| Step | 1F81-261 Press Button(s) | 1F83-261 Press Button(s) | Displayed (Factory Default) | Press | or | to select: | COMMENTS |
| 1 | PRGM and RUN | N/A | HOLD (0:00) | 0 to 8 hrs (in 15 minute increments) | Select temporary Hold time | ||
| 2 | HOLD* | Set SYSTEM switch to OFF and Press and | (FA) | SL | Select FA or SL (Fast or Slow) heating cycle rate | ||
| 3 | HOLD* | and | d-L (ON) | OFF | Select display backlight OFF or ON | ||
| 4 | HOLD* | N/A | E (ON) | OFF | Select Energy Management Recovery OFF or ON | ||
| 5 | HOLD* | and | Filter (000) | 0 to 1950 hours (in 50 hour increments) | Select filter replacement run time | ||
| 6 | HOLD* | and | LOC (OFF) | ON | Select compressor lockout OFF or ON | ||
| 7 | HOLD* | and | 0 HI (0) | 4 LO to 4 HI | Select temperature display adjustment higher or lower | ||
| 8 | HOLD* | and | °(F) | °C | Select temperature display to °F or °C | ||
| 9 | HOLD* | Set SYSTEM switch to HEAT or COOL | 1 + 2 FA
(ON) | OFF | Select ON to start 2nd stage immediately when the setpoint is manually raised more than 3° F in HEAT or lowered more than 3° F in COOL from room temperature | ||
| 10 | RUN | N/A | Returns to normal operation | ||||
* Press HOLD to advance to next item or TIME to move backward to the previous item
NOTE
The following wiring diagrams show typical terminal identification and wiring. For proper installation, refer to the original manufacturer’s instructions.
Relay contacts shown are thermostatically operated.
Reset Operation: 1F81-261
If a voltage spike or static discharge blanks out the display or causes erratic thermostat operation, you can reset the thermostat by pressing , and TIME at the same time. This also resets the factory defaults to the configuration menu and program. If the thermostat has power, has been reset and still does not function correctly, contact your heating/cooling service person or place of purchase.
Reset Operation: 1F83-261
If a voltage spike or static discharge blanks out the display or causes erratic thermostat operation, you can reset the thermostat by pressing , and move the SYSTEM switch from OFF to HEAT at the same time. This also resets the factory defaults to the configuration menu. If the thermostat has power, has been reset and still does not function correctly, contact your heating/cooling service person or place of purchase.
* The 24 Volt neutral connection to terminal C on the thermostat is not required if you replace the batteries once a year with fresh “AA” Energizer® alkaline batteries.
Download Manual: EMERSON White Rodgers 1F81 Programmable Heat Pump Thermostat CONFIGURATION AND TYPICAL WIRING DIAGRAMS
Bad Ragaz Casino No Deposit Bonus Codes For Free Spins 2026 Details pertaining to the…
Online Slot Games For Money Playing online casinos UK on a mobile device Spin the…
Prime Fortune Casino No Deposit Bonus Codes For Free Spins 2026 Fantasy sports became a…
Online Casino Real Money Uk No Deposit Get ready to play the most realistic card…
Sin88 Casino No Deposit Bonus Codes For Free Spins 2026 This can be part of…
How To Always Win Blackjack Casino offer terms and conditions in UK Here is how…