Installation Instructions for: | |
Horizontal | 1D56-310, -347 |
Snap-Action | 1D56W-347 |
Vertical | 1E56-301, -444 |
Sealed Mercury Cell | 1E56W-444 |
Horizontal | 1F56-301 |
Sealed Mercury Cell | 1F56-306, -444 |
1F56W-444 |
System | Models |
Standard Heating & Cooling Systems – 4 or 5 wires Standard Heat Only Systems Standard Central Air Conditioning Gas or Oil Heat Hydronic (Hot Water) Zone Heat – 2 wires |
All Models |
Electric Furnace Heat Pump (No Aux or Emergency Heat) | 1D56-347, 1D56W-347, 1E56-444, 1E56W-444, 1F56-306, -444, 1F56W-444 |
Heat Pump (with Aux or Emergency Heat) Baseboard Electric Heating or Line Voltage (120 or 240 Volt) Millivolt Heat Only Systems – Floor or Wall Furnaces Hydronic (Hot Water) Zone Heat – 3 wires |
None |
Assemble tools required: power drill, flat blade screwdriver, wire cutter/stripper, level. Failure to follow and read all instructions carefully before installing or operating this control could cause personal injury and/or property damage.
To prevent electrical shock and/or equipment damage, disconnect electrical power to the system at the main fuse or circuit breaker until installation is complete. Before removing wires from old thermostat’s switching subbase, label each wire with the terminal designation it was removed from.
Make a note here of the anticipator setting on the old thermostat for future reference and use in step 5. The heat anticipator pointer, if adjustable, will be set at one of a series of numbers representing the current rating of the primary control in your furnace. The number will be one of the following: .2, .4, .8, etc. or 0.2, 0.4, 0.8, etc.
Do not use on circuits exceeding specified voltage. Higher voltage will damage control and could cause shock or fire hazard. Do not short out terminals on gas valve or primary control to test. Short or incorrect wiring will damage the thermostat and could cause personal injury and/ or property damage. Thermostat installation and all components of the system shall conform to Class II circuits per the NEC code.
Hole in Wall Mounting Screw reversing valve connection energized in Heating, attach it to B (see Fig. 4). This thermostat will not provide multi-stage heating or cooling.
|
Mount Thermostat Base: Gently push excess wire back into the wall opening and plug hole with a fire-resistant material, such as fiberglass insulation to prevent drafts from affecting the thermostat Mount the thermostat base to the subbase using the three captive screws on the thermostat base. Tighten the screws securely. Remove the paper tag from the plastic contact cover. Proceed to Step #5.
Set the anticipator to match the setting of your old thermostat you noted in Step 3, or, the anticipator should be set to match the current rating stamped on your main heating control. The heat anticipator is adjustable from 0.15 to 1.2 amps. Adjust the anticipator by rotating the contact arm The anticipator setting is indicated by the numbers on the base that the pointer points to. If you are unsure where to set the anticipator contact the heater manufacturer for a recommended setting. Move the pointer counterclockwise to\ lengthen heating system cycles; move clockwise to shorten heating cycles. Adjustments should not be greater than 1/2 marking at a time. Snap on Cover: Carefully align the cover with the base and snap the cover onto the base.
This thermostat is easy to operate. After power is turned on, use the system switch to select either heating or cooling, or to turn the heating/cooling system off. Use the fan switch to control fan operation. When the fan switch is in the AUTO position, the fan will cycle with the heating or cooling system (the fan will not run if the system switch is in the OFF position and the fan switch is in the AUTO position). When the fan switch is in the N position, the fan will run continuously, regardless of system switch position (even if he system switch is set to OFF, the fan will run if the fan switch is in the ON position).
Figure 2. Typical wiring for single transformer heating/cooling system
Figure 3. Typical wiring for two-transformer heating/cooling system
Symptom | Possible Cause | Corrective Action |
No Heat/No Cool/No Fan (common problems) | 1. Blown fuse or tripped circuit breaker. 2. Furnace power switch to OFF. 3. Furnace blower compartment door or panel loose or not properly installed. | Replace fuse or reset breaker. Turn switch to ON. Replace door panel in proper position to engage safety interlock or door switch. |
No Heat | 1. Pilot light not lit. 2. Broken or melted anticipator wire.
3. Loose connection to thermostat or system. 4. Thermostat or heating system requires replacement or service.
5. System Switch not set to Heat. | Re-light pilot. Excessive current or dead short in system. Have a qualified service person check the system before replacing thermostat. Verify thermostat and system wires are securely attached. Your furnace manufacturer or service person can describe how to test the heating system to verify it is operating correctly. If the heating system is capable of operation and the no heat condition persists, replace the thermostat. Set System Switch to Heat and raise temp above room temp. |
Intermittent Heat | 1. Furnace Lock-Out Condition | Many furnaces have safety devices that shut the system down when a lock-out condition occurs. If the heat works intermittently contact the furnace manufacturer or local service person for assistance. |
No Cool | 1. Loose connection to thermostat or system. 2. Thermostat or cooling system requires replacement or service.
3. System Switch not set to Cool. | Verify thermostat and system wires are securely attached. Your cooling system manufacturer or service person can describe how to test the cooling system to verify it is operating correctly. If the cooling system is capable of operation and the no cooling condition persists, replace the thermostat. Set System Switch to Cool and lower temp below room temp. |
Heat, Cool or Fan Runs Constantly. | 1. Possible short in wiring. 2. Possible short in thermostat. 3. Possible short in heat/cool/fan system. | Check each wire connection to the thermostat to verify it is neatly looped under the terminals. No extra wire should stick out from under the terminals. |
Furnace Cycles Too Fast or Too Slow Narrow or wide temperature swing | See Step 5, Adjusting the Anticipator. | The anticipation setting is the only adjustment that effects the heating cycle rate. If an acceptable cycle rate is not achieved using the anticipator contact a local service person for additional suggestions. The location of the thermostat, size of the Heat/Cool System and current draw can influence the cycle rate. |
Cooling Cycles Too Fast or Too Slow (narrow or wide temperature swing) | 1. Poor thermostat location for sensing room temperature. 2. Cooling system over or undersized. 3. Excessive Current draw influencing thermostat. | The cycle rate for cooling can not be adjusted. The location of the thermostat, size of the Cool system and current draw can influence the cycle rate. Contact a local service person for suggestions. |
Thermostat Setting and Thermostat Thermometer Disagree | 1. Thermostat thermometer setting requires adjustment. 2. Thermostat setting lever requires calibration. | The thermometer can be adjusted by using a standard slotted screwdriver. Turn the thermometer pointer screw located inside the front cover to change the setting. For calibrating the setting lever contact a local heating and cooling service person. |
Adjusting Thermometer | 1. Thermostat thermometer disagrees with other room thermometers. | The thermometer on the thermostat is accurately calibrated at our factory but you can adjust it by using a standard slotted screwdriver. Turn the thermometer pointer screw located inside the front cover to change the setting. |
Download Manual
EMERSON 1D56-310 White-Rodgers Low Voltage Horizontal Mounting Thermostat Instruction Manual
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…