 00( room card status) High byte | x(room card status) Low byte | CRC low | CRC high |
Command frame 9: Read filter dirty status(DC is 2)
Byte l | Byte 2 | Byte 3 | Byte 4 | Byte 5 | Byte 6 | Byte 7 | Byte 8 |
Thermostat address | 03(command code) | 00(start address) High byte | 08(start address) Low byte | 00(register count) High byte | 0l(register count) Low byte | CRC low | CRC high |
Response Frame Given By Thermostat
Byte l | Byte 2 | Byte 3 | Byte 4 | Byte 5 | Byte 6 | Byte 7 |
Thermostat address | 03 (command code) | 02 (Bytes) | xx(filter dirty status) High byte | YY( filter dirty status) Low byte | CRC low | CRC high |
Command frame 10: Read the fan running status
Byte l | Byte 2 | Byte 3 | Byte 4 | Byte 5 | Byte 6 | Byte 7 | Byte 8 |
Thermostat address | 03(command code) | 00(start address) High byte | 09(start address) Low byte | 00(register count) High byte | 0l(register count) Low byte | CRC low | CRC high |
Response Frame Given By Thermostat
Byte l | Byte 2 | Byte 3 | Byte 4 | Byte 5 | Byte 6 | Byte 7 |
Thermostat address | 03 (command code) | 02 (Bytes) | xx(fan status ) High byte | YY( fan status) Low byte | CRC low | CRC high |
Command frame 11: Read the thermostat ON/OFF state
Byte l | Byte 2 | Byte 3 | Byte 4 | Byte 5 | Byte 6 | Byte 7 | Byte 8 |
Thermostat address | 03(reado ut | 00(start address) | 0A(start address) | 00(regist er count) | 0l(regist er count) | CRC low | CRC high |
comman | High | Low byte | High byte | Low byte | |||
d code) | byte |
Response Frame Given By Thermostat
Thermostat address | 03 (command | 02 (Bytes) | 00(ON/OFF state high | xx(ON/OFF state low | CRC low | CRC high |
code) | byte) | byte) |
Command frame 12: Read the thermostat fan speed state
Byte l | Byte 2 | Byte 3 | Byte 4 | Byte 5 | Byte 6 | Byte 7 | Byte 8 |
Thermostat | 03(readou | 00(start | 0B(start | 00(register | 0l(registe | CRC | CRC high |
address | t | address) | address) | count) | r count) | low | |
command | High byte | Low byte | High byte | Low byte | |||
code) |
Response Frame Given By Thermostat
Byte l | Byte 2 | Byte 3 | Byte 4 | Byte 5 | Byte 6 | Byte 7 |
Thermostat address | 03 (command code) | 02 (Bytes) | 00 Fan speed High byte | xx Fan speed Low byte | CRC low | CRC high |
Command frame 13: Read thermostat setting temperature
Byte l | Byte 2 | Byte 3 | Byte 4 | Byte 5 | Byte 6 | Byte 7 | Byte 8 |
Thermostat | 03(comman | 00(start | 0C(start | 00(register | 0l(registe | CRC low | CRC high |
address | d code) | address) | address) | count) | r count) | ||
High | Low byte | High byte | Low byte | ||||
byte |
Response Frame Given By Thermostat
Byte l | Byte 2 | Byte 3 | Byte 4 | Byte 5 | Byte 6 | Byte 7 |
Thermostat | 03 | 02 | xx (Setting | YY (Setting | CRC low | CRC high |
address | (command | (Bytes | temperature) | temperature) | ||
code) | ) | High byte | Low byte |
Command frame 1 (give by upper computer) set the thermostat ON/OFF
Byte l | Byte 2 | Byte 3 | Byte 4 | Byte 5 | Byte 6 | Byte 7 | Byte 8 |
Thermostat address | 06(com mand code) | 00(start address) High byte | 00(start address Low byte) | 00(Setting value high byte) | xx(Setting value low byte) | CRC low | CRC high |
Command frame 2 (give by upper computer) set the mode
Byte l | Byte 2 | Byte 3 | Byte 4 | Byte 5 | Byte 6 | Byte 7 | Byte 8 |
Thermostat address | 06(com mand code) | 00(start address) High byte | 0l(start address Low byte) | 00(Setting value high byte) | xx(Setting value low byte) | CRC low | CRC high |
Command frame 3 ( give by upper computer) set the fan speed
Byte l | Byte 2 | Byte 3 | Byte 4 | Byte 5 | Byte 6 | Byte 7 | Byte 8 |
Thermostat address | 06(com mand code) | 00(start address) High byte | 02(start address Low byte) | 00(Setting value high byte) | xx(Setting value low byte) | CRC low | CRC high |
Command frame 4 ( give by upper computer) set the setting temperature
Byte l | Byte 2 | Byte 3 | Byte 4 | Byte 5 | Byte 6 | Byte 7 | Byte 8 |
Thermostat | 06(com | 00(start | 03(start | xx(Setting | YY(Setting | CRC low | CRC |
address | mand | address) | address | temperature | temperature | high | |
code) | High | Low byte) | high byte) | low byte) | |||
byte |
DOWNLOAD MANUALS:
Hexa Controls RT226-J29 Modulating Digital Thermostat Installation and Operation instructions
Hexa Controls RT226-J29 Modulating Digital Thermostat Installation and Operation instructions
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…