The CHV-TSTATRF is a wireless networked thermostat featuring infiNET™ wireless technology. The CHV-TSTATRF is designed to be installed easily in place of a conventional thermostat without requiring additional control wiring. Although it can be used as a standalone thermostat, the CHV-TSTATRF delivers enhanced functionality as part of a complete Crestron Home® automation system communicating via the infiNET wireless control network. The thermostat is available in three colors: the CHV-TSTATRFA in almond, the CHV-TSTATRFB in black and the CHV-TSTATRFW in white. For simplicity within this guide, these thermostats are referred to as CHV-TSTATRF. The features and specifications for all three thermostats are identical.
Features and Functions
Auto mode support requires firmware version 1.005.0005 or later.
Heat/Cool Thermostat
The CHV-TSTATRF is designed for heating and cooling control of baseboard, forced air, heat pump and dual-fuel heat pump HVAC systems. The large backlit LCD display provides a clear view of current temperature, setpoint, system mode, fan mode, system status and setup functions. Climate-control features include separate heat and cool setpoints and adjustable anticipators to prevent overshooting the desired temperature. Continuous fan operation can be selected when needed for increased circulation.
infiNET™
Creston’s groundbreaking infiNET wireless technology affords reliable two-way communications throughout a home or office structure without the need for physical control wiring. Numerous infiNET thermostats and other devices can be linked to a control system via a single RF gateway. Employing a 2.4 GHz mesh network topology, every infiNET device functions as an RF repeater, increasing effective range and reinforcing the complete network by providing multiple redundant signal paths within the mesh network. In addition, a dedicated repeater (C2N-MNETRPT, sold separately) can be added to increase the system range.
NOTE: The CHV-TSTATRF must be powered by 24 Volt AC source and have its power setting on “24” to allow it to function as a repeater.
Automation System Integration
Its wireless connection to the control system allows the functions of the CHV-TSTATRF to be controlled from touchpanels, keypads, wireless remotes and computers to support unlimited flexibility for remote control, scheduling and integration with other devices and systems. However, in the event that communication with the control system is disrupted for any reason, the CHV-TSTATRF will remain operable to control the HVAC system.
Easy Installation
System design, installation and upgrade using infiNET thermostats along with lighting dimmers and other devices could not be easier. Since there is no control wiring required, the CHV-TSTATRF can be installed just like any conventional thermostat. Setting up a complete network of infiNET devices is simple, utilizing dynamic discovery (self-install) to locate and acquire each RF device automatically. Setting the RF ID of each device employs the same convention as Crestron’s familiar TSID method. The RF ID can also be set manually from the local display. Each device is programmable using Crestron SIMPL™ Windows®, SystemBuilder™ or D3 Pro™ software just like any wired Cresnet® device. Even firmware updates are performed over the wireless network. No further action is required to configure the infiNET network.
Each device assigned to a common gateway automatically behaves as a repeater for any other device within range (approximately 150 feet indoors) and additional repeaters may be added if necessary. At all times, the infiNET gateway monitors each device on the network, ignoring any other 2.4 GHz signals and reconfiguring the entire network automatically in response to new sources of interference and other changes in RF conditions.
Specifications for the CHV-TSTATRF are listed in the following table.
CHV-TSTATRF Specifications
SPECIFICATION | DETAILS |
Wireless | C2N-MNETGW gateway/transceiver required (sold separately) |
RF Transceiver | Two-way RF, 2.4 GHz ISM Channels 11-26 (2400 to 2483.6 MHz), IEEE 802.15.4 compliant |
RF Output Power | 10 mW |
Range (typical) | 150 feet indoor, 250 feet outdoor, subject to site-specific conditions; range is increased by adding additional devices or C2N-MNETRPT repeater |
Display | Backlit LCD with two large seven-segment digits, two small seven-segment digits, 14 dedicated symbols; Displays ambient temperature, setpoint, system mode, fan setting, call activity, low battery, RF or control system communication errors, firmware download progress, setup parameter/function and value |
Measurement Range | |
Ambient Temperature | -10º to 110ºF (-23º to 43ºC) |
Display Limits | -9º to 99ºF (-9º to 43ºC) |
Setpoint Range | |
Heat only setpoint | 38º to 89ºF (3º to 32ºC) |
Cool only setpoint | 59º to 99ºF (15º to 37ºC) or 38º to 99ºF (3º to 37ºC) extended cool mode enabled |
Relay Rating | 1 Amp @ 40 Volts DC or 24 Volts AC (nominal) |
Environmental | |
Temperature | -10º to 110ºF (-23º to 43ºC) |
Humidity | 10% to 90% RH (non-condensing) |
Power Requirements | 0.24 Watts (10 mA @ 24 Volts AC) supplied by heating or cooling system |
Battery | Two AA batteries, estimated one year normal operation (with power parameter set to “Steal Power” setting) |
Default MNET ID | 01 |
Minimum 2-Series Control System Update File1, 2 | Version 3.154 or later |
Housing | Injection molded plastic, surface-mountable to the front of a horizontally oriented single-gang electrical box. |
Dimensions | |
Height | 4.50 in (11.43 cm) |
Width | 5.53 in (14.05 cm) |
Depth | 1.03 in (2.60 cm) |
Weight | 6.7 oz (189.9 g) |
Available Models | |
CHV-TSTATRFA | infiNET Thermostat, Almond |
CHV-TSTATRFB | infiNET Thermostat, Black |
CHV-TSTATRFW | infiNET Thermostat, White |
Available Accessories | |
C2N-MNETGW | infiNET Gateway/Transceiver |
C2N-MNETRPT | infiNET Repeater |
NOTE: Crestron software and any files on the website are for authorized Crestron dealers and Crestron Authorized Independent Programmers (CAIP) only. New users may be required to register to obtain access to certain areas of the site (including the FTP site).
This section provides information on the connections, controls and indicators available on your CHV-TSTATRF.
CHV-TSTATRF Physical View
CHV-TSTATRF Overall Dimensions (Front and Side Views)
CHV-TSTATRF Overall Dimensions (Rear View)
CHV-TSTATRF (Connection View, front with cover removed)
Connectors, Controls & Indicators
# | CONNECTORS, CONTROLS & INDICATORS | DESCRIPTION |
1 | MODE BUTTON | Cycles through available System Modes: OFF, HEAT, EMERGENCY HEAT (for heat pump or dual-fuel systems only), COOL and AUTO. |
2 | FAN BUTTON | Toggles fan setting between FAN AUTO and FAN ON. |
3 | (RAISE BUTTON) | Raises the setpoint. |
4 | (LOWER BUTTON) | Lowers the setpoint. |
5 | LCD DISPLAY | Displays ambient temperature, setpoint, system mode, fan setting, call activity, low battery, RF or control system communication errors, firmware download progress, setup parameter/function and value. |
6 | HVAC | (4) Two-position terminal blocks. C 24 VAC common terminal supplies remote power to thermostat W Heat – Switched to RH during a call for heat in heat/cool systems or aux heat in heat pump systems O Changeover control – Switched to RC during cooling modes B Switched to RC during heating modes RH Reference Heat – Used for calls to heating system RC Reference Cool – Used for calls to cooling system G Fan – Switched to RC during call for fan Y Compressor: – Switched to RC when compressor is run |
Industry Compliance
FCC ID: EROCWD1013
Compliance Statement (Part 15.19)
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
Warning (Part 15.21)
Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.
FCC Interference Statement
This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one of the following measures:
FCC Statement
To comply with FCC’s RF exposure limits for general population / uncontrolled exposure, the antenna(s) used for this transmitter must be installed to provide a separation distance of at least 20 cm from all persons and must not be co-located or operating in conjunction with any other antenna or transmitter.
Industry Canada Statement
The term “IC” before the certification/registration number only signifies that the Industry Canada technical specifications were met
IC: 5683A-CWD1013
Section 7.1.5 of RSS-GEN
Operation is subject to the following two conditions:
NOTE: Installers should have a strong working knowledge of HVAC systems.
Mounting the CVH-TSTATRF to the Wall
The location of the thermostat can affect its performance and efficiency. Install the thermostat away from direct sunlight, drafts, doorways, skylights and windows. Also make sure the thermostat is conveniently located for control access and setup and do not mount on an exterior wall. Thermostats should be mounted 60 inches (152.4 cm) above the finished floor (HVAC industry standard). The following tools/hardware are required for installation.
Use the following procedure to install the CHV-TSTATRF in a standard, single-gang electrical box (refer to illustration on the following):
Installation view
Wiring the CHV-TSTATRF to the HVAC System
Make the necessary connections as called out in the illustrations that follow. A flat head screwdriver (not supplied) is required to attach the control wires from the HVAC system. Apply power after all connections have been made. The illustrations on the following pages show examples for connection to various types of HVAC systems. If your system does not match any of the systems described below, contact Crestron Technical Support for assistance.
Connections for the CHV-TSTATRF
NOTE
CHV-TSTATRF in Heat Only Application
CHV-TSTATRF in Heat Only with Fan Application
NOTE: To run fan during heat calls, be sure to enable the HF parameter by setting it to “Y”. Refer to “Advanced Setup” which starts on page 19 for details.
CHV-TSTATRF in Cool Only Application
CHV-TSTATRF in Heat-Cool Application with Separate Systems
CHV-TSTATRF in Heat-Cool Application with Integrated Control Unit
CHV-TSTATRF in Heat Pump System Application with Integrated Controller
NOTE: Heat pump and dual-fuel heat pump systems require an outdoor temperature sensor (e.g. Crestron’s C2N-RTHS, sold separately) to function properly. In SIMPL Windows, connect the “Temp” output of the sensor to the “OutdoorTemp” input of the CHV-TSTATRF. For details, refer to the SIMPL Windows help file. If using D3 Pro or SystemBuilder refer to “Programming with Crestron D3 Pro or SystemBuilder”.
CHV-TSTATRF in Dual-Fuel Heat Pump Application
NOTE: The diagram above applies where furnace control is not integrated into the heat pump system.
Basic Thermostat Setup
NOTE: When first setting up the CHV-TSTATRF, batteries are required, even if you plan to power it from a constant 24 VAC supply.
Place the CHV-TSTATRF in the Setup mode by doing the following:
By default, the CHV-TSTATRF is configured to be powered by two AA alkaline batteries. In addition, in order to extend battery life, the device is able to steal power from the HVAC system by drawing a small amount of current through the heat or cool terminals. It will not draw enough current to cause the external heat or cool relays to close. More specifically, when the unit is not making a call for heat, it will draw power through the RH and W terminals. When the unit is making a call for heat, it will draw power through the RC and Y terminals. (This will not work if the thermostat has been wired for a cool only application.)
NOTE
If you have wired the thermostat so that 24 Volts AC will always be present on the “C” terminal (refer to “Wiring the CHV-TSTATRF to the HVAC System” which starts on page 10), you can set the unit to run from this power supply, thus eliminating the need for batteries (except during initial setup). The thermostat will run on battery power if 24 VAC is not present. In addition, when the unit detects 24 VAC is present, it will no longer “sleep”, meaning that it will offer real-time communication with the control system. When shipped from the factory, the CHV-TSTATRF will have a steal power setting. If you plan to power the device from a constant 24 VAC supply, you must still install batteries in order to access Setup mode and change the power setting to “24”.
NOTE: When the unit is powered from a constant 24 VAC supply, there may be a slight discrepancy between the ambient temperature displayed on the thermostat and the actual room temperature. This discrepancy will also be seen when switching from “SP” to “24”. This is normal and the discrepancy will disappear within approximately 10 minutes.
The MNET ID of the CHV-TSTATRF has been factory set to 01. After an infiNET device is added to an infiNET network, its MNET ID must be changed to a value that can be addressed by the control system program (03 to 20). The MNET IDs of multiple CHV-TSTATRF devices on the same gateway must be unique. MNET IDs are changed locally using the setup parameter ability of the CHV-TSTATRF (refer to “Setup Mode Parameters/Functions” which starts on page 20). They can also be changed from a personal computer (PC) via the Crestron Toolbox™.
When setting the MNET ID, consider the following:
NOTE: An infiNET device can be acquired by only one gateway.
To acquire the CHV-TSTATRF, perform the following procedure:
NOTE
After the process is complete, take the C2N-MNETGW out of the Acquire mode by pressing ACQUIRE on the gateway. Refer to the latest revision of the C2N-MNETGW guide (Doc. 6317). To exit from Setup mode, press the FAN button on the CHV-TSTATRF.
The Fan icon will indicate the status of infiNET communication:
Setup Mode
After the CHV-TSTATRF is installed, it is necessary to set it up for a particular heating/cooling system. Please note that some of the setup parameters listed below will not always be available. Refer to “Setup Mode Parameters/Functions”, which starts for details. Place the CHV-TSTATRF in the Setup mode by doing the following:
Once in Setup mode, the display will indicate the currently selected setup parameter/function. Press and release the MODE button quickly (must be released within one second) to change to the next parameter/function in the list.
NOTE: Holding the MODE button for more than one second will reset the currently selected parameter/function to its default value.
CHV-TSTATRF LCD Display (Setup Mode)
NOTE
The following table shows the available setup parameters/functions.
PARAMETER/ FUNCTION | CODE | VALID VALUES | DEFAULT VALUE | NOTES |
Temperature Scale | FC | F, C1 or C2 | F | Sets units to use for temperature display (Fahrenheit or Celsius). When using Celsius temperature scale, C2 allows the setpoint to be adjusted in 0.5ºC steps. |
Backlight Timeout | bL | 1 – 4 seconds or disabled (–) | — | Sets the number of seconds the backlight will remain lit after a button press. |
Heat/Cool Type | HC | Heat/Cool (HC), Heat pump (HP), Dual-Fuel Heat pump (dF) | HC | Sets the system type being used. Heat pump type will allow aux heat to stage with the heat pump. A dual-fuel heat pump type will not allow both systems to run at the same time. |
Auto mode | AU | Disabled (–), Dual setpoint (d) or Single setpoint (S) | — | Used to enable Auto mode with single or dual setpoint operation. |
Auto Dead Band (will only appear when Auto mode is enabled) | db | 2 – 4 (for Fahrenheit) or 1 – 3 (for Celsius) | 2 | Used to set minimum separation between heat and cool setpoints (with dual setpoints) or maximum drift before system latches alternate mode (with single setpoint). |
Temperature Offset | to | -9 to +9 (for Fahrenheit) or -5 to +5 (for Celsius) | 0 | Permits recalibration of room temperature sensor. This is the number of degrees added to or subtracted from the actual temperature. This adjustment changes the actual regulation temperature, not just the display. |
Wide-range Cool Mode (Extended Cool) | EC | Enabled (Y) or Disabled (no) | no | Useful for wine chiller applications; extends the cool setpoint range down to the minimum used for Heat mode (38ºF/3ºC). |
Heat Anticipator | HA | 1 – 6 | 3 | Lower setting results in more frequent cycles and faster response (tighter regulation). Higher setting results in less frequent cycles and slower response (looser regulation). The default value should suffice in nearly all installations. |
Cool Anticipator | CA | 1 – 6 | 3 | Lower setting results in more frequent cycles and faster response (tighter regulation). Higher setting results in less frequent cycles and slower response (looser regulation). The default value should suffice in nearly all installations. |
Heat pump Balance Point (will only appear for Heat pump and Dual- Fuel Heat pump systems) | Hb | 16 to 90 (for Fahrenheit) or -9 to 32 (for Celsius) or Disabled (–) | — | Heat pump systems have performance restrictions based on outdoor temperature. This setting is the minimum outdoor temperature at which the heat pump (or dual-fuel heat pump) system will run. |
Aux-Heat Balance Point (will only appear for Heat pump type systems) | Ab | 16 to 90 (for Fahrenheit) or -9 to 32 (for Celsius) or Disabled (–) | — | Aux heat operation is locked out when outdoor temperature exceeds the Aux Heat Balance Point. Dual-fuel systems do not allow both the heat pump and the aux to run at the same time. |
Interstage Differential (will only appear for Heat pump systems) | dF | 05 to 80 (tenths of a degree Fahrenheit), adjustable in 5 tenths degree increments or 05 to 45 (tenths of a degree Celsius), adjustable in 5 tenths degree increments | 20 (F) or 10 (C) | Heat pump systems can allow both the heat pump and aux to run at the same time. This sets the ambient temperature threshold to trigger aux heat in addition to the heat pump. |
Run Fan During Heat Calls | HF | Enabled (Y) or Disabled (no) | no | Most heat systems handle the fan call if required. If the system requires the thermostat to control the fan during heat calls, set this parameter to “Y”. |
Changeover Outputs (will only appear for Heat-Cool systems) | Co | Enabled (Y) or Disabled (no) | no | Indicates the mode in which the thermostat is operating. Will automatically be engaged for heat pump or dual-fuel heat pump systems. If not required, it should be disabled to extend battery life. |
Power Source | Po | 24V always available (24) or steal power (SP) | 24 | Selects source of input power for thermostat. 24VAC assumes constant power is available between the C and RH connectors. The steal-power function allows recovery of some power from the HVAC system when constant power is not available. Steal power may not work with some zone controllers. In this case, set value to “24” and ensure that you have two AA batteries installed. |
Check Firmware Version | rE | Firmware version is displayed in xx.yy.zz format. “—“ can also be displayed | — | When firmware version is not yet shown, display will be “—“. Each press of the |
infiNET ID (MNET ID) | id | 01 and 03 – FE | 01 | Sets the infiNET ID. SIMPL Windows restricts infiNET devices to an ID range of 03 – 20. |
infiNET RF Channel | CH | 11-26 for fixed-channel operation, “Au” for auto or “0” for disabled (battery saver) | 26 | Selects the RF channel. A fixed channel allows faster setup and reconnect when the gateway channel is fixed. Auto channel allows more flexibility but may consume slightly more power if network communications are interrupted. A setting of “0” disables the radio. |
infiNET Sleep Time | SL | Short (S) or Long (L) | L | Indicates thermostat update rate. Setting for fewer updates (“L”) will conserve battery power. |
Start infiNET Acquire | AC | Not started (–) In progress (flashing — ) Finished, found GW (00) Finished, could not find GW (E#, where # represents an error code) | N/A | Used to acquire the device to a gateway. ”E0” indicates that search time has expired and no gateway was found. ”E1” indicates the infiNET RF Channel is set to “0” (disabled). |
Unacquire Gateway | UA | Not started (–) In progress (flashing — ) Finished, success (00) Finished, failed (E#, where # represents an error code) | N/A | Used to remove gateway information from the device, so it will no longer communicate with the current gateway. ”E0” indicates that there is no previous gateway information (i.e. the gateway may already have been unacquired). |
Check Battery Life | bA | Not started (–) Estimated remaining battery life (0 – 99) | N/A | Gives estimated remaining battery life in percent. |
Restore Factory Defaults | Fd | Not started (–) In progress (blank or flashing –) Finished (00) Button not held long enough (Er) | N/A | Restores all setup parameters to their default settings. To prevent accidentally performing this action, you must press and hold either the |
Perform Heat Call Test (Toggle) | H | Not started/Heat call off (–) Heat call on (on) (also, “H” icon will turn on) | N/A | Will test the heat call output. Bypasses short-cycle timers. Useful for technician system testing. Note that calling the heat may activate other relays in the thermostat as required, such as the fan output for heat pump or dual-fuel types. |
Perform Cool Call Test (Toggle) | C | Not started/Cool call off (–) Cool call on (on) (also, “C” icon will turn on) | N/A | Will test the cool call output. Bypasses short-cycle timers. Useful for technician system testing. Note that calling the cooling may activate other relays in the thermostat as required, such as the fan output. |
Perform Aux Heat Call Test (Toggle) (will appear only on Heat pump and Dual- Fuel Heat pump systems) | A | Not started/Aux call off (–) Aux call on (on) (also, “A” icon will turn on) | N/A | Same as above, for testing aux heat output. |
Perform Fan Call Test (Toggle) | F | Not started/Fan call off (–) Fan call on (on) (also, “F” icon will turn on) | N/A | Same as above, for fan. Note that only the fan relay can be activated for a fan call test. |
Perform Self Test | St | Not started (–) In progress (flashing –) Finished, self test ok (00) Finished, self test failed (E#, where # represents an error code) | N/A | Performs a self-test of the thermostat. ”E0” indicates low battery voltage (replace batteries). ”E1” indicates low HVAC system voltage (check supply voltage – must be at least 24 VAC or 30 VDC). ”E5” indicates no gateway information (acquire the device to a C2N-MNETGW). ”E2”, “E3”, “E4”, “E6”, “E7” reserved (serious errors, contact tech support). |
System Mode
Off Mode
Heat Mode
Emergency Heat Mode
NOTE: Emergency Heat mode can only be accessed when heat/cool type has been set to “Heat pump” or “Dual-Fuel Heat pump”. This setting can be useful when the heat pump is being serviced or when there is an unexpected problem with it. The display will flash the “flame” icon when the system is in Emergency Heat mode.
Cool Mode
Auto Mode
NOTE: Auto mode support requires firmware version 1.005.0005 or later.
Dual Setpoint Auto Mode (“AU” = “d” in Setup Mode)
Single Setpoint Auto Mode (“AU” = “S” in Setup Mode)
NOTE: When using a single setpoint, the CHV-TSTATRF has a 20-minute change limiter to prevent system toggling.
The FAN button toggles the fan setting between fan AUTO and fan ON. When set to AUTO, a fan call will be made whenever the system makes a cool call or when the system makes a heat call or auxiliary heat call (if the HF setup parameter is set to “Y”). When set to ON the fan will always run.
Setpoints
NOTE: While the setpoint is being adjusted, if it is set to a half-degree increment, the integer portion of the number will be displayed and will alternate with “_5” every quarter second for a period of four seconds after the last adjustment. After four seconds, only the integer portion of the number will be displayed.
Hold
As an infiNET device, the CHV-TSTATRF can be controlled remotely via a Crestron control system. Most often, control of the thermostat will be achieved via a touchpanel or web-based graphical interface. In order to extend battery life, the thermostat will only communicate with the control system once every 30 seconds or one minute, based on the infiNET Sleep Time setting. Because of this, there will be a noticeable delay between the time a button is pressed on a touchpanel and when the thermostat reacts to the command. To account for this, the CHV-TSTATRF modules written by Crestron and provided in the Crestron Database will mimic the feedback from the thermostat so that the user will see an immediate response on the touchpanel.
Likewise, pressing a local button on the thermostat (for example, setpoint raise or lower) will not cause an immediate change to the corresponding display on a touchpanel. Instead, the thermostat will wake up approximately 10 seconds after the last button press to send its updated status to the control system.
NOTE: When the CHV-TSTATRF is powered via a constant 24 VAC supply, it will not go to sleep.
CHV-TSTATRF LCD Display
LCD Display Elements
# | LCD DISPLAY ELEMENT | DESCRIPTION |
1 | Large seven-segment digits | Indicates current ambient temperature1, 2. In Setup mode, indicates current setup parameter/function. Display range is limited to –9º to 99ºF (-9º to 43ºC). If the ambient temperature is above 99º, the display will indicate 99º. If the ambient temperature is below –9º, the display will indicate –9º. |
2 | Small seven-segment digits | Indicates current setpoint (in F or C) in whole degrees. While the setpoint is being adjusted, if it is set to a half-degree increment, the integer portion of the number will be displayed and will alternate with “_5” every quarter second for a period of four seconds after the last adjustment. After four seconds, only the integer portion of the number will be displayed. In Setup mode, indicates current value for selected Setup Parameter. |
3 | Flame icon | Displayed when the system mode is Heat. Flashes (on two seconds, off one half second) when the system mode is Emergency Heat. Displayed with snowflake icon when system is in Auto mode. |
4 | Snowflake icon | Displayed when the system mode is Cool. Displayed with flame icon when system is in Auto mode. |
5 | Fan icon | Displayed at all times. Flashes if a communication error occurs. |
6 | AUTO indicator | Displayed when FAN setting is AUTO. If this is not displayed, FAN is always ON. |
7 | OFF indicator | Displayed when the system mode is Off. |
8 | HOLD indicator | Displayed when the HOLD setting is active. |
9 | H, C, F & A indicators | H – Displayed whenever a Heat Call is being made. C – Displayed whenever a Cool Call is being made. F – Displayed whenever a Fan Call is being made. A – Displayed whenever an Aux Heat Call is being made. |
Have a question or comment about Crestron software?
Answers to frequently asked questions (FAQs) can be viewed in the Online Help section of the Crestron website. To post a question or view questions you have submitted to Crestron’s True Blue Support, log in at http://support.crestron.com. First-time users will need to establish a user account.
Earliest Version Software Requirements for the PC
NOTE: Crestron recommends that you use the latest software to take advantage of the most recently released features. The latest software is available from the Crestron website.
Crestron has developed an assortment of Windows-based software tools to develop an infiNET system. For the minimum recommended software versions, visit the Version Tracker page of the Crestron website (www.crestron.com/versiontracker).
Programming with Crestron D3 Pro or SystemBuilder
Crestron D3 Pro or SystemBuilder is the easiest method of programming but does not offer as much flexibility as SIMPL Windows. For additional details, download D3 Pro or SystemBuilder from the Crestron website and examine the extensive help files.
NOTE: Heat pump and dual-fuel heat pump systems require an outdoor temperature sensor (e.g. Crestron’s C2N-RTHS, sold separately) to function properly. Use a “Connect” step to attach the sensor’s “Temp” output to the “OutdoorTemp” input of the CHV-TSTATRF.
Programming with SIMPL Windows
NOTE: While SIMPL Windows can be used to program the CHV-TSTATRF, it is recommended to use SystemBuilder or D3 Pro for configuring a system.
SIMPL Windows is Crestron’s premier software for programming Crestron control systems. It is organized into two separate but equally important “Managers”.
Configuration Manager
Configuration Manager is the view where programmers “build” a Crestron control system by selecting hardware from the Device Library.
NOTE: It is not recommended to add the CHV-TSTATRF directly. Instead, add one of the available “modules” listed underneath it as shown below.
Locating the C2N-MNETGW in the Device Library
C2Net Device, Slot 9
“CHV-TSTATRF Device Settings” Window
Program Manager
Program Manager is the view where programmers “program” a Crestron control system by assigning signals to symbols. The symbol can be viewed by double clicking on the icon or dragging it into Detail View. Each signal in the symbol is described in the SIMPL Windows help file (F1).
Example Program
Crestron recommends using the latest programming software and that each device contains the latest firmware to take advantage of the most recently released features. However, before attempting to upload or upgrade it is necessary to establish communication. Once communication has been established, files (for example, programs or firmware) can be transferred to the control system (and/or device). Finally, program checks can be performed (such as changing the device ID) to ensure proper functioning.
Establishing Communication
Use Crestron Toolbox for communicating with the CHV-TSTATRF; refer to the Crestron Toolbox help file for details. There is a single method of communication: indirect serial communication.
Indirect Serial Communication
Programs and Firmware
Program or firmware files may be distributed from programmers to installers or from Crestron to dealers. Firmware upgrades are available from the Crestron website as new features are developed after product releases. One has the option to upload programs via the programming software or to upload and upgrade via the Crestron Toolbox. For details on uploading and upgrading, refer to the SIMPL Windows help file or the Crestron Toolbox help file.
SIMPL Windows
Check the Crestron website to find the latest firmware. (New users may be required to register to obtain access to certain areas of the site, including the FTP site.) Upgrade CHV-TSTATRF firmware via Crestron Toolbox.
Since the CHV-TSTATRF might be “asleep”, there may be a delay of one minute or less before the update starts.
Program Checks
Using Crestron Toolbox, display the network device tree (Tools | Network Device Tree) to show all network devices connected to the control system and all infiNET devices that have been acquired by the CHV-TSTATRF (C2N-MNETGW). Right-click on the CHV-TSTATRF (C2N-MNETGW) to display actions that can be performed on the CHV-TSTATRF (C2N-MNETGW).
Troubleshooting
The following table provides corrective action for possible trouble situations. If further assistance is required, please contact a Crestron customer service representative.
CHV-TSTATRF Troubleshooting
TROUBLE | POSSIBLE CAUSE(S) | CORRECTIVE ACTION |
No display | No power from system. | Check for +24V on C connector. Check circuit breaker powering furnace or boiler. Check thermostat wiring. Check batteries (if running on battery power). |
Incorrect mounting to back plate. | Check thermostat mounting. | |
Device does not follow control system commands. | Device is not communicating with the C2N-MNETGW. | Open Crestron Toolbox and select the Network Device Tree. Expand the tree until the gateway to be managed is selected. Right-click the NET ID of the selected gateway to open the sub-menu and select Functions | MNET Gateway… If device is not listed, acquire the device to the infiNET network (refer to ”Basic Thermostat Setup” which starts. |
MNET ID of device (or the gateway ID) is not set to match the MNET ID of the SIMPL Windows program. | Use the Network Device Tree infiNET network in Crestron Toolbox to poll the infiNET network. Verify that the MNET ID for the infiNET device is set to match the MNET ID specified in the SIMPL Windows program. | |
Device has entered a state of “hibernation”. | If the thermostat is unable to locate its gateway for a period of one hour, in order to prevent excess battery usage, it will hibernate. In this state, it will only look for the gateway once every 20 minutes. To remedy this, press any button on the thermostat. It should look for the gateway within 10 seconds. | |
Heating/Cooling system is not operating. | No power to thermostat. | Check circuit breaker. Check for +24V on C connector. Check circuit breaker powering furnace or boiler. Recheck wiring connections. Check batteries, replace if necessary. |
Cannot change setpoint setting. | The upper or lower temperature limits were reached. | Heat setpoint range is 38º to 89ºF (3º to 32ºC). Cool setpoint range is 59º to 99ºF (15º to 37ºC) or 38º to 99ºF (3º to 37ºC) if extended cool mode enabled. |
System cycles too quickly. | Anticipator setting is too low. | Reprogram anticipator setting (refer to “Setup Mode Parameters/Functions” which. |
Room has high temperature variance. | Anticipator setting is too high. | Reprogram anticipator setting (refer to “Setup Mode Parameters/Functions” which. |
Wide temperature variance in single setpoint Auto mode. | Auto dead band setting is too high. | Reprogram auto dead band (db) setting (refer to “Setup Mode Parameters/Functions” which). |
Heating/Cooling not operating in single setpoint Auto mode. | 20-minute system toggling lockout. | Reprogram auto dead band (db) and anticipator settings for smoother operation (refer to “Setup Mode Parameters/Functions” which). |
Wrong temperature is displayed. | Wrong temperature scale. | Select F or C as necessary. |
A Temperature Offset has been applied. | Reset Temperature Offset (refer to “Setup Mode Parameters/Functions” which starts). | |
Bad location. | Ensure the thermostat is located away from direct sunlight, drafts, doorways, skylights and windows or exterior walls. | |
Heat or cool call occurs but device does not indicate a heat or cool call. | Steal power function may be causing problems with HVAC system. | Change power setting (Po) to “24” and ensure you have two AA batteries installed. |
Improper wiring connections. | Recheck wiring connections. | |
Can not enter Auto mode. | Auto mode is disabled in setup. | Reprogram Auto mode setting (AU) to “S” (for single setpoint operation) or “d” (for dual setpoint operation) (refer to “Setup Mode Parameters/Functions” which starts). |
Bootloader
The bootloader is a low-level version of the CHV-TSTATRF’s firmware that will become active in the event an upload of the standard firmware fails. This lets you perform some basic functions with the goal of getting the CHV-TSTATRF back to normal operation.
If the CHV-TSTATRF goes into bootloader, the large seven-segment display will show “Ld”, except when in Setup mode. All other LCD segments will be off. All button presses will be ignored, except for the sequence which enters Setup mode (refer to “Setup Mode” which starts).
From the bootloader, Setup mode will support only the following functions:
To restore functionality, try cycling power to the CHV-TSTATRF. If unit remains in bootloader, you should resend the latest firmware using Crestron Toolbox.
NOTE: To manually enter bootloader, press and hold the MODE button for 10 seconds during unit power up.
The latest version of all documents mentioned within the guide can be obtained from the Crestron website (http://www.crestron.com/manuals). This link will provide a list of product manuals arranged in alphabetical order by model number.
List of Related Reference Documents
DOCUMENT TITLE |
2-Series Control Systems Reference Guide |
C2N-MNETGW infiNET Gateway/Transceiver |
Further Inquiries
Future Updates
As Crestron improves functions, adds new features and extends the capabilities of the CHV-TSTATRF, additional information may be made available as manual updates. These updates are solely electronic and serve as intermediary supplements prior to the release of a complete technical documentation revision. Check the Crestron website periodically for manual update availability and its relevance. Updates are identified as an “Addendum” in the Download column.
Heat Pump Operation
Merchandise Returns / Repair Service
CRESTRON Limited Warranty
CRESTRON ELECTRONICS, Inc. warrants its products to be free from manufacturing defects in materials and workmanship under normal use for a period of three (3) years from the date of purchase from CRESTRON, with the following exceptions: disk drives and any other moving or rotating mechanical parts, pan/tilt heads and power supplies are covered for a period of one (1) year; touchscreen display and overlay components are covered for 90 days; batteries and incandescent lamps are not covered.
This warranty extends to products purchased directly from CRESTRON or an authorized CRESTRON dealer. Purchasers should inquire of the dealer regarding the nature and extent of the dealer’s warranty, if any.
CRESTRON shall not be liable to honor the terms of this warranty if the product has been used in any application other than that for which it was intended or if it has been subjected to misuse, accidental damage, modification or improper installation procedures. Furthermore, this warranty does not cover any product that has had the serial number altered, defaced or removed.
This warranty shall be the sole and exclusive remedy to the original purchaser. In no event shall CRESTRON be liable for incidental or consequential damages of any kind (property or economic damages inclusive) arising from the sale or use of this equipment. CRESTRON is not liable for any claim made by a third party or made by the purchaser for a third party.
CRESTRON shall, at its option, repair or replace any product found defective, without charge for parts or labor. Repaired or replaced equipment and parts supplied under this warranty shall be covered only by the unexpired portion of the warranty.
Except as expressly set forth in this warranty, CRESTRON makes no other warranties, expressed or implied, nor authorizes any other party to offer any warranty, including any implied warranties of merchantability or fitness for a particular purpose. Any implied warranties that may be imposed by law are limited to the terms of this limited warranty. This warranty statement supersedes all previous warranties.
Trademark Information
All brand names, product names and trademarks are the sole property of their respective owners. Windows is a registered trademark of Microsoft Corporation. Windows 95/98/Me/XP/Vista and WindowsNT/2000 are trademarks of Microsoft Corporation.
Crestron Electronics, Inc.
Specifications subject to change without notice.
This document was prepared and written by the Technical Documentation department at:
All brand names, product names and trademarks are the property of their respective owners.
©2008 Crestron Electronics, Inc.
Download Manual:
Crestron CHV-TSTATRF Wireless Programmable Thermostat Installation Guide
Crestron CHV-TSTATRF Wireless Programmable Thermostat Installation Guide
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…