CAUTION Follow the Installation Instructions before proceeding. Set the thermostat mode to “OFF” prior to changing settings in setup or restoring Factory Defaults.
NOTE: Due to variations in environmental conditions, it is not always possible to achieve the desired humidification or dehumidification setpoint. This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation
Auto-Changeover:
A mode in which the thermostat will turn on the heating or cooling based on room temperature demand.
Cool Setpoint: The warmest temperature that the space should rise to before cooling is turned on (without regard to deadband).
Deadband: The number of degrees the thermostat will wait, once a setpoint has been reached, before energizing heating or cooling.
Dehumidify: To reduce the amount of moisture in the air.
Differential: The forced temperature difference between the heat setpoint and the cool setpoint.
Heat Setpoint: The coolest temperature that the space should drop to before heating is turned on (without regard to deadband).
Humidify: To increase the amount of moisture in the air.
Icon: The word or symbol that appears on the thermostat display.
Mode: The current operating condition of the thermostat (i.e. Off, Heat, Cool, Auto, Program On).
Non-Programmable Thermostat: A thermostat that does not have the capability of running Time Period Programming.
Temperature Swing: Same as Deadband.
Display Features
During Setup and Programming
Press the UP or DOWN buttons to modify the selection. Press the MODE button to advance and confirm through the setup steps.
The select mode by pressing the MODE button. Heating Only – The HEAT setting indicates the temperature the room has to reach before the furnace will turn on to heat the room.
Cooling Only – The COOL setting indicates the temperature the room has to reach before the air conditioner will turn on to cool the room.
Heating or Cooling (Auto-Changeover) – AUTO will automatically select heat or cool based on room temperature demand.
OFF – OFF indicates both heating and air conditioning systems are turned off.
Selecting Your Desired Temperature
AUTO-CHANGEOVER MODE – Pressing the UP or DOWN buttons in Auto mode will adjust both the heat and cool setpoints simultaneously. To adjust the heat and cool setpoints individually, choose HEAT mode to adjust the heat setpoint and COOL mode to adjust the cool setpoint, then return to AUTO mode.
HEAT OR COOL MODE – Pressing the UP or DOWN buttons in Heat or cool mode will adjust only the heat or cool setpoints individually displayed.
NOTE – This thermostat has a fixed two-degree deadband. With a Cool setpoint of 72 degrees Fahrenheit, cooling will energize at a room temperature of 74 degrees. With a Heat setpoint of 68 degrees Fahrenheit, heating will energize at 66 degrees.
Using the Reset Filter Button
Reset Filter – Press the RST FILTER button to view the current filter runtime. Press the OUTDOOR button to reset the filter runtime counter to 0. Press the RST FILTER button again to return to normal operation
NOTE: Override may only be used when the Dry Contact has forced the thermostat into the Unoccupied mode
Unoccupied Operation
During a Dry Contact forced unoccupied period pressing the OVERRIDE button will force the thermostat into the mode it was in before the Dry The contact forced it into the Unoccupied mode. For example: if the thermostat was in the Auto mode and the Dry Contact forced it into Unoccupied mode, pressing OVERRIDE will force the thermostat back into Auto mode. The remaining override time will be displayed in the upper left corner of the display. Each press of the OVERRIDE button will add another 30 minutes of time for up to 4 hours. If the maximum time has been set, the next press of the OVERRIDE button will reset the timer and return the thermostat to the Unoccupied mode.
Viewing the Outdoor and Remote Temperature Sensors
OUTDOOR TEMP – Press the OUTDOOR button to view the current outdoor temperature. Pressing the OUTDOOR button again to return to normal operation.
REMOTE TEMP – Press the ACCESSORY button to enter the accessory setup screen. Press the UP button to view linked wireless and wired sensors and other accessories. Press the ACCESSORY button to return to the main screen.
Note: If no outdoor sensor is connected, 2 dashes [- -] will appear with the first button press
Viewing and Setting the Indoor Humidity Sensor
Press the HUMIDITY button to display the current humidity measured at the thermostat. The room’s relative humidity is displayed in the top left corner. The humidification setpoint appears in the larger center display and can be adjusted using the UP or DOWN buttons. Press the MODE button to view and adjust the dehumidification setpoints. Press the HUMIDITY button again to confirm settings and return to normal operation.
Note: Due to variations in environmental conditions, it is not always possible to achieve the desired humidification or dehumidification setpoint.
IMPORTANT: Allow at least 2 minutes after the thermostat is powered on for the humidity to read correctly
Remove & Replace the Old Thermostat
To install the thermostat properly, please follow these step-by-step instructions. If you are unsure about any of these steps, call a qualified technician for assistance.
Wire Connections
If the terminal designations on your old thermostat do not match those on the new thermostat, refer to the chart below or the wiring diagrams that follow
Wire from the old thermostat terminal marked | Function | Install on the new thermostat connector marked |
G or F | Fan | G |
Y1, Y or C | Cooling | Y1 |
W1, W or H | Heating | W1/O/B |
Rh, R, M, Vr, A | Power | R |
C | Common | C |
O/B | Rev. Valve | W1/O/B* |
W2 | 2nd Stage Heat | W2 |
Y2 | 2nd Stage Cooling | Y2 |
H, HUM | Humidity | HUM |
D, DEHUM | Dehumidity | DEHUM |
Ck1 | Dry Contact Switch | DRY CONTACT |
CKGND | Dry Contact Switch | DRY CONTACT |
S1, OUT – | Remote/Outdoor Sensor | REMOTE/ OUTDOOR |
S2, OUT + | Remote/Outdoor Sensor | REMOTE/ OUTDOOR |
IMPORTANT: This thermostat requires both R (24 VAC Return) and C (24 VAC Common) be connected to the backplate terminals.
Jumpers are located on the back of the thermostat
Sample Wiring Diagrams
Conventional Heating and Cooling Systems
Sample Wiring Diagrams
Heat Pump Systems
This thermostat has a diagnostic feature that enables testing of all outputs. This feature is contained in Technician Setup. To enter Technician Setup, press and hold the SETUP button for 5 seconds until all the icons appear. Follow the next steps to view settings and test equipment.
To exit Technician Setup at any time, press the SETUP button. Technician Setup will automatically exit after 10 minutes if no buttons are pressed.
How to Change Settings in the Setup Screens
To enter Advanced Setup, press the SETUP button, then press MODE. Use the UP or DOWN buttons to adjust the value of your selection. Press MODE to advance to the next setup step. Press SETUP again to leave the setup screens.
Backlight (Setup Step 3)
The thermostat backlight may be set to be always on, on temporarily with any button press, on throughout the evening, or always off. (For always off, see Backlight Level) Press the SETUP button, then press MODE repeatedly until the Backlight setup step appears. Use the UP or DOWN buttons to make a selection. Press MODE to advance to the next step. Press SETUP to leave the setup screens.
Backlight Off – Backlight turns on with any button press and turns off after 8 seconds. Backlight On – Backlight is on continuously
Backlight Level (Setup Step 4)
The backlight can be adjusted between always off and seven levels of brightness. Press the SETUP button, then press MODE repeatedly until the Backlight setup step appears. Use the UP or DOWN buttons to adjust the brightness. Press MODE to advance to the next step. Press SETUP to leave the setup screens.
Language (Setup Step 18)
Setup step instructions on the scrolling display can be set for English, Spanish, or French. Press the SETUP button, then press MODE repeatedly until the Language setup step appears. Use the UP or DOWN buttons to make a selection.
Scrolling Display Method (Setup Step 19)
This option allows the user to choose how the scrolling text is displayed. Options are:
Press the SETUP button, then press MODE repeatedly until the Scrolling Method setup step appears. Use the UP or DOWN buttons to make a selection. Press MODE to advance to the next step. Press SETUP to leave the setup screens.
Example of “Whole Words Centered”:
Display
This option allows the user to “de-clutter” the thermostat display screen by removing icons from the main display. The room temperature will always be shown. Service information may also be viewed by pressing and holding the DISPLAY button. Each press of the DISPLAY button will remove icons. Keep pressing DISPLAY to make icons reappear. Press and hold DISPLAY for 5 seconds
to view a name and phone number to call for service. Any removed icons will be displayed temporarily when a setting change is made.
Emergency Heat
The Emergency Heat function is only available if your thermostat is set to control a Heat Pump. To initiate the Emergency Heat feature, Press and hold the EMERGENCY HEAT button for 2 seconds. During Emergency Heat operation the thermostat will turn on the fan and auxiliary stages of heat when there is a demand for heat. The 1st stage of heating and all stages of cooling will be unavailable. To exit Emergency Heat, press the EMERGENCY HEAT button.
Accessory
The ACCESSORY button allows the user to view wired and wireless sensors and “link” these and other wireless devices to the thermostat via an optional RF module. Press the ACCESSORY button to enter the Accessory setup screen. Press UP to view linked and wired accessories. Follow the instructions included with the wireless accessory to begin the linking process. Next, press DOWN to enter the wireless linking mode. Press MODE to initiate linking. Press ACCESSORY to return to the main screen. NOTE: A wired outdoor sensor’s temperature reading is updated once every minute; a wireless outdoor sensor’s temperature reading is updated once every 5 minutes.
Using the Fan Button
Fan On indicates constant fan operation. Pressing the FAN button toggles this feature on or off.
Using the Service Button
SERVICE – Press the SERVICE button to display who to call for heating and cooling system repair. Press the SERVICE button again to return to normal operation.
Note: The TSTATGAC-UP USB Programmer will need to be used to program the service information into the thermostat.
These setup steps allow the user to monitor equipment runtimes and program service alerts.
System Runtimes (Setup Steps 6-17)
Press the SETUP button, then press MODE repeatedly until the desired setup step appears. Use the UP or DOWN buttons to make a selection. Press MODE to advance to the next step. Press SETUP to leave the setup screens.
How to Change Settings in the Setup Screens
To enter Advanced Setup, press the SETUP button, then press MODE. Use the UP or DOWN buttons to adjust the value of your selection. Press MODE to advance to the next setup step. Press SETUP again to leave the setup screens.
Selecting Your Available Modes (Setup Step 2)
Auto-Changeover – Allows the thermostat to turn on heating or cooling based on room temperature demand. Also allows the manual selection of HEAT only or COOL only and OFF.Heat and Cool – Allows the thermostat to turn on heating or cooling depending on which one has been manually selected. Auto-Changeover is not available when this is selected.
Heat Only – Allows the thermostat to only turn on the HEAT or OFF modes.
Cool Only – Allows the thermostat to only turn on COOL or OFF modes.
Setpoint Limits (Setup Step 20)
This feature allows the user to set 4 different levels of security: (0 – 3).
No Setpoint Limits (0) – When this level is selected, no restrictions are activated.
Use Setpoint Limits (1) – When this level is selected, the heat and cool setpoints can be restricted to preset levels, set in setup steps 21 and 22.
Cycles Per Hour (Setup Step 23)
The Cycles Per Hour setting may limit the number of times per hour your HVAC unit may energize. For example, at a setting of 6 cycles per hour the HVAC unit will only be allowed to energize once every 10 minutes. The Cycles Per Hour limit may be overridden and reset by pressing the UP or DOWN buttons on the thermostat. Settings are No Limit, 2, 3, 4, 5, or 6.
Compressor Minimum Off Minutes (Setup Step 24)
This feature allows the user to set a minimum off time for the compressor. Settings are 5 mins., 3 mins., or 0 mins.
Minimum Heat/Cool Setpoint Difference (Setup Step 25) This feature allows the user to set the minimum gap between Heat and Cool setpoints in AUTO mode. Select from 0 to 6. If setup step 2 is not set for AUTO-CHANGEOVER, this step will not appear.
Number of Compressor Stages (Setup Step 26)
This feature is for heat pump applications only.
This feature allows the thermostat to control 1 or 2 compressor stages when configured for heat pump.
Wired Sensor Use (Setup step 38)
This feature allows the user to choose if the wired sensor will be used as an indoor or outdoor sensor.
Control To Temp Source (Setup Step 39)
This feature allows the user to specify which temperature sensor source the thermostat will use to measure room temperature.
Humidity Only With Heat (Setup Step 40) – When this step is set to ON, Humidity will not run without a demand for Heat. Fan With Humidity Demand (Setup Step 41) – Specifies if the fan should be turned on with a demand for Humidity. (This step will only appear if step 40 is set to OFF.) Cool To Dehumidify (Setup Step 43) – Specifies if the cooling equipment is allowed to turn on exclusively to lower room humidity. (If set to OFF the following two steps will not appear.) Max Dehum Overcool (Setup Step 44) – Specifies how many degrees below the Cool setpoint the air conditioning will run to satisfy a Cool to Dehumidify demand. (0˚- 5˚)
Humidity Output Polarity (Setup Step 75)
Humidity Output Normally Open – means no voltage is sent to the HUM output when there is no demand for humidity.
Humidity Output Normally Closed – means voltage is sent to the HUM output when there is no demand for humidity.
Dehumidify Output Polarity (Setup Step 76)
Dehumidify Output Normally Open – means no voltage is sent to the DEHUM output when there is no demand to dehumidify.
Dehumidify Output Normally Closed – means voltage is sent to the
DEHUM output when there is no demand to dehumidify.
Fahrenheit or Celsius (setup step 56)
This feature allows the thermostat to display the temperature in Fahrenheit or Celsius.
Dry Contact Operation (setup step 70 – 73)
Dry Contact Polarity (Setup Step 70)
Open (Normally Open)
The dry contact is open until the connected device closes the circuit.
Closed (Normally Closed)
The dry contact is closed until the connected device opens the circuit.
PAN – If PAN is selected when the dry contact is active, the thermostat will lockout the compressor terminal(s) and “SERVICE DRAIN PAN” will appear on the display
FORCE UNOCCUPIED – If Force Unoccupied is selected in step 71, when the dry contact is energized the thermostat will be forced into or out of Unoccupied setpoints. To adjust the Unoccupied setpoints follow the setup steps below. from Occupied to Unoccupied. Set Unoccupied Cool Setpoint (Setup Step 72) – Press the Up or Down buttons to adjust the Unoccupied cool setpoint desired. Set Unoccupied Heat Setpoint (Setup Step 73) – Press the Up or Down buttons to adjust the Unoccupied heat setpoint desired.
Press Outdoor To Clear All Messages (setup step 79)
This feature allows the user to clear all current error messages from the display.
To prevent unauthorized use of the thermostat, the front panel buttons may be disabled. To disable, or ‘lock’ the keypad, press and hold the MODE button. While holding the MODE button, press the UP and DOWN buttons together. The icon will appear on the display, then release the
To unlock the keypad, press and hold the MODE button. While holding the MODE button, press the UP and DOWN buttons together. The icon
Resetting the Thermostat to the Factory Default
Settings (for default values see page 34) If, for any reason, you desire to return all the stored settings back to the factory default settings, follow the instructions below.
WARNING: This will reset all Advanced Programming to the default settings. Any information entered prior to this reset may be permanently lost.
To enter Technician Setup, press and hold the SETUP button for 5 seconds. After all the icons appear, press MODE. The version numbers of the thermostat will appear in the scrolling text. Press MODE to advance to the next step. Use the UP or DOWN buttons to adjust the value of your selection. To leave Technician Setup, press SETUP.
Technician Setup is for diagnostic and testing purposes and is intended for use by a qualified technician. See page 14 for more detailed instructions.
Technician Setup contains the following options
Advanced Setup Table -2200C-2 Df = Factory Default Setting | |||||
Step# | Description | Pg# | Range | Df | |
2 | Available Modes | 19 | Heat/Cool/Auto/Off, Heat/Cool/Off, Heat/Off, Cool/Off | Heat/Cool/ Auto/Off | |
3 | Backlight | 15 | On, Off | Off | |
4 | Backlight Level | 15 | Off-7 levels of brightness | Level 5 | |
6 | Current Service Filter Runtime Hours | 18 | 0-1999 | 0 | |
7 | Current Service Filter Calendar Days | 18 | 0-1999 | 0 | |
11 | Current Override Hours | 18 | 0-1999 | 0 | |
12 | Current UV Lamp Calendar Days | 18 | 0-1999 | 0 | |
13 | Current Humidifier Calendar Days | 18 | 0-1999 | 0 | |
14 | Set Service Filter Runtime Hours | 18 | 0-1950 | 0 | |
15 | Set Service Filter Calendar Days | 18 | 0-720 | 0 | |
16 | Set UV Lamp Calendar Days | 18 | 0-720 | 0 | |
17 | Set Humidifier Calendar Days | 18 | 0-720 | 0 | |
18 | Language | 15 | English,Espanol,Francais | English | |
19 | Scrolling Method | 16 | L-R Slow,L-R Fast,Word L-R Slow,Word L-R Fast, Whole Word L Slow, Whole Word L Fast, Whole Word Ctr Slow, Whole Word Ctr Fast | Whole Word Ctr Fast | |
20 | Setpoint Limits | 19 | No, Use, Force Current Mode, Setpoints Frozen | No | |
21 | Max Heat Setpoint | 19 | 35˚- 99˚ | 80˚ | |
22 | Min Cool Setpoint | 19 | 35˚- 99˚ | 65˚ | |
23 | Cycles Per Hour | 20 | No Limit, 2, 3, 4, 5, 6 | 6 | |
24 | Compressor Minimum Off Minutes | 20 | 0,3,5 | 5 | |
25 | Minimum Heat/Cool Setpoint Difference | 20 | 0˚- 6˚ | 2˚ | |
26 | Number Of Compressor Stages | 20 | 1 or 2 | 1 | |
38 | Wired Sensor Use | 20 | Indoor, Outdoor | Outdoor | |
39 | Control To Temp Source | 20 | Tstat, Remote | Tstat | |
40 | Humidity Only With Heat | 21 | On,Off | Off | |
41 | Fan With Humidity Demand | 21 | Fan On,Fan Off | Fan Off | |
43 | Cool To Dehumidify | 21 | On, Off | Off | |
44 | Maximum Dehum Overcool | 21 | 0˚- 5˚ | 2˚ | |
56 | F/C | 21 | Fahrenheit, Celsius | F | |
70 | Dry Contact Polarity | 22 | Open, Closed | Open | |
71 | Dry Contact Use | 22 | Pan, Unoccupied | Unoccupied | |
72 | Set Unoccupied Cool Setpoint | 22 | 35˚- 99˚ | 85˚ | |
73 | Set Unoccupied Heat Setpoint | 22 | 35˚- 99˚ | 55˚ |
Advanced Setup Table Df = Factory Default Setting | |||||
Step# | Description | Pg# | Range | Df | |
75 | Humidity Polarity | 21 | Open,Closed | Open | |
76 | Dehumidify Polarity | 21 | Open,Closed | Open | |
79 | Press Outdoor To Clear All Messages | 22 | N/A | N/A |
Five-Year Warranty – This Product is warranted to be free from defects in material and workmanship. If it appears within five years from the date of original installation, whether or not actual use begins on that date, that the product does not meet this warranty, a new or remanufactured part, at the manufacturer’s sole option to replace any defective part, will be provided without charge for the part itself provided the defective part is returned to the distributor through a qualified servicing dealer. THIS WARRANTY DOES NOT INCLUDE LABOR OR OTHER COSTS incurred for diagnosing, repairing, removing, installing, shipping, servicing or handling of either defective parts or replacement parts. Such costs may be covered by a separate warranty provided by the installer. THIS WARRANTY APPLIES ONLY TO PRODUCTS IN THEIR ORIGINAL INSTALLATION LOCATION AND BECOMES VOID UPON REINSTALLATION. LIMITATIONS OF WARRANTIES – ALL IMPLIED WARRANTIES (INCLUDING IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE AND MERCHANTABILITY) ARE HEREBY LIMITED IN DURATION TO THE PERIOD FOR WHICH THE LIMITED WARRANTY IS GIVEN. SOME STATES DO NOT ALLOW LIMITATIONS ON HOW LONG AN IMPLIED WARRANTY LASTS, SO THE ABOVE MAY NOT APPLY TO YOU. THE EXPRESSED WARRANTIES MADE IN THIS WARRANTY ARE EXCLUSIVE AND MAY NOT BE ALTERED, ENLARGED, OR CHANGED BY ANY DISTRIBUTOR, DEALER, OR OTHER PERSON WHATSOEVER. ALL WORK UNDER THE TERMS OF THIS WARRANTY SHALL BE PERFORMED DURING NORMAL WORKING HOURS. ALL REPLACEMENT PARTS, WHETHER NEW OR REMANUFACTURED, ASSUME AS THEIR WARRANTY PERIOD ONLY THE REMAINING TIME PERIOD OF THIS WARRANTY.
THE MANUFACTURER WILL NOT BE RESPONSIBLE FOR
Download Manual:
Daikin TSTATD2200C Non-Programmable Digital Thermostat Owner Manual
OTHER MANUALS
Daikin TSTATD2200C Programmable Digital Thermostat Owner Manual
Daikin TSTATD2200C Non-Programmable Digital Thermostat Owner Manual
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…