TPOne Programmable Room Thermostat platform delivers new levels of user-friendly interaction. The flexible dot matrix display uses easy read icons and text information to provide feedback on status and settings to the installer and user. When the display is activated the backlight illuminates and guides are given on the what buttons will adjust temperatures or navigate the setting menus. Chrono Proportional, Load Compensation control is the default heat regulation system that will deliver increased comfort and improved economy over standard on/off control. Standard On/Off can also be selected. When the chrono-proportional mode is set, the thermostat introduces a fixed cycle rate on the system and then determines the duration of the On and Off periods within each cycle in proportion to load. The control algorithm used to determine the on/off periods uses a proportional + integral (PI) routine to eliminate offset normally associated with on/off or simple proportional control. Chrono-proportional control significantly improves comfort and generally improves boiler efficiency by optimising water temperature. For TPOne we have redesigned the heating startup options. Standard startup is default giving instant heat at the scheduled time. New dynamic Delayed and Optimised start features are also selectable. Delayed start will pause the heating startup at the scheduled time dependant on the difference between ambient and required temperature which will decrease energy usage. Optimized start will monitor the difference between ambient and required temperature and will calculate the best time to start heating to hit setpoint at the scheduled time. Both features dynamically adjust according to performance accuracy each day to ensure most acurate control and remove the need for manual setting and adjustment.
Additional TPOne features include:
TPOne Programmable Room Thermostat introduces the quick access Scenario interface. To the left of the display are 4 dedicated user buttons. As a programmable device heating is controlled by a preset schedule but sometimes our schedules change intermittently so we have made it easy for the user to adapt their heating to suit. The Home, Away & Asleep buttons allow the user to quickly change the current setting to either save energy or deliver comfort when needed. These manual overrides stay until the next scheduled heating change so no need to remember to switch back to automatic control. The additional standby button also gives the control to stop the heating completely, this will save energy when airing the home or can be used to switch off during Summer months without having to change the schedule. Standby remains until the user chooses to switch back on.
Thermostat Features | TPOne-M | TPOne-B | TPOne-RF + RX1-S |
Ordering codes | 087N785200 | 087N785100 | 087N785400 |
Code without receiver | – | – | 087N785300 |
Product Line | 03 | 03 | 03 |
Type | Programmable Thermostat | RF Programmable Thermostat | |
Power Supply TPOne | 230Vac, 50/60Hz | 2.5 – 3VDC (2x AA Alkaline Batteries) | |
Battery Life | – | Min 2 years | |
Power Supply RX1-S | – | 230Vac, 50/60Hz | |
Output Channel 1 | Volt free, SPDT type 1B | Volt free, SPDT type 1B (RX1-S) | |
Switch Rating Channel 1 | 3A at 230Vac | 3A at 230Vac (RX1-S) | |
Output Channel 2 | 3A at 230Vac | – | |
Operating Frequency | – | 433.92MHz | |
Maximum Range | – | 30 meters | |
Setting temperature range | 5-35 °C | ||
Operating temperature range | 0-45 °C | ||
IP Rating | IP20 | ||
On/Off Control | Yes | ||
Chrono-proportional control | Yes | ||
Dimensions (mm) | H66 x W155 x D30 | ||
Dimensions (mm) RX1-S | – | H84 x W84 x D28 |
ERP Class | ||
The products represented within this document are classified according to, and allow completion of, the Energy Related Product (ErP) Directive System Package fiche and the ErP system data label. ErP Labelling obligation is applicable from 26th September 2015. | ||
ErP Class | Product Function and ErP Description | Additional efficiency gain |
IV | TPI Room Thermostat, for use with on/off output heaters An electronic room thermostat that controls both thermostat cycle rate and in-cycle on/off ratio of the heater proportional to room temperature. TPI control strategy reduces mean water tem- perature, improves room temperature control accuracy and enhances system efficiency. | 2% |
Danfoss Ltd. Ampthill Road Bedford MK42 9ER
Tel: 01234 364621
Fax: 01234 219705
Email: ukheating@danfoss.com
Website: www.heating.danfoss.co.uk
Danfoss can accept no responsibility for possible errors in catalogues, brochures, and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed.
All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
Danfoss TPOne Electronic Programmable Room Thermostat Installation Guide
Danfoss TPOne Electronic Room Thermostats Technical Specification Data Sheet
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…