FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE.
APPLICATIONS
For use with the following Class II systems:
DO NOT USE WITH:
Electrical Rating:
This thermostat is intended for use with a low-voltage NEC Class II system. Do not use this thermostat with a line voltage system. If in doubt about whether your wiring is millivolt, line, or low voltage, have it inspected by a qualified heating and air conditioning contractor or electrician. Do not exceed the specification ratings.
All wiring must conform to local and national electrical codes and ordinances.
This control is a precision instrument and should be handled carefully. Rough handling or distorting components could cause the control to malfunction.
CAUTION
To prevent electrical shock and/or equipment damage, disconnect electric power to the system at the main fuse or circuit breaker box until installation is complete.
WARNING
Do not use on circuits exceeding specified voltage. Higher voltage will damage control and could cause shock or fire hazards.
Do not short out terminals on the gas valve or primary control to test. Short or incorrect wiring will damage the thermostat and could cause personal injury and/or property damage.
Thermostat installation and all components of the system shall conform to Class II (current limited) circuits per the NEC code. Failure to do so could cause a fi re hazard.
REMOVE OLD THERMOSTAT
ATTENTION!
This product does not contain mercury. However, this product may replace a unit that contains mercury.
Do not open mercury cells. If a cell becomes damaged, do not touch any spilled mercury. Wearing nonabsorbent gloves, take up the spilled mercury and place into a container that can be sealed. If a cell becomes damaged, the unit should be discarded.
Mercury must not be discarded in household trash. When the unit this product is replacing is to be discarded, place it in a suitable container. Refer to www.white-rodgers.com for a location to send the product containing mercury.
ATTACH THERMOSTAT BASE TO WALL
O/B TERMINAL SWITCH SELECTION
The O/B switch on this thermostat is factory set to the “O” position. This will accommodate the majority of heat pump applications, which require the changeover relay to be energized in COOL. If the thermostat you are replacing or the heat pump being installed with this thermostat requires a “B” terminal, to energize the changeover relay in HEAT, the O/B switch must be moved to the “B” position.
GAS / ELEC SWITCH
If your system is a heat pump, the GAS/ELEC Switch must be set to ELEC (see Fig. 1) If your system is a single stage, the switch must be set to GAS. The switch setting must agree with the system configuration selected in the configuration menu.
Two “AA” alkaline batteries are installed in your thermostat with a battery tag to prevent power drainage. Prior to use, open the battery door and remove the battery tag. To open, pull the battery door as shown by the arrow and lift it open. The two “AA” batteries will operate all functions or maintain time and continuously display the temperature during a loss of AC power. Installed batteries will also allow programming prior to installation. To replace batteries, pull the battery door shown by the arrow and lift it open. Using the polarity indicated inside the battery door, insert the batteries. To close the battery door, swing the door down while pulling in the direction of the arrow. Once fully down, snap the door back into position. The thermostat can be powered by system AC power or a Battery. If is displayed, the thermostat is battery-powered. If is not displayed, the thermostat is system powered with optional battery backup. When the battery power remaining is approximately half, they will be displayed. When “Change ” is displayed, install fresh “AA” alkaline batteries immediately. For best results, use new premium brand alkalines batteries such as Duracell® or Energizer®. We recommend replacing batteries every 2 years. If the home is going to be unoccupied for an extended period (over 3 months) and is displayed, the batteries should be replaced before leaving. When less than two months of battery life remain, the setpoint temperature will offset by 10 degrees (10 degrees cooler in Heat mode / 10 degrees warmer in Cool mode). If offset occurs, the normal setpoint can be manually reset with or. Another offset will occur within two days if the batteries are not replaced. To replace the batteries, set system to OFF.
ENERGY MANAGEMENT RECOVERY (EMR)
When the EMR feature is activated the thermostat’s microcomputer calculates the time it will take to change the room temperature to the next heat or cool program setting. Then the thermostat will start the system before the next programmed period so that the desired temperature is reached at or near the beginning of the period (the thermostat calculates 15 minutes for every 1°F temperature change). This feature provides better efficiency by allowing gradual temperature changes.
For example, The thermostat is programmed to provide an overnight heating temperature of 66°F, and during the next program period, beginning at 6:00 AM, the programmed temperature is 70°F. With EMR activated, the thermostat will automatically start the heating system at 5:00 AM, so that the programmed temperature of 70°F is reached by about 6:00 AM.
If the overnight room temperature drops only to 68°F, the thermostat will start the system at 5:30 to reach the programmed temperature of 70°F at 6:00. The thermostat is shipped with the EMR feature active, which means that the thermostat will start the heating system before the beginning of the next program period. To deactivate the EMR function, see the Configuration menu on Page 5). The thermostat will then wait until the programmed time to start the system for a temperature change.
Before you begin programming your thermostat, you should be familiar with its features and with the display and the location and operation of the thermostat buttons and switches (see fig. 5). Your thermostat consists of two parts: the thermostat cover and the base. To remove the cover, pull it straight out from the base. To replace the cover, line up the cover with the base and press until the cover snaps onto the base.
The Thermostat Buttons and Switches
The configuration menu allows you to set certain thermostat operating characteristics to your system or personal requirements. To enter the menu: Set your thermostat to OFF and press the and buttons simultaneously. The display will show the first item in the configuration menu. Press RUN/HOLD to change to the next menu item or press TIME to go back to the previous item in the menu. To exit the menu and return to the program operation, press PRGM. If no keys are pressed within fifteen minutes, the thermostat will revert to normal operation.
Menu Reference Number | Press Key | Displayed (Factory Default) | Press or select from the listed options | Comments |
1 | and | SS | HP | Select Single Stage (SS) or Heat Pump (HP, 1 compressor) |
2 | RUN/HOLD* | CS (OFF) | On | Select Cool Savings Feature On or OFF |
RUN/HOLD* | CS (3) | 1, 2, 3, 4, 5, 6 | If CS selected On, selects Cool Savings value | |
3 | RUN/HOLD* | E (On) | OFF | Select Energy Management Recovery On or OFF |
4 | RUN/HOLD* | CR Heat (ME) | FA, SL | Select Adjustable Anticipation, cycle rate, Heat Single Stage |
5 | RUN/HOLD* | CR Cool (FA) | SL | Select Adjustable Anticipation, cycle rate, Cool Single Stage |
6 | RUN/HOLD* | CL (OFF) | On | Select Compressor lockout OFF or On |
7 | RUN/HOLD* | L (On) | OFF | Select Display Light On or OFF |
8 | RUN/HOLD* | Temp (0 HI) | 4 LO to 4 HI | Select temperature display adjustment higher or lower |
9 | RUN/HOLD* | oF | oC | Select oF / oC Display (temperature units in Fahrenheit or Celsius) |
10 | RUN/HOLD* | Change Filter (OFF) | On | Select filter replacement indicator OFF or On |
RUN/HOLD* | Change Filter (200 h) | 25 to 1975 | If Change Filter is selected On, select the time interval for Change Filter Indicator. (in 25-hour increments) | |
11 | RUN/HOLD* | Returns to normal operation |
*Press RUN/HOLD to advance to the next item or TIME to move backwards to the previous item
CHECK THERMOSTAT OPERATION
If at any time during testing your system does not operate properly, contact a qualified service person.
Turn on the power to the system.
Fan Operation
If your system does not have a G terminal connection, skip to Heating System.
Heating System
Cooling System
CAUTION
To prevent compressor and/or property damage, if the outdoor temperature is below 50oF, DO NOT operate the cooling system.
CAUTION
Do not allow the compressor to run unless the compressor oil heaters have been operational for 6 hours and the system has not been operational for at least 5 minutes.
MANUAL OPERATION
PROGRAMMING YOUR THERMOSTAT
This section will help you plan your thermostat’s program to meet your needs. For maximum comfort and efficiency, keep the following guidelines in mind when planning your program.
Planning Your Program
Look at the factory preprogrammed times and temperatures are shown in the sample schedule. If this program will suit your needs, simply press the RUN/HOLD button to begin running the factory preset program.
If you want to change the preprogrammed times and temperatures, follow these steps.
Determine the time periods and temperatures for your program.
You must program four periods for each day. However, you may use the same heating and cooling temperatures for consecutive time periods. You can choose start times, heating temperatures, and cooling temperatures independently (for example, you may select 5:00 AM and 70° as the daily 1st period heating start time and temperature, and also choose 7:00 AM and 76° as the daily 1st period cooling start time and temperature).
Use the table to plan your program time periods and the temperatures you want during each period. Fill in the complete table to have a record of your programs.
Entering Your Program
Set Current Time and Day
Enter Heating Program
Period | WEEKDAYS (5 Day) | SATURDAY (1 Day) | SUNDAY (1 Day) | ||||
Start Time | Temp | Start Time | Temp | Start Time | Temp | ||
HEAT | 1ST | 6:00 AM | 70F | 6:00 AM | 70F | 6:00 AM | 70F |
2ND | 8:00 AM | 62F | 8:00 AM | 62F | 8:00 AM | 62F | |
3RD | 5:00 PM | 70F | 5:00 PM | 70F | 5:00 PM | 70F | |
4TH | 10:00 PM | 62F | 10:00 PM | 62F | 10:00 PM | 62F | |
COOL | 1ST | 6:00 AM | 78F | 6:00 AM | 78F | 6:00 AM | 78F |
2ND | 8:00 AM | 85F | 8:00 AM | 85F | 8:00 AM | 85F | |
3RD | 5:00 PM | 78F | 5:00 PM | 78F | 5:00 PM | 78F | |
4TH | 10:00 PM | 82F | 10:00 PM | 82F | 10:00 PM | 82F |
Heating/Cooling Schedule Plan
Period | WEEKDAYS (5 Day) | SATURDAY (1 Day) | SUNDAY (1 Day) | ||||
Start Time | Temp | Start Time | Temp | Start Time | Temp | ||
HEAT | 1ST | ||||||
2ND | |||||||
3RD | |||||||
4TH | |||||||
COOL | 1ST | ||||||
2ND | |||||||
3RD | |||||||
4TH |
Enter Cooling Program
CAUTION
If the outside temperature is below 50oF, disconnect power to the cooling system before programming. Energizing the air conditioner compressor during cold weather may cause personal injury or property damage.
CHECK YOUR PROGRAMMING
Follow these steps to check your thermostat programming one final time before beginning thermostat operation.
YOUR THERMOSTAT IS NOW PROGRAMMED AND READY TO PROVIDE MAXIMUM COMFORT AND EFFICIENCY!
Reset Operation
If a voltage spike or static discharge blanks out the display or causes erratic thermostat operation, reset the thermostat by pressing the, and TIME buttons simultaneously.
If the thermostat has power, has been reset and still does not function correctly contact your heating/cooling service person or place of purchase.
Symptom | Possible Cause | Corrective Action |
No Heat/No Cool/No Fan (common problems) | 1. Blown fuse or tripped circuit breaker. 2. Furnace power switch to OFF. 3. Furnace blower compartment door or panel loose or not properly installed. | Replace fuse or reset breaker. Turn switch to ON. Replace door panel in proper position to engage safety interlock or door switch. |
No Heat | 1. System Switch not set to Heat.
2. Loose connection to thermostat or system 3. Heating System requires service or thermostat requires replacement. | Set System Switch to Heat and raise setpoint above room temperature. Verify thermostat and system wires are securely attached. Diagnostic: Set System Switch to Heat and raise the setpoint above room temperature. Within a five minutes the thermostat should make a soft slick sound. This sound usually indicates the thermostat is operating properly. If the thermostat does not click, try the reset operation listed above. If the thermostat does not click after being reset contact your heating and cooling service person or place of purchase for a replacement. If the thermostat clicks, contact the furnace manufac- turer or a service person to verify the heating system is operating correctly. |
No Cool | 1. System Switch not set to Cool.
2. Loose connection to thermostat or system. 3. Cooling System requires service or thermostat requires replacement | Set System Switch to Cool and lower setpoint below room temperature. Verify thermostat and system wires are securely attached. Same procedures as diagnostic for No Heat condi- tion except set the thermostat to Cool and lower the setpoint below the room temperature. There may be up to a five minute delay before the thermostat clicks in Cooling if the compressor lock-out option is selected in the configuration menu (Item 6). |
Heat, Cool or Fan Runs Constantly | 1. Possible short in wiring. 2. Possible short in thermostat. 3. Possible short in Heat/Cool/Fan system. 4. Fan Switch set to Fan On. | Check each wire connection to verify they are not shorted or touching together. No bare wire should stick out from under terminal screws. Try resetting the thermostat as described below. If the condition persists, the manufacturer of your system or service person can instruct you on how to test the Heat/Cool/ system for correct operation. If the system operates correctly, replace the thermostat. |
Furnace Cycles Too Fast or Too Slow Cooling Cycles Too Fast or Too Slow (narrow or wide temperature swing) | 1. The location of the thermostat and/ or the size of the Heating or Cooling System may be influencing the cycle rate. | Item 4 (CR Heat) or 5 (CR Cool) in the Configuration Menu is the adjustment that controls the cycle rate. If an acceptable cycle rate is not achieved using the FA (Fast) or SL (Slow) adjustment contact a local service person for additional suggestions. |
Thermostat Setting and Thermometer Disagree | 1. Thermostat thermometer setting requires adjustment. | The thermometer can be adjusted +/- degrees as listed in item 8 of the Configuration Menu. No other adjust- ment is possible. |
Clock Loses or Gains Time | 1. Loss of power to the thermostat. | The thermostat will maintain its program in memory even with no power but the clock time will be incorrect when power is restored. See No Heat/No Cool /No Fan (common problems) above for items to check in the system. |
Heat or Cool Starts Early | 1. EMR activated. | See Configuration Menu (Item 3) |
The thermostat Does Not Follow Program | 1. AM or PM set incorrectly in the program. 2. AM or PM set incorrectly on the clock. 3. Voltage spike or static discharge. 4. See “Heat or Cool Starts Early” above. | Check current clock and program settings including the AM or PM designations for each time period. If a voltage spike or static discharge occurs use the Reset Operation listed above. |
Blank Display and/or Keypad Not Responding | 1. Voltage Spike or Static Discharge. | If a voltage spike or static discharge occurs use the Reset Operation listed above. |
White-Rodgers is a division of Emerson Electric Co.
The Emerson logo is a trademark and service mark of Emerson Electric Co.
Download Manual
Emerson 1F80-0261 Day Programmable Thermostat Installation Guide
Emerson 1F80-0261 Day Programmable Thermostat Installation Guide
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…