Assemble tools required as shown below.
YOUR THERMOSTAT REPLACES
Description | 1F85-277 |
Heat Pump (No Aux. or Emergency Heat) | Yes |
Heat Pump (with Aux. or Emergency Heat) | Yes |
Standard Heat & Cooling Systems | Yes |
Two Stage Heat & Two Stage Cool | Yes |
Standard Heat Only Systems | Yes |
Millivolt Heat Only Systems – Floor or Wall Furnaces | Yes |
Standard Central Air Conditioning | Yes |
Gas or Oil Heat | Yes |
Electric Furnace | Yes |
Hydronic (Hot Water) Zone Heat – 2 Wires | Yes |
Hydronic (Hot Water) Zone Heat – 3 Wires | No |
ATTENTION! This product does not contain mercury. However, this product may replace a unit which contains mercury. Do not open mercury cells. If a cell becomes damaged, do not touch any spilled mercury. Wearing non-absorbent gloves, clean up the spilled mercury and place into a container which can be sealed. If a cell becomes damaged, the unit should be discarded. Mercury must not be discarded in household trash. When the unit this product is replacing is to be discarded, place in a suitable container and return to White-Rodgers at 2895 Harrison Street, Batesville, AR 72501 for proper disposal.
CAUTION
To prevent electrical shock and/or equipment damage, disconnect electric power to the system at main fuse or circuit breaker box until installation is complete.
Before removing wires from old thermostat’s switching subbase, label each wire with the terminal designation it was removed from.
WARNING
Do not use on circuits exceeding specified voltage. Higher voltage will damage control and could cause shock or fire hazard.
Do not short out terminals on gas valve or primary control to test. Short or incorrect wiring will damage thermostat and could cause personal injury and/or property damage.
Thermostat installation and all components of the system shall conform to Class II circuits per the NEC code.
This thermostat is configured from the factory to operate a heat/ cool, fossil fuel (gas, oil, etc.), forced air system. It is configured correctly for any system that DOES NOT require the thermostat to energize the fan on a call for heat. If you system is an electric heat or heat-pump system that REQUIRES the thermostat to turn on the fan on a call for heat, locate the ELEC/GAS switch on the back of the thermostat (see fig. 1) and switch it to the ELEC position. This will allow the thermostat to energize the fan immediately on a call for heat. If you are unsure if the heating/ cooling system requires the thermostat to control the fan, contact a qualified heating and air conditioning service person. When the thermostat is configured for Heat Pump, the thermostat will always power the circulator fan on a call for heat in the HEAT mode. The ELEC/GAS switch must be set to match the type of Auxiliary heat your system uses for proper operation in the EMERgency mode.
All wiring diagrams are for typical systems only. Refer to equipment manufacturers’ instructions for specific system wiring information.
2 “AA” alkaline batteries are included in the thermostat at the factory with a battery tag to prevent power drainage. You must remove the battery tag to engage the batteries. If “BATT” is displayed, the batteries are low and should be replaced with fresh “AA” Energizer® alkaline batteries. To replace batteries, press system button to OFF, install the batteries along the top of the base (see Fig. 1). The batteries must be installed with the positive (+) end to the left.
Refer to equipment manufacturers’ instructions for specific system wiring information. You can configure the thermostat for use with the following heat pump system types: HEAT PUMP TYPE 1. Single stage compressor system; gas or electric backup. This thermostat is designed to operate a single-transformer system. If you have a two-transformer system, cut and tape off one transformer. If transformer safety circuits are in only one of the systems, remove the transformer of the system with NO safety circuits. If required, replace remaining transformer with a 75VA Class II transformer. After disconnecting one transformer, the two commons must be jumpered together. Use the terminal output information below to help you wire the thermostat properly for your heat pump system. After wiring, see CONFIGURATION section for proper thermostat configuration.
THERMOSTAT TERMINALS (HEAT PUMP) | ||||||||||
SYSTEM | L | C* | R | W2 | E/W1 | Y2 | Y1 | G | O | B |
Heat Pump 1 | Malfunction Light | 24 Volt (Common) | 24 Volt (Hot) | HP 1 and Emergency 2nd stage HP 2 3rd stage | Emergency Mode 1st stage | No Output | Heat and Cool mode 1st stage (compressor) | Blower/Fan Energized on call for Heat and Cool Set GAS/ELEC switch for Emergency mode | Energized in Cool Mode | Energized in Heat OFF Emergency mode |
Heat Pump 2 | 2nd stage | |||||||||
compressor |
Refer to equipment manufacturers’ instructions for specific system wiring information. You can configure the thermostat for use with either multi-stage electric heat systems or multi-stage gas systems. When configured for electric heat, the G terminal (blower/fan) will be energized on a call for heat. This thermostat is designed to operate a single-transformer system. If you have a two-transformer system, cut and tape off one transformer. If transformer safety circuits are in only one of the systems, remove the transformer of the system with NO safety circuits. If required, replace remaining transformer with a 75VA Class II transformer. After disconnecting one transformer, the two commons must be jumpered together. Use the terminal output information below to help you wire the thermostat properly for your multi-stage system. After wiring, see CONFIGURATION section for proper thermostat configuration.
THERMOSTAT TERMINALS (MULTI-STAGE) | ||||||||||
SYSTEM | L | C* | R | W2 | E/W1 | Y2 | Y1 | G | O | B |
Multi-stage | Malfunction Light | 24 Volt (Common) | 24 Volt (Hot) | Heat Mode 2nd stage | Heat mode 1st stage | Cool Mode 2nd stage | Cool Mode 1st stage | Blower/Fan Energized on call for Cool (and Heat if configured to Electric Heat) | Energized in Cool Mode | Energized in Heat, Off, and Emergency Modes |
To prevent static discharge problems, touch the side of the thermostat to release static build-up before touching any keys.
If at any time during testing your system does not operate properly, contact a qualified service person.
Fan Operation
If your system does not have a G terminal connection, skip to
Heating System.
CAUTION
Do not allow the compressor to run unless the compressor oil heaters have been operational for 6 hours and the system has not been operational for at least 5 minutes.
Emergency System
EMER bypasses the Heat Pump to use the heat source wired to terminal E on the thermostat. EMER is typically used when compressor operation is not desired, or you prefer backup heat only.
To prevent compressor and/or property damage, if the outdoor temperature is below 50°F, DO NOT operate the cooling system.
Cooling System
Before you begin programming your thermostat, you should be familiar with its features and with the display and the location and operation of the thermostat buttons. Your thermostat consists of two parts: the thermostat cover and the base. To remove the cover, pull it straight out from the base. To replace the cover, line up the cover with the base and press until the cover snaps onto the base.
The Thermostat Buttons and Switches
The configuration menu allows you to set certain thermostat operating characteristics to your system or personal requirements. Set the SYSTEM button to OFF, then simultaneously press
The configuration menu table summarizes the configuration options. An explanation of each option follows.
Press SYSTEM to change to the next menu item. To exit the menu and return to the program operation, press RUN. If no keys are pressed within fifteen minutes, the thermostat will revert to normal operation.
Press the SYSTEM button until OFF is displayed, then press the and simultaneously | ||||
INSTALLER/CONFIGURATION MENU | ||||
Step | Press Button(s) | Displayed (Factory Default) | Press or to select | Comments |
1 | System | MS 2 | SS1, HP2, HP1 | Selects Single stage, Multi-stage, or Heat Pump (Single stage or 2-stage) System Configuration |
2 | System | 7d | 5d, 0d | Selects Programs Per Week |
3 | System | PRG 4 | PRG 2 | Selects Programmable Periods (PRG 2 = 2 programmable periods; PRG 4 = 4 programmable periods) |
4 | System | 4:00 HOLD | 0:15 to 4:00 (increments of 15 minutes) | Selects Temporary Program Override Time |
5 | System | EMR (ON) | OFF | Selects Energy Management Recovery OFF or ON |
6 | System | FA | SL | Selects Fast or Slow Cycle Selection |
7 | System | CL (OFF) | CL (ON) | Selects Compressor Lockout CL OFF or ON |
8 | System | CDL (ON) | CDL (OFF) | Selects Backlight Display |
9 | System | FA (ON) | FA (OFF) | Selects Fast Second Stage ON or OFF |
10 | System | 0 FLTR | 50-1950 (increments of 50) | Selects filter replacement run time |
11 | System | 0°F (Room Temperature) | 4 LO to 4 HI | Selects Temperature Display Adjustment 4 LO to 4 HI |
12 | System | °F | °C | Selects temperature display F° or °C selection |
13 | System | AU On | OFF | Selects AUTO Mode ON or OFF |
14 | System | LR (90) | LR 62 to LR89 | Selects Limited HEAT range |
15 | System | LR (45) | LR 46 to LR 82 | Selects Limited COOL range |
16 | System | CA (OFF) | CA (ON) | Feature Not Available |
17 | System | (OFF) | (ON) | Selects Keypad Lockout |
18 | System | 0 | 001 to 999 | Selects Keypad lockout combination number Press System to set code |
19 | Run | Returns to the OFF position |
THERMAL DATA
The system “mode” is selected by pressing the SYSTEM button. Icons on the bottom right corner of the display will indicate the mode: COOL (
Automatic System Changeover
When the thermostat is in the AUTO mode, both the Flame and Snowflake icons are displayed. The thermostat will call for heat or cool depending on the room temperature. The setpoint temperature displayed will be that of the last mode called. If the last system cycle was heat, the HEAT setpoint will be displayed. If the room temperature raises above the HEAT setpoint and the COOL setpoint and a call for cool is required, the temperature displayed will change to be the COOL setpoint.
Second Stage Time Delay
Your thermostat is designed to determine the optimum time to activate the second stage. Simply raising the temperature in heating or lowering it in cooling will not always force thethermostat to bring the second stage on quickly. There is a time delay from 0-30 minutes depending on the performance of the first stage of the system.
EXAMPLE: For the last 2 hours the thermostat is set on 70° and the room temperature is 70° with the equipment using only the first stage of heat. Since the equipment is keeping the temperature within 1° of setpoint, the thermostat will delay second stage for a longer time if you manually raise the temperature or if the room temperature quickly changes. Once the second stage comes on, it will come on sooner the next time there is a difference between the setpoint and the room temperature. The net effect of the staging program is that when the first stage iscapable of making temperature the second stage will delay longer. When the thermostat calculates that first stage cannot make the temperature in a reasonable time, the second stage will come on sooner. This built in function automatically optimizes the use of additional stages of heat or cool.
Manual Operation
Permanent Program Override (HOLD) – With the SYSTEM button set to HEAT or COOL, press the HOLD button once and release. “HOLD” will be displayed. Use or to adjust the temperature. The thermostat will hold the room temperature at the selected setting until you press RUN button to start program operation again.
Temperature Program Override – Press or until the display shows the temperature you want. The thermostat will override current programming and keep the room temperature at the selected temperature for a programmed time period.
“HOLD” will be displayed and flashing. The thermostat will automatically revert to the program after programmed period.
PROGRAMMING YOUR THERMOSTAT
This section will help you plan your thermostat’s program to meet your needs. For maximum comfort and efficiency, keep the following guidelines in mind when planning your program.
Planning Your Program
Look at the factory preprogrammed times and temperatures shown in the sample schedule. If this program will suit your needs, simply press the RUN button to begin running the factory preset program. If you want to change the preprogrammed times and temperatures, follow these steps. Determine the time periods and temperatures for your program. You can program four or two periods for each day (see Configuration menu, item 3). You may use the same heating and cooling temperatures for consecutive time periods. You can choose start times, heating temperatures, and cooling temperatures independently (for example, you may select 5:00 AM and 70° as the weekday 1st period heating start time and temperature and also choose 7:00 AM and 76° as the weekday 1st period cooling start time and temperature). Use the table to plan your program time periods and the temperatures you want during each period. Fill in the complete table to have a record of your programs.
SAMPLE
Heating/Cooling Schedule Plan (Factory Program)
Period | ALL DAYS OF THE WEEK | ||
Start Time | Temperature | ||
HEAT | 1ST | 6:00 AM | 70 F |
2ND | 8:00 AM | 62 F | |
3RD | 5:00 PM | 70 F | |
4TH | 10:00 PM | 62 F | |
COOL | 1ST | 6:00 AM | 78 F |
2ND | 8:00 AM | 85 F | |
3RD | 5:00 PM | 78 F | |
4TH | 10:00 PM | 82 F |
Set Current Time and Day
Enter Heating Program
Heating/Cooling Schedule Plan
PERIOD 1 | PERIOD 2 | PERIOD 3 | PERIOD 4 | |||||||||||||
HEAT | COOL | HEAT | COOL | HEAT | COOL | HEAT | COOL | |||||||||
Time | Temp | Time | Temp | Time | Temp | Time | Temp | Time | Temp | Time | Temp | Time | Temp | Time | Temp | |
Mon | ||||||||||||||||
Tues | ||||||||||||||||
Wed | ||||||||||||||||
Thur | ||||||||||||||||
Fri | ||||||||||||||||
Sat | ||||||||||||||||
Sun |
Enter Cooling Program
If the outside temperature is below 50°F, disconnect power to the cooling system before programming. Energizing the air conditioner compressor during cold weather may cause personal injury or property damage.
CHECK YOUR PROGRAMMING
Follow these steps to check your thermostat programming one final time before beginning thermostat operation.
Reset Operation
If a voltage spike or static discharge blanks out the display or causes erratic thermostat operation, you can reset the thermostat by removing the wires from terminals R and C and removing batteries for 2 minutes. After resetting the thermostat, replace the wires and batteries. If the thermostat has been reset and still does not function correctly, contact your heating/cooling service person or place of purchase.
Symptom | Possible Cause | Corrective Action |
No Heat/No Cool/No Fan (common problems) | 1. Blown fuse or tripped circuit breaker. 2. Furnace power switch to OFF. 3. Furnace blower compartment door or panel loose or not properly installed. | Replace fuse or reset breaker. Turn switch to ON. Replace door panel in proper position to engage safety interlock or door switch. |
No Heat
10 | 1. Pilot light not lit. 2. SYSTEM button not set to HEAT.
3. Loose connection to thermostat or system. 4. Furnace Lock-Out Condition. Heat may also be intermittent.
5. Heating system requires service or thermostat requires replacement. | Re-light pilot. Press SYSTEM button to HEAT and raise setpoint above room temperature. Verify thermostat and system wires are securely attached. Many furnaces have safety devices that shut down when a lock-out condition occurs. If the heat works intermittently contact the furnace manufacturer or local service person for assistance. Diagnostic: Press SYSTEM button to HEAT and raise the setpoint above room temperature. Within a few seconds the thermostat should make a soft click |
Symptom | Possible Cause | Corrective Action |
No Heat (continued) | 5. Heating system requires service or thermostat requires replacement. (continued) | sound. This sound usually indicates the thermostat is operating properly. If the thermostat does not click, try the reset operation listed above. If the thermostat does not click after being reset contact your heating and cooling service person or place of purchase for a replacement. If the thermostat clicks, contact the furnace manufacturer or a service person to verify the heating is operating correctly. |
No Cool | 1. SYSTEM button not pressed to COOL.
2. Loose connection to thermostat or system. 3. Cooling system requires service or thermostat requires replacement. | Press SYSTEM button to COOL and lower setpoint below room temperature. Verify thermostat and system wires are securely attached. Same procedure as diagnostic for No Heat condition except set the thermostat to COOL and lower the setpoint below the room temperature. There may be up to a five minute delay before the thermostat clicks in Cooling. |
Heat, Cool or Fan Runs Constantly | 1. Possible short in wiring. 2. Possible short in thermostat. 3. Possible short in heat/cool/fan system. 4. FAN Switch set to Fan On. | Check each wire connection to verify they are not shorted or touching together. No bare wire should stick out from under terminal screws. Try resetting the thermostat as described above. If the condition persists the manufacturer of your system or service person can instruct you on how to test the Heat/Cool system for correct operation. If the system operates correctly, replace the thermostat. |
Furnace (Air Conditioner) Cycles Too Fast or Too Slow (narrow or wide temperature swing) | 1. The location of the thermostat and/or the size of the Heating System may be influencing the cycle rate. | Digital thermostats normally provide precise tem- perature control and may cycle faster than some older mechanical models. A faster cycle rate means the unit turns on and off more frequently but runs for a shorter time so there is no increase in energy use. If you would like to increase the cycle time, choose SL for slow cycle in the menu, step 4. If an accept- able cycle rate is not achieved as received or by choosing slow cycle, contact a local service person for additional suggestions. |
Thermostat Setting & Thermostat Thermometer Disagree | 1. Thermostat thermometer setting requires adjustment. | The thermometer can be adjusted +/- 4 degrees. See Temperature Display Adjustment in the Configu- ration Menu section. |
Blank Display and/or Keypad Not Responding | 1. Voltage spike or static discharge. | Use the Reset Operation at top of previous page. |
Heat Setpoint will not Respond to the Temperature Up Key | 1. The desired setpoint conflicts with the setpoint of the COOL mode. | Change system mode to COOL. Raise the Cool setpoint. Return to HEAT mode and set desired temperature. |
Cool Setpoint will not Respond to the Temperature Down Key | 1. The desired setpoint conflicts with the setpoint of the HEAT mode. | Change system mode to HEAT. Lower the Heat setpoint. Return to COOL mode and set desired temperature. |
Forgot Keypad Lockout Code | CAUTION: This resets the thermostat to factory default settings of the configuration menu. After performing this reset, the thermostat will require configuration again. Be sure that you know the required configuration settings before resetting. With the thermostat in any mode, press and at the same time to enter the configuration menu at the point where the lockout code is to be entered. Press |
Symptom | Possible Cause | Corrective Action |
Forgot Keypad Lockout Code (continued) | and and SYSTEM button at the same time to reset the lockout code, unlock the keypad and reset all configuration menu settings. | |
Why won’t my 2nd or 3rd stage come on? | First stage is keeping up with demand. | Your thermostat is designed to determine the optimum time to activate the second stage. Simply raising the temperature in heating or lowering it in cooling will not always force the thermostat to bring the second stage on quickly. There is a time delay from 0-30 minutes depending on the performance of the first stage of the system. |
Symptom | Corrective Action |
My thermostat is reading in Celsius. How do I change it to Fahrenheit? | Your thermostat display can be set to display temperature in Fahrenheit or Celsius. This option can be set in the INSTALLER/CONFIGURATION MENU of your thermostat. See page 6 step 12. |
Do I have to program a stop time for each program period? | There is no need to select a time to stop a programming period. Starting a new programming period will stop the previous program period. |
My thermostat does not follow it’s program. What should I do? | Unless the thermostat appears to be damaged it will follow the program that is in the memory. The most common reason a thermostat will appear not to be following the program is a programming error. Verify that the AM or PM settings are correct for each period. Also verify that the Day of the week is set correctly. Models with EMR (Energy Management Recovery) start early to make the temperature they are programmed for by the time specified in the program. See the CONFIGURATION MENU on page 6 step 3. |
Between heating and cooling seasons, I want to turn my system off. Will this change my program? | Any time you wish to turn your system off, simply press the SYSTEM button until “OFF” is displayed. This will not affect your thermostat’s programming in any way. To turn the system back on, press the SYSTEM button to HEAT or COOL and press RUN. The system will begin operating according to the current thermostat program. See under OPERATION page 8 & 9. |
My display light does not work. Can it be fixed or replaced? | Because it is soldered to the circuit board it is not possible to repair or replace. |
Do I have to reprogram my thermostat after I change the batteries? | No. This thermostat has permanent memory, although you will have to reset your clock. |
My setpoint temperature is flashing. What does that mean? | When the thermostat compressor time delay occurs it will flash the setpoint for about five minutes. This is intended to help protect the compressor from short cycling. |
How can I get a copy of the Operating Manual for my thermostat? | Visit our website at www.white-rodgers.com for operating manuals. |
My program or configuration menu is all messed up, how do I start from the beginning? | You can perform software reset by pressing and SYSTEM buttons simultaneously when SYSTEM mode is OFF. See “Forget Keypad Lockout Code” under “TROUBLESHOOTING” for details. |
Download Manual: EMERSON White Rodgers 1F85-277 Universal Thermostat INSTALLATION INSTRUCTIONS
EMERSON White Rodgers 1F85-277 Universal Thermostat INSTALLATION INSTRUCTIONS
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…