H7711 series thermostats are used to control room temperature in industrial, commercial, and residential environments via controlling electric modulating valve with 0-10VDC (4-20mA) control signal or floating control as well as damper actuator of VAV system. The electronic control technology is adopted, with a green backlit LCD display of working mode
Function:
Model | Output signal | Fan (Single/3-speed) | RS485 Network | Input Control | Remote Sensor | |
Floating | Modulation | |||||
H7711A | Cooling/Heating | √ | √ | |||
H7711AN | Cooling/Heating | √ | √ | √ | ||
H7711B | Cooling/Heating | √ | √ | |||
H7711BN | Cooling/Heating | √ | √ | √ | ||
H7711C | Cooling/Heating | √ | √ | √ | ||
H7711CN | Cooling/Heating | √ | √ | √ | √ | |
H7711D | Cooling/Heating | √ | √ | √ | ||
H7711DN | Cooling/Heating | √ | √ | √ | √ | |
H7711E | Cooling | Heating | √ | √ | √ | |
H7711EN | Cooling | Heating | √ | √ | √ | √ |
H7711F | Heating | Cooling | √ | √ | √ | |
H7711FN | Heating | Cooling | √ | √ | √ | √ |
H7711I | Cooling&Heating | √ | √ | √ | ||
H7711IN | Cooling&Heating | √ | √ | √ | √ | |
H7711K | Cooling&Heating | √ | √ | √ | ||
H7711N | Cooling&Heating | √ | √ | √ | √ |
Parameter table
Parameter | Description | Default | Range | Step |
1 | Power on status (0: Off; 1: On; 2: Hold) | 2 | 0 – 2 | |
2 | Fan speed (0: Single Speed; 1: Three Speed) | 1 | 0 – 1 | |
3 | Fan mode (DA; DB) | 0 | ||
4 | Sensor selection (0: Internal; 1: Remote) | 1 | 0 – 1 | |
5 | Temperature format (0: Celsius; 1: Fahrenheit) | 0 | 0 – 1 | 0.1 |
6 | Temperature calibration | 0 | -20.0 – ﹢20.0 | 0.1 |
7 | Minimum setpoint | 5℃/41℉ | 0 – 99.5 | 0.5 |
8 | Maximum setpoint | 35℃/96 | 0 – 99.5 | 0.5 |
9 | Dead band (from 7711E to 7711K) | 2 | 0 – 10 | 0.5 |
10 | Heating & Auto sleep setpoint | 7℃/45℉ | 0 – 99.5 | 0.5 |
11 | Cooling sleep setpoint | 28℃/82 | 0 – 99.5 | 0.5 |
12 | Comms# (7711XN) | 1 | 1 – 32 | 1 |
13 | Input Signal Mode 0: Invalid 1: Changeover(from 7711A to 7711D) 2: thermostat will be sleep without input signal 3: thermostat will be Off without input signal |
0 |
0 – 3 | |
14 | Heating reset time | 90 sec. | 10 – 300 sec. | 10 sec. |
15 | Cooling reset time | 90 sec. | 10 – 300 sec. | 10 sec. |
16 | Ports mode (0: Modulation & Floating; 1: On/Off) | 0 | 0 – 1 | |
17 | Valve status as turn off (0: Close; 1:Hold; 2: Open ) | 0 | 0 – 2 | |
18 | Port1 Modulation direction(0:10V Open; 1:10V Close) | 0 | 0 – 1 | |
19 | Port1 Modulation minimum signal | 0Bit | 0-128Bit(5V/10mA) | 0.04V/Bit(0.08mA/Bit) |
20 | Port1 Modulation proportional | 2 | 1 – 20 | 0.5 |
21 | Port2 Modulation direction(0:10V Open;1:10V Close) | 0 | 0 – 1 | |
22 | Port2 Modulation minimum Signal | 0 Bit | 0-128Bit(5V/10mA) | 0.04V/Bit(0.08mA/Bit) |
23 | Port2 Modulation proportional | 2 | 1 – 20 | 0.5 |
24 | Port1 Floating minimum time | 1 sec. | 1 – 9 sec. | 1 sec. |
25 | Port1 Floating maximum time | 30 sec. | 10 – 300 sec. | 10 sec. |
26 | Port1 Floating minimum time | 1 sec. | 1-9 sec. | 1 sec. |
27 | Port1 Floating maximum time | 30 sec. | 10 – 300 sec. | 10 sec. |
28 | Disable / Enable bypass PID control ( 0: Disable; 1: Enable ) | 0 | 0 – 1 | |
29 | Override output value when bypass PID control Display output value when enable PID control | 0 – 255 | ||
30 | Override output value when bypass PID control Display output value when enable PID control | 0 – 255 | ||
31 | Input signal management: 0: Input valid 1: Override Input: open 2: Override Input: close | 0 | 0 – 2 | |
32 | Display room temperature or set-point 0: Room temperature 1: Set-Point | 0 | 0 – 1 | |
33 | Configuration external sensor 0: B = 3950; 1: B = 3450; 2: B = 3900 3: User define (via network. default B = 3950) | 0 | 0 – 3 | |
34-38 | N/A | |||
39 | Start temperature of Low temperature protection | 5℃/42℉ | 0-15℃/42-62℉ | 1℃/2℉ |
40 | Stop temperature of Low temperature protection | 7℃/46℉ | 2-17℃/46-66℉ | 1℃/2℉ |
Switch: There is a 5 poles switch on PCB. The meaning is below:
Location | ON | OFF |
1 | 120 ohm Resistance between AB wires | No Resistance between AB wires |
2 | Port 1 Modulation 0 – 20mA | Off |
3 | Port 1 Modulation 0 – 10VDC | Off |
4 | Port 2 Modulation 0 – 20mA | Off |
5 | Port 3 Modulation 0 – 10VDC | Off |
Note: Be sure to connect all the wires as per the wiring diagrams and keep it away from water, mud and other material so as to prevent the unit being spoiled!
All specifications and information within this document are reflecting the information available at the time of going to print and are meant for informational purposes only. Herz Armaturen reserves the right to modify and change products as well as its technical specifications and/or function according to technological progress and requirements. All diagrams are indicative in nature and do not to be complete. It is understood that all images of Herz products are symbolic representations and therefore may visually differ from the actual product. Colors may differ due to the printing technology used. In case of any further questions don’t hesitate to contact your closest HERZ Branch-Office.
HERZ Armaturen Ges.m.b.H.
A-1230 Wien, Richard-Strauss-Strasse 22, A-1230 Vienna, Austria.
DOWNLOAD MANUALS:
HERZ H7711 Digital Thermostat PRODUCT SPECIFICATION SHEET
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…