Before Installation
If you do not have the knowledge to install the thermostat safely then you must arrange for a competent electrician to install it for you. Wiring must conform to the current IEE regulations.
Prior to commencing the installation you must ensure the mains supply is switched off.
10 Upper CH water set point | 30-80°C | Default 70°C |
11 Lower CH water set point | 10-25°C | Default 10°C |
12 Set DHW temp | 45-70°C | Default 60°C |
To make changes to the default Installer Options shown below, enter the Installer Options menu by pressing the settings button
(Option 01) Partial Sight Assistant
When enabled, audible tones indicate when the setpoint is more than, less than or equal to the current room temperature when a user manually adjusts the setpoint using the + button:
(Option 02) Frost Protection
The Digistat will switch on the heating if the temperature falls to 5°C and maintains a temperature of 7°C even when in OFF mode.
(Option 03) Minimum Setpoint Limit
Change minimum setpoint temperature. After any changes to setpoint limits, all setpoints in AUTO, MANUAL, BOOST and HOLIDAY modes will be modified to conform accordingly.
(Option 04) Maximum Setpoint Limit
Change maximum setpoint temperature. After any changes to setpoint limits, all setpoints in AUTO, MANUAL, BOOST and HOLIDAY modes will be modified to conform accordingly.
(Option 05) Optimum Start
When enabled, this uses current ambient temperature, the next scheduled setpoint and heat gain data captured by the device to adjust the thermostat setpoint early, so the ambient temperature is at the required level when the next event starts.
Delayed Start
When enabled, this uses current ambient temperature, current event setpoint and heating characteristics of the environment to delay implementation of the setpoint if the ambient temperature is already close to it, therefore saving energy.
(Option 06) Valve Protection Time
In some hydronic heating systems it may be required to protect the valve by operating it for a given time. When enabled, this maintenance feature ensures that each relay output is operated for at least one (1) minute each week.
(Option 07) Sensor Fault Function
In the event of a sensor fault, central heating output is reduced to 30% by turning heating ON for 3 minutes, then OFF for 7 minutes.
(Option 08) Application Type
Select the central heating system energy type.
(Option 09) System Capability
Select the flow capability of the heating system.
(Option 13) Installer Settings Lock
When enabled, installers can lock the installer settings menu until a 3 digit code is entered. If the code is forgotten while device is locked, please call the Technical Helpline.
(Option 20) Reset (Service Interval settings are NOT reset)
Reset the Digistat to its original factory settings. Note that resetting the thermostat will lose the pairing with the receiver. The receiver will also need to be reset before attempting to pair again. To reset the receiver press the receiver button for 15 seconds until the LED flashes green/amber.
(Si Option 01) Si Status
Enable or disable Service Interval Mode.
(Si Option 02) Si Type
Select effect imposed on the heating when service is due.
(Si Option 03) Service Due Date
Set date when next service is due.
(Si Option 04) Warning
Select no. of days before service due date.
(Si Option 05) Service Due Alarm
Enable or disable the audible service due alarm.
(Si Option 06) Si Boost
Enable or disable the Service Boost feature (5 boosts).
(Si Option 07) Password Reset
Change the 4 digit PIN. If you forget your Si password, please call the Technical Helpline.
Installer Options | What is it | Select between | Default | ||||
1 | Partial Sight Assistant | OFF | ON | ON | |||
2 | Frost Protection | ON | OFF | ON | |||
3 | Low Set Point C | 5 | High Limit | 5 | |||
4 | High Set Point C | Low Limit | 30 | 30 | |||
5 | Optimum Start | OFF | Delayed Start | Optimum Start | OFF | ||
6 | Valve Protection Time (Mins) | OFF | 5 | 4 | 3 2 1 | OFF | |
7 | Sensor Fault Function | OFF | ON | OFF | |||
8 | Application Type | Gas | Electric | Oil | Heat Pump | Gas | |
9 | System Capability | Fast Flow | Normal/Slow Flow | Fast Flow | |||
13 | Installer Settings Lock | OFF | ON | OFF | |||
20 | Reset | NO | YES | NO | |||
Service Internal Options | 1 | Si Status | OFF | ON | OFF | ||
2 | Si Type | Reduced Comfort | Heating OFF | NO Effect | Reduced Comfort | ||
3 | Si Due Date | YY/MM/DD | |||||
4 | Si Warning | 0 | 99 | 30 | |||
5 | Si Due Alarm | OFF | ON | OFF | |||
6 | Si Boost | OFF | ON | OFF | |||
7 | Si Password Reset | Select 4-Digit PIN | 0 |
The Drayton Digistat thermostat is a universal thermostat with 24 hour, 5-2day or 7day program types and up to 8 time/temperature events per day and can also be used as a simple room thermostat.
Your Digistat is fitted with a “real-time clock”, which is pre-set at the factory; you will not have to alter the time settings. A special feature of this real-time clock is it will automatically change over during the GMT/BST summer/winter change-over, removing the need to manually alter the clock at these times.
Programmable thermostats do not have “On” and “Off” times like traditional timers. They offer temperature control both day and night and you simply select which temperatures you require at each point in the day. With the unit in “Auto Mode” (the calendar icon is visible at the bottom of the screen) the temperature can be changed for a short time by using the + and – buttons. Changing the temperature in this way will keep the Digistat set to your new temperature until the next pre-programmed event (at which time it will revert to programmed temperature). The temperature you are setting will flash on the screen. Once temperature is set, the unit will revert to showing the room temperature again. The indicator will show on the screen if the unit is calling for heat.
Your Digistat comes with the following settings pre-programmed for your convenience and is suitable for those working out of the house during a typical 9-5 pattern. When the 5-2day program type is selected the pre-set temperatures will be different Mon-Fri and Sat-Sun, as per the tables below:
Pre-set Program 1 (24h, 5-2day weekdays, or 7day):
Event | 1 | 2 | 3 | 4 | (5)* | (6) | (7) | (8) |
Time | 06:30 | 08:30 | 16:30 | 22:30 | ||||
Temperature | 20°C | 16°C | 21°C | OFF | All done! |
Pre-set Program 1 (5-2day weekend):
Event | 1 | 2 | 3 | 4 | (5)* | (6) | (7) | (8) |
TimeTemperature | 07:0020°C | 09:0018°C | 16:0021°C | 23:00OFF |
To add these additional time periods manually (max. 8 per day) please refer to the steps to the right.
The Bluetooth® word mark and logos are registered trademarks owned by Bluetooth SIG, Inc. and any use of such marks by Schneider Electric is under license. Other trademarks and trade names are those of their respective owners.
All done!
You have completed the quick start and the unit is now set correctly to follow your required timings. For further user information surrounding the thermostat and the app control please use the website where you can download full user instructions.
The declaration of conformity may be consulted at www.draytoncontrols.co.uk
Technical Helpline Tel: 0333 7000 622
Website: www.draytoncontrols.co.uk
Email: customer.care@draytoncontrols.co.uk
Download manual:
Drayton RF901 Wireless Programmable Room Thermostat Installation Guide
Other manuals;
Drayton RF901 Wireless Programmable Room Thermostat User Guide
Drayton RF901 Wireless Programmable Room Thermostat Product Specifications Guide
Drayton RF901 Wireless Programmable Room Thermostat Installation Guide
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…