Once temperature settings have been set for each zone in heating and cooling, the thermostat memory will retain these settings during seasonal changovers and times of no electrical power.
A connection for an “Auto Generator Start” appliance is included on the upper unit control board that is mounted in the return air of the air conditioner or heat pump. This calls for the generator to run when calling for the compressor for cooling or heating, or when calling for strip heat. Note that the generator will not be called for fan only operation or for gas heat operation.
The thermostat wiring is factory installed by the OEM (original equipment manufacturer). The thermostat connects to the upper unit(s) with a 9-pin plug and 2-pin plug (see system wiring diagram). The OEM must supply the 12 VDC wiring and the heating appliance control wiring which connects to the 9-pin plug on the thermostat. RV Products suggests the thermostat wiring be a minimum of 18 gauge.
Zone arrangement should be set with the front of the vehicle as zone 1 and progress toward the rear of the coach.
The OEM installed the upper control boxes for the zone system at the factory and programmed the thermostat for the system that is installed in this motor coach. Before programming the thermostat, it is imperative that the programmer knows the types of appliances that have been installed in the motor coach in each zone. The heating appliance control circuit must not exceed 1 Amp.
Control Box
The control box mounted in the return air plenum has an opening that allows viewing of the green LED on the control board. The green LED, when lighted, indicates that the control voltage is adequate to run the system. When the LED is not lighted, there is a problem with the 12 Volt DC control voltage and it must be serviced by a trained technician.
Caution
Application
Note:
Setpoint Buttons
The Setpoint buttons are located to the right and below of the LCD display. These buttons adjust the desired temperature setpoint up and down. To change the setpoint press UP or DOWN once. This displays the word Set on the LCD and puts the system in the mode to change the setpoint. Then, each press of the UP or DOWN changes the setpoint up or down for the displayed zone by one degree per press of the button. The setpoints are not adjustable when the thermostat is turned off. Also setpoint is not adjustable for the displayed zone when the displayed zone is set to run Fan High or Fan Low in that zone, or if the displayed zone is turned to Off. The setpoints are stored permanently in memory for each zone in both heating and cooling. This allows the user to switch between heating and cooling at season changes and still have the same settings as the previous year.
SYSTEM Button
ZONE Button
This button allows the user to toggle through the different area zones. By pressing the ZONE button the user toggles through each zone. When the system is first powered up, it determines how many zones are in the system and only displays the detected zones.
MODE Button
By pressing the MODE button, the user toggles through the different modes for the system. When in cool, the thermostat will toggle through the following modes: Cool Auto, Cool High, Cool Low, Fan High, Fan Low and Off. When in heat, the thermostat will toggle through the following modes: Gas Heat, Heat Elec and Off. However, this will only happen if the system has both gas and electric heat in a zone. For instance, if a system only has an air conditioner and a gas furnace in a zone, then when set to heat, the user will only be able to toggle through Gas Heat and OFF because there is not electric heat available. Furthermore, if the system does not have an appliance connected in a zone, then the user will not be able to toggle modes in that zone.
Setting the Thermostat
The thermostat default setting for each zone upon initial startup is 78°F for cooling and 68°F for heating. The fan speed for the cooling mode is COOL AUTO, which is set to vary the fan speed according to the cooling needs. The fan speed for the heating mode is dependent on the type of heat that is installed for each zone and can not be changed.
Note: The temperature setpoint cannot be adjusted in the following situations: when in OFF, when the zone is turned off for either heating or cooling mode or when the fan is set to be running continuously in either high or low speed.
Set Temperature
Changing Temperature Scale
Press both SYSTEM and MODE buttons in for 5 seconds. Temperature changes from °F to °C or °C to °F
Set Fan Speed for Cooling Mode
System | Mode | Zones | Demand | Control Box HP Jumper | Operation of Unit |
Off | N/A | 1 – 4 | N/A | N/A | No units operating in this mode, LCD is displaying temperature of zone. User can toggle thru zones to see temperature in each zone (setpoint can’t be adjusted) |
Cool | Cool Auto | 1 – 4 | No | N/A | Nothing is operating since there is no cooling demand, LCD is displaying temperature of zone |
Cool | Cool Auto | 1 – 4 | Yes | N/A | Compressor is energized, fan is energized |
Cool | Cool High | 1 – 4 | No | N/A | Fan high is energized |
Cool | Cool High | 1 – 4 | Yes | N/A | Compressor is energized, fan high is energized |
Cool | Cool Low | 1 – 4 | No | N/A | Fan low is energized |
Cool | Cool Low | 1 – 4 | Yes | N/A | Compressor is energized, fan low is energized |
Cool | Fan High | 1 – 4 | N/A | N/A | Fan high is energized (setpoint cannot be adjusted) |
Cool | Fan Low | 1 – 4 | N/A | N/A | Fan low is energized (setpoint cannot be adjusted) |
Cool | Off | 1 – 4 | N/A | N/A | Nothing operational in zone (setpoint cannot be adjusted) |
Heat | Elec | 1 – 4 | No | Non HP | Nothing is operating in this mode since there is no heating demand |
Heat | Elec | 1 – 4 | Yes | Non HP | Fan is energized, heat strip is energized |
Heat | Elec | 1 – 4 | No | Hp | Nothing is operating in this mode since there is no heating demand |
Heat | Elec | 1 – 4 | Yes | Hp | High fan energized, compressor & reversing valve energized |
Heat | Gas | 1 – 4 | No | N/A | Nothing is operating in this mode since there is no heating demand |
Heat | Gas | 1 – 4 | Yes | N/A | Gas heat energized |
Heat | Off | 1 – 4 | N/A | N/A | Nothing operational in zone (setpoint cannot be adjusted) |
Notes: 1) When 2nd or 3rd stage heating is activated, it stays on until setpoint is satified. When heating stage is running for more than 20 minutes without reaching setpoint then the next available heating stage will be energized. 2) The word “GAS” will display on the LCD when 2nd stage heat (low gas furnace) is operating. |
Heat Pump Lockout
If the system has both gas heat, (LP furnace or hydronic heat) and electric heat,(electric strip heat or heatpump) appliances installed in the same zone, then the system will automatically switch from Heat Electric to Gas Heat if the electric heat can not satisfy the desired setpoint temperature. Because of the nature of the electric heating systems, they tend to be less effective the lower the outside temperature. Therefore, at low temperatures, your electric strip heat or heatpump may not be able to satisfy the setpoint. The system switches from Heat Elec to Gas Heat when the actual zone room temperature is five degrees or more below the desired setpoint temperature. If this happens three times in a row, the electric heat is locked out for two hours and the gas heat is the primary heat source. When this happens, the LCD will continue to display Elec but the word Gas will flash on the LCD to alert the user that the electric heat source is locked out. See table below for an example of how the heatpump lockout system works.
Setpoint | Indoor Temp. | Operation |
70 | 70+ | Nothing is operating |
69 | Electric heat turns on (primary heat source) | |
71 | Electric heat turns off (thermostat satisfied) | |
69 | Electric heat turns on | |
65 | Gas furnace turns on (first strike for 2nd stage elec heat counter) *see note* | |
71 | Electric heat and gas furnace turn off | |
69 | Electric heat turns on | |
65 | Low gas furnace turns on (second strike for 2nd stage elec heat counter) *see note* | |
71 | Electric heat and gas furnace turn off | |
69 | Electric heat turns on | |
65 | Gas furnace turns on and electric heat turns off (2nd stage elec heat counter reaches 3rd strike and the electric heat is locked out for 2 hours) *see note* | |
71 | Gas furnace turns off (thermostat satisfied) | |
69 | Gas furnace turns on (becomes primary heat source) | |
71 | Gas furnace turns off (thermostat satisfied) | |
After 2 hour lockout | ||
69 | Electric heat turns on (resumes as primary heat source) | |
65 | Electric heat turns off and low gas furnace turns on (becomes primary heat source and the electric heat is locked out for another 2 hours) | |
71 | Gas furnace turns off (thermostat satisfied) | |
After 2 hour lockout | ||
69 | Electric heat turns on (resumes as primary heat source) | |
71 | Electric heat turns off (thermostat satisfied) (2nd stage elec heat counter is reset anytime the electric heat satisfies the thermostat setpoint and does not need the gas furnace) | |
Note: The word “gas” will flash on LCD when 2nd stage heat is operating. |
OEM must supply these mating parts to connect these thermostats as shown below. A minimum wire size of AWG 18 must be used for this system. Check with appliance manufacturers for exact wire size needed for each appliance.
Thermostat and Room Temperature Sensor Location
This system is designed to work one of two ways. A built-in temperature sensor on the thermostat can control zone 1. In this case the thermostat must be located in zone 1. On the other hand, a remote temperature sensor can be connected to zone 1. This situation would allow the thermostat to be located virtually anywhere in the coach as long as the user can get to it to operate it. Every zone other than zone 1 must always have a remote temperature sensor to control the system. This thermostat is a sensitive instrument. For accurate temperature control and comfort, the following considerations should be taken into account when locating both remote sensors and the thermostat if the thermostat is to be used as the zone 1 temperature sensor.
Attaching the Wall Thermostat and Room Temperature Sensors
Setting the Upper Control Board
When adjusting the jumpers on the upper unit control board be sure the line Voltage, (115 VAC) and the control Voltage, (12 VDC) are disconnected from the board. Failure to do this could result in injury or death.
Each zone must be controlled by an upper unit control board. When installed, this board is located in the return air plenum of the air conditioner (see installation instructions for the air conditioner control box). When installing the system, the upper unit control board must have two jumpers installed to operate properly. First of all, the zone jumper must be set according to which zone the board is to control. We recommend starting at the front of the coach as zone 1 and progressing towards the rear. If the board is to control zone 1, then the jumper must be across the two jumpers labeled 1 and so on for each zone (see drawing below). The second jumper that must be installed is the HP/NON-HP jumper (see drawing below). This tells the system whether the unit being controlled is a heat pump or not. If the unit being controlled is a heat pump, the jumper must be between the center post and the one closest to the HP. Likewise if the unit being controlled is not a heat pump, then the jumper must be between the center post and the one closest to NON-HP. For further explanation, see installation instructions for the control box
The green LED lights when there is adequate control voltage, (12 VDC) at the board. The green LED will initially flash the number of times corresponding to the zone jumper setting. The green LED will stop flashing when communication with the thermostat is established. For further explanation, see troubleshooting section of manual.
CAUTION: All zones boards must be wired and should have 12 VDC at each one before programming can be done. The system only needs to be programmed once. The programmer must know what appliances are installed in each zone before proceeding with programming. If the system is programmed incorrectly the user will not be able to operate some of the climate control appliances that are installed.
If these applications are connected: | Then thermostat LCD display that should be selected is: | |||||
A/C | Cool | |||||
A/C | Gas Heater | Cool | Gas | Heat | ||
Gas Heater | Gas | Heat | ||||
A/C | Gas Heater | HP or Strip Heat | Cool | Gas | Heat | Elec |
A/C | HP or Strip Heat | Cool | Heat | Elec |
Toggle through all options, then stop at the desired one. Once the correct setup is selected for zone
Note: If two or more upper unit control boards have been set to the same zone, the units will operate the same as one another.
Symptom | Remedy |
No display on LCD | No power to the thermostat (Remove the ceiling assembly grille and look in the round opening of the control box for green LED light. Light not displayed, there is no power to the control box). |
Heat or Cool displays on the thermostat, but can’t modify settings | Appliances may not be installed on this coach, check the homeowners’ packet |
“Er” displayed on the thermostat | The current temperature may be outside the display range of the thermostat The external room sensor circuit may be disrupted. Contact service technician. |
Temperature does not change on the thermostat when the unit is running | The current temperature may be outside the display range of the thermostat (thermostat designed to show 41°F-110°F) |
Appliances not responding to thermostat setting changes | Zone or appliance settings on upper control boards may not be correct for zones or appliances installed Built-in delay for communication signal |
Setpoint cannot be adjusted | Check the setting of the thermostat (Setpoint cannot be adjusted when SYSTEM is set to OFF, Cool or HEAT mode is set to OFF, the zone is turned OFF, or FAN is set to run HIGH or LOW continuously) |
GAS flashing on LCD display | The backup heat source is energized to supplement primary heat |
Backup heat source running with Heat Pump idle | Heat pump is unable to keep up with heating demand, system locks out heat pump for 2 hours and backup heat becomes the primary heat source for those 2 hours |
Two or more units have an identical operation | Upper unit control boards may be set to the same zone. Have the service technician check. |
Unit not responding | Communication signal lost to that zone (Signal wire might have vibrated loose). The system does not operate below 9.75 VDC. |
DOWNLOAD MANUALS:
Coleman 9330A3341 PROGRAMMABLE Thermostats Installation Manual
Coleman 9330A3341 PROGRAMMABLE Thermostats Installation Manual
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…