The P5601UF thermostat is designed for controlling underfloor heating.
Description of Control Elements and Screen (See Fig. 1)
1 – 2 – 6 time slots 3 – time/set temperature 4 – day of the week 5 – mode 6 – UP button 7 – DOWN button | 8 – internal room sensor 9 – on/off button 10 – heating mode 11 – button lock 12 – room temperature 13 – low-temperature protection mode 14 – program mode |
Attention
Before changing the thermostat, disconnect the heating/air-conditioning system from the main power in your flat. This will prevent potential injury by electric current.
Thermostat Placement
Thermostat placement significantly affects its functioning. Choose a location where members of the family spend most of their time, preferably on the inside wall where air circulates freely, with no direct sunlight. Do not place the thermostat in the vicinity of heat sources (such as TV sets, radiators, and fridges), or close to a door (due to frequent shocks or vibrations). If you do not follow these recommendations, the thermostat will not maintain room temperature correctly.
Thermostat Installation (See Fig. 4)
(See Fig. 3)
L | 230 V AC power connection |
N | neutral wire |
N1, L1 | connected device (e.g. heating mat) |
Sensor | floor sensor |
Press the
The thermostat turns on and the screen will activate.
Setting Day and Time
Long press the
Use the up
Then use the up/down arrows to set hours and confirm with
Then use the up/down arrows to set day (1 – Monday to 7 – Sunday) and confirm with
Screen Illumination
Pressing any button activates screen illumination for 5 seconds.
Factory Preset Programmes
The programmable indoor thermostat was designed to be easy to use and require minimal user input.
Icon | Time | Temperature | ||
monday – friday | 1st change | 6:00 | 20 °C | |
2nd change | 8:00 | 15 °C | ||
3rd change | 11:30 | 15 °C | ||
4th change | 12:30 | 15 °C | ||
5th change | 17:00 | 22 °C | ||
6th change | 22:00 | 15 °C |
Icon | Time | Temperature | ||
saturday – sunday | 1st change | 8:00 | 22 °C | |
2nd change | 23:00 | 15 °C |
The entire working day is divided into 6-time slots = 6 temperature changes. Weekend days are divided into 2-time slots = 2 temperature changes (the number of slots cannot be changed). If the factory preset programs do not suit your needs, you can adjust their timing and temperatures. You can also set Saturday and Sunday to be included among working days – with this setting, Saturday and Sunday will also be split into 6-time slots.
Note: In both automated and manual temperature mode, field 3 on the screen automatically alternates between displaying the set temperature and time every 5 seconds – this setting cannot be changed.
Once you have selected the days, press the
Short-Term Manual Change of Temperature
When in automatic mode, where temperature is controlled by the selected programme, it is possible to make a short-term change to the current temperature setting.
Use the up
The screen will display both the
Upon the next scheduled temperature change, the hand icon
The manual change can also be cancelled prematurely by pressing the
Manual Temperature Setting Mode
Advanced Thermostat Settings
Turn off the thermostat by pressing
Long-press the
This will open advanced thermostat settings.
Press the
Symbol on the screen | Function | Setting with up and down arrows |
1.ADJ | Temperature calibration The temperature sensor in the thermostat is calibrated from production. but further calibration can be done to optimise the thermostat further. for instance by com- paring the measured room temperature with a reference thermometer. Example: The thermostat shows room temperature of 22 °C. setting calibration to +1 °C will cause the thermostat to display 23 °C instead. | temperature change from -9.9 °C to +9.9 °C, 0.1 °C resolution |
2.SEN | Temperature sensor selection | IN internal room sensor OUT: underfloor sensor ALL: both sensors Note: if the underfloor sensor is not connected, selecting OUT or ALL will result in “Er” appearing on the screen. |
Symbol on the screen | Function | Setting with up and down arrows |
3. LIT | Limitation of underfloor sensor temperature Sets a temperature limit for the underfloor sensor. | can be set to +5 °C to +60 °C, 1 °C resolution |
4. DIF | Temperature differential The differential (hysteresis) is the difference in temperature required for switching the system on and off. If, for example, you set the temperature in the heating system to 20 °C and differential to 0.4 °C, the thermostat activates heating as soon as room temperature drops to 19.6 °C and switches heating off when temperature reaches 20.4 °C. | can be set to 1 °C to 10 °C, with 1 °C resolution |
5. LTP | Low temperature protection The preset temperature for this mode is 5 °C. | Turned on or off ( |
6. PRG | Days of the week setting | programming off, manual mode only — OFF 5 wo2345rking dgs + 2 weekend days mode12345 6 working dgs + 1 weekend day mode 123456 7 working dgs mode 1234567 |
7. RLE | This function is not available for this thermostat | |
8. DLY | This function is not available for this thermostat |
Symbol on the screen | Function | Setting with up and down arrows |
9. HIT | Highest temperature in the room Setting for the highest possible tempera- ture that can be set on the thermostat. | 35 °C to 95 °C |
AFAC | Factory reset If the thermostat is not working properly, you can reset it to factory settings. | long-press (ca. 5 seconds) the up arrow |
The product is designed to serve reliably for many years if used properly.
Here are some tips for proper operation:
Download Manual
EMOS P5601UF Floor Heating Thermostat User Manual
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…