Operator: Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE.
Your new 5-Day/1-Day/1-Day Digital Thermostat uses the tech-nology of a solid-state microcomputer to provide precise time/temperature control. This thermostat offers you the flexibility to design heating and cooling programs that fit your needs.
CAUTION To prevent electrical shock and/or equipment damage, disconnect electric power to system at main fuse or circuit breaker box until installation is complete.
WARNING
Electrical Rating:
APPLICATIONS
For use with the following Class II systems:
DO NOT USE WITH:
REMOVE OLD THERMOSTAT
ATTENTION!
This product does not contain mercury. However, this product may replace a unit which contains mercury.
Do not open mercury cells. If a cell becomes damaged, do not touch any spilled mercury. Wearing nonabsorbent gloves, take up the spilled mercury and place into a container which can be sealed. If a cell becomes damaged, the unit should be discarded. Mercury must not be discarded in household trash. When the unit this product is replacing is to be discarded, place in a suitable container. Refer to www.thermostat-recycle.org for location to send the product containing mercury.
ATTACH THERMOSTAT BASE TO WALL
ELECTRIC/GAS JUMPER (Fan Option)
Read the following information before clipping the nonelectric heat jumper. If you are unsure of your application, contact a qualified service person.
If your emergency or auxiliary system will energize the blower, then jumper, W904, on the thermostat base must be cut (see fig. 1).
If your emergency or auxiliary heat system requires that the thermostat energize the fan circuit, do not cut jumper W904.
OPTIONAL BATTERIES
With two “AA” batteries installed, your thermostat will maintain time and continuously display the temperature during a loss of AC power. Installed batteries will also allow programming prior to installation. For best results, use new premium brand batteries such as Duracell® or Energizer®.
ENERGY MANAGEMENT RECOVERY (EMR)
When the EMR feature is activated the thermostat’s microcomput-er calculates the time it will take to change the room temperature to the next heat or cool program setting. Then the thermostat will start the system before the next programmed period so that the desired temperature is reached at or near the beginning of the period (the thermostat calculates 15 minutes for every 1°F temperature change). This minimizes the use of auxiliary stages during the transition period to reduce energy costs.
For example: The thermostat is programmed to provide an over-night heating temperature of 66°F, and during the next program period, beginning at 6:00 AM, the programmed temperature is 70°F. With EMR activated, the thermostat will automatically start the heating system at 5:00 AM, so that the programmed temperature of 70°F is reached by about 6:00 AM.
If the overnight room temperature drops only to 68F°, the ther-mostat will start the system at 5:30 to reach the programmed temperature of 70°F at 6:00.
The thermostat is shipped with the EMR feature active, which means that the thermostat will start the heating system before the beginning of the next program period. This feature provides better efficiency by allowing gradual temperature changes using only the first stage of heat.
To deactivate the EMR function, see the Configuration menu on Page 5). The thermostat will then wait until the programmed time to start the system for a temperature change.
O/B TERMINAL SWITCH SELECTION
The O/B switch on this thermostat is factory set to the “O” position. This will accommodate the majority of heat pump applications, which require the changeover relay to be energized in COOL. If the thermostat you are replacing or the heat pump being in-stalled with this thermostat requires a “B” terminal, to energize the changeover relay in HEAT, the O/B switch must be moved to the “B” position.
If at any time during testing your system does not operate properly, contact a qualified service person.
Turn on power to the system.
Fan Operation
If your system does not have a G terminal connection, skip to Heating System.
Heating System
Emergency System
EMER bypasses the Heat Pump to use the heat source wired to terminal E on the thermostat. EMER is typically used when compressor operation is not desired, or you prefer back-up heat only.
Cooling System
CAUTION To prevent compressor and/or property damage, if the outdoor temperature is below 50°F, DO NOT operate the cooling system.
CAUTION Do not allow the compressor to run unless the compressor oil heaters have been operational for 6 hours and the system has not been operational for at least 5 minutes.
Before you begin programming your thermostat, you should be familiar with its features and with the display and the location and operation of the thermostat buttons. Your thermostat consists of two parts: the thermostat cover and the base. To remove the cover, pull it straight out from the base. To replace the cover, line up the cover with the base and press until the cover snaps onto the base.
Other than
The Thermostat Buttons and Switches
The configuration menu allows you to set certain thermostat operating characteristics to your system or personal requirements.
Press RUN to make sure the thermostat is in the run program mode, then press PRGM and RUN at the same time to enter the configuration menu. The display will show the first item in the configuration menu.
The configuration menu chart summarizes the configuration options. An explanation of each option follows.
Press HOLD to change to the next menu item or press TIME to go backwards to the previous item in the menu. To exit the menu and return to the program operation, press RUN. If no keys are pressed within fifteen minutes, the thermostat will revert to normal operation.
Select Temporary Hold Time – The thermostat can hold any temperature you set it to for the amount of time you select on this option. Your choices are 0:00 to 8:00 hours in 15 minute increments. 0:00 disables the function
Example: Using the Temporary Hold Function
Select FA or SL (Fast or Slow) Heat Pump stage Cycle Rate
The FA setting is used to produce shorter heating cycles. The SL setting produces a longer heating/cooling cycle. Both settings produce very accurate temperature control and can be set to your personal preference. FA cycles the system just under .75°F and the SL setting cycles at approximately 1.2°F.
Select FA or SL (Fast or Slow) Auxiliary or Emergency Cycle Rate
The FA setting is frequently used for gas, oil or electric heat. The SL setting produces a longer heating cycle. Both settings produce very accurate temperature control and can be set to your personal preference. FA cycles the system just under .6°F and the SL setting cycles at approximately 1.°F.
Select backlit display – The display backlight improves display contrast in low lighting conditions. Selecting backlight ON will keep the light on continuously. Selecting OFF will keep the light off.
Step | Press Button(s) | Displayed (Factory Default) | Press | COMMENTS |
1 | PRGM and RUN | HOLD (0:00) | 0 to 8 hrs (in 15 minute increments) | Select temporary Hold time |
2 | HOLD* | (SL) | FA | Select FA or SL (Fast or Slow) pump cycle rate |
3 | HOLD* | EMER (FA) | SL | Select FA or SL (Fast or Slow) Auxiliary and Emergency Aux heating cycle rate |
4 | HOLD* | d-L (on) | OFF | Select display backlight OFF or ON |
5 | HOLD* | E (on) | OFF | Select Energy Management Recovery OFF or ON |
6 | HOLD* | Filter (000) | 0 to 1950 hours (in 50 hour increments) | Select filter replacement run time |
7 | HOLD* | LOC (OFF) | on | Select Compressor lockout OFF or ON |
8 | HOLD* | 0 HI (0) | 4 LO to 4 HI | Select temperature display adjustment higher or lower |
9 | HOLD* | (F) | C | Select temperature display to F or C |
10 | HOLD* | FA (on) | OFF | Select fast second stage ON or OFF |
11 | RUN | Returns to normal operation |
Note: Press HOLD to advance to next item or TIME to move backwards to previous item
Select Energy Management Recovery OFF or ON
Energy Management Recovery (EMR) causes the thermostat to start heating or cooling early to make the building temperature reach the program setpoint at the time you specify.
Select filter replacement run time
The thermostat will display FLTR after a set time of operation. This is a reminder to change or clean your air filter. This time can be set from 0 to 1950 hours in 50 hour increments. A selection of 000 will cancel this feature. When FLTR is displayed, you can clear it by pressing HOLD and RUN at the same time. This resets the timer and starts counting the hours until the next filter change. Contact your heat pump manufacturer for a specific replacement/maintenance interval.
Select Compressor Lockout LOC OFF or ON
Selecting LOC ON will cause the thermostat to wait 5 minutes before turning on the compressor if the heating and cooling system loses power. It will also wait 5 minutes minimum between cooling or heating cycles. This is intended to help protect the compressor from short cycling. Some newer compressors already have a time delay built in and do not require this feature. Your compressor manufacturer can tell you if the lockout feature is already present in their system. When the thermostat compressor time delay occurs it will flash the Snowflake and Flame icons for about five minutes.
Select Temperature Display Adjustment 4 LO to 4 HI
Allows you to adjust the room temperature display up to 4°higher or lower. Your thermostat was accurately calibrated at the factory but you have the option to change the display temperature to match your previous thermostat. The current or adjusted room temperature will be displayed on the right side of the display.
Select F° or C° Readout
Changes the display readout to Celsius or Fahrenheit as required. The current room tem-perature will be displayed on the right side of the display.
Select Fast second stage
In the RUN mode, if the tem-perature is manually raised by 3°F ( 2°C) or more above room temperature using
This section will help you plan your thermostat’s program to meet your needs. For maximum comfort and efficiency, keep the following guidelines in mind when planning your program.
Planning Your Program
Look at the factory preprogrammed times and temperatures shown in the sample schedule. If this program will suit your needs, simply press the RUN button to begin running the factory preset program.
If you want to change the preprogrammed times and tempera-tures, follow these steps.
Determine the time periods and temperatures for your program. You must program four periods for each day. However, you may use the same heating and cooling temperatures for consecutive time periods. You can choose start times, heating temperatures, and cooling temperatures independently (for example, you may select 5:00 AM and 70° as the weekday 1st period heating start time and temperature, and also choose 7:00 AM and 76° as the weekday 1st period cooling start time and temperature). Use the table to plan your program time periods and the tem-peratures you want during each period. Fill in the complete table to have a record of your programs.
SAMPLE
Heating/Cooling Schedule Plan (Factory Program)
Period | WEEKDAYS (5 Day) | SATURDAY (1 Day) | SUNDAY (1 Day) | ||||
Start Time | Temp | Start Time | Temp | Start Time | Temp | ||
HEAT | 1ST | 6:00 AM | 70°F | 6:00 AM | 70°F | 6:00 AM | 70°F |
2ND | 8:00 AM | 62°F | 8:00 AM | 62°F | 8:00 AM | 62°F | |
3RD | 5:00 PM | 70°F | 5:00 PM | 70°F | 5:00 PM | 70°F | |
4TH | 10:00 PM | 62°F | 10:00 PM | 62°F | 10:00 PM | 62°F | |
COOL | 1ST | 6:00 AM | 78°F | 6:00 AM | 78°F | 6:00 AM | 78°F |
2ND | 8:00 AM | 85°F | 8:00 AM | 85°F | 8:00 AM | 85°F | |
3RD | 5:00 PM | 78°F | 5:00 PM | 78°F | 5:00 PM | 78°F | |
4TH | 10:00 PM | 82°F | 10:00 PM | 82°F | 10:00 PM | 82°F |
Heating/Cooling Schedule Plan
Period | WEEKDAYS (5 Day) | SATURDAY (1 Day) | SUNDAY (1 Day) | ||||
Start Time | Temp | Start Time | Temp | Start Time | Temp | ||
HEAT | 1ST | ||||||
2ND | |||||||
3RD | |||||||
4TH | |||||||
COOL | 1ST | ||||||
2ND | |||||||
3RD | |||||||
4TH |
Set Current Time and Day
Enter Heating Program
Enter Cooling Program
CAUTION If the outside temperature is below 50°F, disconnect power to the cooling system before programming. Energizing the air conditioner compressor during cold weather may cause personal injury or property damage.
Follow these steps to check your thermostat programming one final time before beginning thermostat operation.
NOTE: Batteries are not required to keep your programming or menu data. With two optional “AA” batteries installed, your thermostat will maintain time and continuously display the tem-perature during a loss of AC power. Installed batteries will also allow programming prior to installation.
YOUR THERMOSTAT IS NOW PROGRAMMED AND READY TO PROVIDE MAXIMUM COMFORT AND EFFICIENCY!
Reset Operation
If a voltage spike or pressing
Symptom | Possible Cause | Corrective Action |
No Heat/No Cool/No Fan (common problems) | 1. Blown fuse or tripped circuit breaker. 2. Furnace power switch to OFF. 3. Furnace blower compartment door or panel loose or not properly installed. | Replace fuse or reset breaker. Turn switch to ON. Replace door panel in proper position to engage safety inter- lock or door switch. |
No Heat | 1. System Switch not set to Heat.
2. Loose connection to thermostat or system.
3. Heating System requires service or thermo- stat requires replacement. | Set System Switch to Heat and raise setpoint above room temperature. Verify thermostat and system wires are securely attached. Diagnostic: Set System Switch to Heat and raise the setpoint above room temperature. Within a five minutes the thermostat should make a soft click sound. This sound usually indicates the thermostat is operating properly. If the thermostat does not click, try the reset operation listed above. If the thermostat does not click after being reset, contact your heating and cooling service person or place of purchase for a replace- ment. If the thermostat clicks, contact the furnace manu- facturer or a service person to verify the heating system is operating correctly. |
No Cool | 1. System Switch not set to Cool. 2. Loose connection to thermostat or system. 3. Cooling System requires service or thermo- stat requires replacement. | Set System Switch to Cool and lower setpoint below room temperature. Verify thermostat and system wires are securely attached. Same procedure as diagnostic for No Heat condition except set the thermostat to Cool and lower the setpoint below the room temperature. There may be up to a five minute delay before the thermostat clicks in Cooling if the compressor lock- out option is selected in the configuration menu (Item 7). |
Heat, Cool or Fan Runs Constantly. | 1. Possible short in wiring. 2. Possible short in thermostat. 3. Possible short in Heat/Cool/Fan system. 4. Fan Switch set to Fan On. | Check each wire connection to verify they are not shorted or touching together. No bare wire should stick out from under terminal screws. Try resetting the thermostat as described below. If the condition persists, the manufacturer of your system or service person can instruct you on how to test the Heat/Cool system for correct operation. If the system operates correctly, replace the thermostat. |
Furnace Cycles Too Fast or Too Slow (narrow or wide temperature swing) | 1. The location of the thermostat and/or the size of the Heating System may be influencing the cycle rate. | Item 2 in the Configuration Menu is the adjustment that controls the cycle rate. If an acceptable cycle rate is not achieved using the FA (Fast) or SL (Slow) adjustment contact a local service person for additional suggestions. |
Cooling Cycles Too Fast or Too Slow (narrow or wide temperature swing) | 1. The location of the thermostat and/or the size of the Cooling System may be influencing the cycle rate. | The cycle rate for cooling is fixed and can not be adjusted. Contact a local service person for suggestions. |
Thermostat Setting and Thermometer Disagree | 1. Thermostat thermometer setting requires adjustment. | The thermometer can be adjusted +/- 4 degrees as listed in item 8 of the Configuration Menu. No other adjustment is possible. |
Clock Loses or Gains Time | 1. Loss of power to thermostat. | The thermostat will maintain its program in memory even with no power but the clock time will be incorrect when power is restored. See No Heat/No Cool/No Fan (common problems) above for items to check in the system. |
Heat or Cool Starts Early | 1.EMR activated | See Configuration Menu (Item 5). |
Thermostat Does Not Follow Program | 1. AM or PM set incorrectly in program. 2. AM or PM set incorrectly on the clock. 3. Voltage spike or static discharge. | Check current clock and program settings including the AM or PM designations for each time period. If a voltage spike or static discharge occurs use the Reset Operation listed above. |
Blank Display and/or Keypad Not Responding | 1. Voltage Spike or Static Discharge. | If a voltage spike or static discharge occurs use the Reset Operation listed above. |
White-Rodgers is a business of Emerson Electric Co.
The Emerson logo is a trademark and service mark of Emerson Electric Co.
white-rodgers.com
emersonclimate.com
Download manual: EMERSON White-Rodgers 1F82-261 Programmable Electronic Digital Heat Pump Thermostat
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…