Read and follow manufacturer instructions carefully. Follow all local electrical codes during installation. All wiring must conform to local and national electrical codes. Improper wiring or installation may damage AC/HP Control. Recognize safety information. This is the safety- alert symbol . When you see this symbol on the equipment and in the instruction manual, be alert to the potential for personal injury. Understand the signal words DANGER, WARNING, and CAUTION. These words are used with the safety- alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies a hazard which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
Carrier’s 7-day, 5/2-day, 1-day programmable and non-programmable Performance Series Thermostat Control is a wall-mounted, low- voltage temperature control in either a single unit or a two- piece unit. In two- piece configuration, the relays are located near the equipment and a two-wire connection is used between the Display Module and the Equipment Control Module. Single-piece installation requires more wiring and results in a higher profile. The Edget Thermostat has no need for batteries to store user- configured settings in memory. During power loss its internal memory saves settings for unlimited time, and the clock continues to run for at least 24 hours. An extension of Carrier’s proven line of thermostats; it provides separate setpoints for heating and cooling. In the Edge Thermostat Control programmable configuration, different heating and cooling setpoints and times are programmable for 4 periods per day or 2 periods per day. Programming can be done for 7 days per week, 5/2 days per week, or 1 day. The programmable Thermostat Control can also be user configured as a non- programmable Thermostat Control. The non-programmable Thermostat Control features Touch ’N’ Got settings for quick and easy temperature change without complicated programming schedules. And, its Touch ’N’ Go technology enables the user to switch between three different user- configurable settings through intuitive buttons located just below the display.
Power
This control is powered by 24VAC only. It requires 24VAC (Rh and/or Rc and C terminals) of the low-voltage transformer to be connected to it for proper operation. It will not operate without these 2 connections. Rh and Rc are connected via PCB breakout jumper. See Fig. 1. For applications using two 24VAC transformers, one in the indoor unit and one in the outdoor unit, connect the common from each to the C terminal. Connect R from the indoor unit to the Rh terminal. Connect R from the outdoor unit to the Rc terminal. Then, break jumper on the circuit board. The W signal is taken from the Rh power and the G signal is taken from the Rc power. If the thermostat has been installed in a two- transformer application that is later changed to a single- transformer installation, installer must install a field supplied jumper between Rc and Rh. Depending on the installation, up to 14 wires may be required. Installation as two-piece unit is recommended. Only 2 wires are required for connection between Display Module and Equipment Control Module. These two wires (V+ and Vg) do not provide ordinary 24VAC. They carry a combination of power and communications data that is unique to these products.
Failure to follow the recommended wiring practices could result in damage to the wall control and personal property. Improper wiring or installation may damage AC/HP Control. Check to make sure wiring is correct before proceeding with installation or turning on power.
! CAUTION
Installation Notes:
Carton contains the following components. See Fig. 3 for programmable models or
Fig. 4 for non-programmable models.
AC/HP Control Location
AC/HP Control should be mounted:
AC/HP Control should NOT be mounted:
The installer should determine whether the control will be installed as single- a piece or two-piece. In a single-piece configuration, as many as 14 wires may need to run to wall mounting location for connection to the control. In two- piece configuration,
the Display Module and Equipment Control Module are connected by two wires.
Install AC/HP Control
WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing AC/HP Control, turn off all power to equipment.
There may be more than 1 power disconnect.
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Improper wiring or installation may damage AC/HP Control. Check to make sure the wiring is correct before proceeding with installation or turning on power.
CAUTION
ENVIRONMENTAL HAZARD
Failure to follow this caution may result in environmental damage.
Mercury is a hazardous waste. Federal regulations require that Mercury be disposed of properly.
The following steps should be followed for the installation of the two-piece configuration.
NOTE: The 2-wire pigtail is not intended to support the weight of the User Interface. Do not hang the User Interface from the equipment Control Module screw terminals.
The following steps should be followed for the installation of the single-piece configuration.
Configuration options enable the installer to configure the thermostat for a particular installation. Most are not presented to the homeowner and therefore must be properly set by the installer. (Only those marked with an asterisk * below are
available to the homeowner.) The homeowner configurations are described in the owner’s manual. A special procedure allows entry into the configuration mode. Description of each selection and how to use the configuration mode follows.
CONFIGURATION OPTIONS – SUMMARY
TO ENTER CONFIGURATION MODE
Press and hold FAN button for approximately 10 sec. The Display Module is now in configuration mode. It will automatically exit this mode if no button is pressed for 3 minutes. Pressing either FAN or DONE button will exit configuration mode immediately.
The option number is displayed in the heat setpoint location and the configuration setting is displayed in the cool setpoint location. On the TP-PAC/PHP (programmable) models, a box will surround the option number. The mode button is used to move the box between the two displayed values. The soft keys below the listed values may also be used to move the box between selected values. The value inside the box is changed by using the UP/DOWN buttons. On the TP-NAC/NHP (non-programmable) models, one of the values will be flashing. The mode button is used to change which value is flashing or the Home and Sleep buttons may also be used to select which value to flash. The value that is flashing is changed by using the UP/Down buttons. All changes made are saved at the time of selection and will be saved in the event of the 3 minute time- out or when installer exits from configuration menu
Option 01 —Equipment Type
Option 02 —Clean Filter Timer
Select hours of blower operation (heating, cooling, or fan) before CHECK FILTER icon is displayed. With OF selected, icon will never come on, disabling this feature. Time selection can range from 800 to 7200 hr by selecting numbers 1 through 9. (Time is 800 X number selected.) Default is 4 (3200 hr). Recommended selections are disposable filter-800 to 2400 hr, media filter-2400 to 3200 hr, or electronic air cleaner-1600 to 2400 hr of blower operation. For higher efficiency filter, please consult filter’s Installation Instruction for details.
Option 03 —Fahrenheit/Centigrade
Select between Fahrenheit (F) and Centigrade (C) operation. Factory default is Fahrenheit (F).
Option 04 —Fan (G) OnWithW/W1
This selection determines whether fan (G) output is to be On or OFF when any W/W1 (furnace or strip heat) output is On. Most furnaces and fan coils manage their own blowers and do not require separate G signals. For these applications, select OFF. Some auxiliary heaters require a separate G signal to turn on blower. In this case, select On. Default is OF (off).
Option 05 —Room Air Temperature Sensing (programmable models only)
The remote room sensor may be installed as a single sensor or multiple sensors may be installed for further averaging functionality. See Fig. 17
This selection determines which sensor the control will use for measuring room air temperature. Room air temperature can be sensed in one of three ways; the local sensor (L) located on the Display Module, the remote room air sensor (r), or the average of local and remote sensors (Lr). Settings are L, r, Lr. Default is L.
Option 06 —Cooling Lockout Below 55_F/13_C
This selection disables cooling when outdoor temperature is below 55_F/13_C. It requires an outdoor temperature sensor. Setting is not available if valid outdoor sensor is not connected. Set to OF (off) to allow cooling below 55_F/13_C. Set to On to prevent cooling below 55_F/13_C. Factory default is OF (off).
Option 07 —Zoning
This selection should be set to On when the thermostat is to be used as part of a zoning system. It is assumed that the zoning equipment will take care of time guard and cycle timers. The minimum on time is still controlled by the thermostat. Default is OF (off).
Option 08 —Auxiliary Heat Lockout Temperature
This selection is available on heat pump systems with a valid outdoor temperature sensor connected. Available settings are: Off, 5, 10, 15, 20, 25, 30, 35, 40, 45, 50, 55.
OF (off) – function is disabled. Auxiliary heat is allowed to operate whenever sufficient demand for heat is available.
5 to 55_F (-15 to 13_C) – Outdoor temperature above which the auxiliary heat is not allowed to operate (unless MODE is set to Emergency Heat). If room temperature falls below 45_F (7_C), the auxiliary heat will be allowed to turn on and will continue to run until demand is satisfied. Default is OF (off).
Option 10 —Reversing Valve
This selection is only available on heat pump systems. “O” terminal can be configured to be energized in either heating mode or in cooling mode, depending on heat pump operation. “O” is used to describe a heat pump system that energizes its reversing valve in cooling. “B” is used to describe a heat pump system that energized its reversing valve in heating. H — Reversing valve output (O/W2/B) is energized when HEAT mode is selected.
C — Reversing valve output (O/W2/B) is energized when COOL mode is selected. Default is C.
Option 11 —Deadband Setting Between Heat & Cool
This option is not available on Heat Only and Cool Only systems. This selection is
to allow the installer to choose how much differential exists between the heating
and cooling setpoints. Allowable selections are 1-6.
Default is 2.
Option 12 —Smart Recovery
Smart Recovery OF (off) means setpoints change precisely at setback recovery time. Thirty, 60, or 90 selects the number of minutes recovery starts before programmed recovery time. Recovery takes place smoothly during the selected recovery time, ending at the recovery time and temperature which is programmed. Not available with non-programmable thermostats or when thermostat is configured as non-programmable. Default is 90.
Option 13 —Room Air Temperature Offset Adjust
The number of degrees to be added to the displayed temperature to calibrate or deliberately miscalibrate the measured room temperature ( -5 to +5_). Default is 0.
Option 15 —Enable Auto Mode
This selection is not available if the thermostat is configured as Heat Only or Cool Only in Option 1. This allows the homeowner to select auto changeover mode in addition to heat and cool. This allows the thermostat to automatically change between heating mode and cooling mode when sufficient demand for heating or cooling exists.
Option 16 —Maximum Cycles Per Hour
This selection limits the number of cycles per hour that the thermostat allows the system to operate. Selections are 2, 4, 6.
Option 17 —Time Between Equipment Stages
This selection is only available for heat pump systems. This determines the minimum number of minutes of equipment operation on the highest compressor stage before allowing the transition to auxiliary heat. Available selections are 10, 15, 20, and 25. The time between stages of any individual piece of equipment, such as low speed and high speed compressor or fan coil stages, will be fixed at 10 minutes.
Default is 15.
Option 18 —Backlight Configuration
When OF (off), the backlight will be lit for 10 seconds after a button is pressed. After 10 seconds of no button presses, the backlight turns off. When On, the backlight will normally be on and dim in appearance. The backlight brightness becomes brighter when a button is pressed. After 10 seconds of no button presses, the backlight will return to the dimmer level until another button press occurs. The range of brightness is 1 through 5 with 5 being full brightness. Default is 3.
Option 19 —Dry Contact Configuration (programmable models only)
There are 2 available selections, OF and 1.
Option 20 —Outdoor Air Temperature Offset Adjustment
This selection allows the calibration, or deliberate miscalibration of the outdoor air temperature sensor reading. The selection ranges from -5 to +5_.
Default is 0.
Option 21 —Keypad Lockout (programmable models only)
This selection allows the installer to limit access to the keypad. Selections are OF (off), 1, 2, 3.
OF (off) — The user has full access to the keypad.
When the keypad lock selection is turned on, the padlock icon will be displayed. To unlock the keypad, press and hold the UP/DOWN buttons simultaneously for five seconds. When the keypad is unlocked, the padlock icon will turn off. The keypad will remain unlocked for two minutes after the last button press. After two minutes with no button presses, the keypad will lock again. The keypad will not lock in the software configuration mode or in the installer test mode.
Default is OF (off).
Option 21 —Keypad Lockout (non- programmable models only)
This selection allows the installer to limit access to the keypad. Selections are OF (off), 1, 2.
When the keypad lock selection is turned on, the padlock icon will be displayed. To unlock the keypad, press and hold the UP/DOWN buttons simultaneously for five seconds. When the keypad is unlocked, the padlock icon will turn off. The keypad will remain unlocked for two minutes after the last button press. After two minutes with no button presses, the keypad will lock again. The keypad will not lock in the software configuration mode or in the installer test mode.
Default is OF (off).
Option 22 —High Cool Latch Temperature (only available if outdoor sensor is present)
An outdoor sensor is required for high cool latch feature.
This selection is only available when Option 1 is set to H2, A2, or h2 and when
Option 7 (zoning) is set to OF (off). Configuration settings are OF (off), 80, 85, 90, 95, 100, 105, 110, On.
OF (off) — Cooling always starts in low stage (Y1) and stages up to high stage (Y1 and Y/Y2) when demand is sufficient and staging timer constraints have been satisfied.
80 to 110_F (27 to 43_C) — Outdoor temperature above which both first and second stages of the compressor are energized to satisfy all cooling demands.When a cycle starts under a high cool latch, it will finish the cooling cycle on high stage. On — The Y1 and Y/Y2 outputs are simultaneously energized to satisfy all cooling demands.
Default is OF (off).
Option 23 —High Heat Latch Temperature (only available if outdoor sensor is present)
This selection is only available when Option 1 is set to H2, or h2 and Option 7 (zoning) is set to OF (off). Configuration settings are OF (off), 20, 25, 30, 35, 40, 45, 50, On.
Option 24 —Programmable/Non-Programmable
This selection allows the installer to configure the thermostat as either programmable or non-programmable. Selections are P, nP.
Default is P (programmable models only).
Option 25 —Number of Programmable Periods
This selection allows the installer to configure the thermostat for two or four periods per day. Two periods is a common commercial application and four periods is more common for residential. This selection is not available if Option 24 has been set to nP to configure the thermostat for non-programmable operation.
Option 26 —Minimum Cooling Setpoint
This selection allows the installer to configure the minimum cooling setpoint that the user is allowed to set. The range is based on the value of the adjustable deadband Option 11, such that the minimum of the range is 50_F/10_C plus the adjustable deadband and the maximum is 90_F/32_C. Default is 52_F/11_C (based on the adjustable deadband default = 2).
Option 27 —Maximum Heating Setpoint
This selection allows the installer to configure the maximum heating setpoint. The range is based on the adjustable deadband value Option 11, such that the minimum of the range is 50_F/10_C and the maximum is 90_F/32_C minus the deadband.
Default is 88_F/31_C (based on the adjustable deadband default = 2).
Option 28 —UV Light Reminder
This selection allows the installer to select the number of months after which the UV Light icon will be displayed to indicate to the homeowner that it is time to call the dealer to have the UV Lights replaced. Selections available are OF (off), 6, 12, 18, 24, 30, 36, 42, 48.
Option 30 —Programmable Fan (programmable models only)
This selection allows the homeowner to program the fan selection to “Auto” or
When the program schedule is running, the programmed heat setpoint, cool setpoint, and fan selection for that period will be used. If the homeowner “overrides” the programmed fan setting by pressing the fan button, the overrideselection will remain in effect until the next programmed period time.
Default is OF (off).
Option 31 —Daylight Savings Time Configuration (programmable models only)
This selection allows the installer to set the thermostat to automatically change by one hour on the specified day, month, and week specified.
Option 32 —Furnace Heat Staging Control (available only when the HP thermostat is configured to operate AC equipment or Heat Only).
Option 33 —Single or Two-Piece Installation
This configuration allows the thermostat to compensate for the amount of heat generated by the thermostat electronics to allow more accurate sensing of the temperature sensor. The amount of heat compensation will be different between single installation and two-piece installation.
Range: 1P or 2P
Option 41 —Variable Speed Blower
This selection allows the installer to select between a single speed or variable motor.
Option 44 —Super Comfort Heat
This option is only available on heat pump units HP (HP, H2) when Option 41 (Variable Speed Blower) is set to On and the system has a valid OAT sensor.
If the outdoor air temperature is between 12 to 40_F (-11 to 4_C) and the compressor is running in heating, then the fan output is turned off. This will signal the variable speed blower to reduce the air speed. The fan output is turned off even if the user has the fan selection set to continuous fan. The fan output will be turned back on in this temperature range if the maximum capacity of auxiliary heat is on due to system demand (auxiliary heat on in response to a defrost signal shouldn’t cause the fan to turn back on).
If the outdoor air temperature is below 12_F/-11_C and there is sufficient demand for the equipment to be on, then the fan output is turned back on and the W/W1 output is energized. In a two speed unit the Y/Y2 output should be energized in addition to the W/W1 output.
NOTE: All temperature boundaries have a +/- 2_ hysteresis. Factory default is OF (Off).
Option 99 —Reset to Factory Defaults
Use this capability to reset the stat to “out of the box” conditions. BEWARE! All configuration settings, program settings, clock, and calendar which have been manually entered will be lost!
When this option is selected, the configuration number (99), will appear on the left and 10 will appear on the right. To perform the reset, first use the MODE key to move the box from the 99 to the 10 (programmable model) or to flash the 10 (non-programmable model). Then press and hold the DOWN key. The 10 will start counting down toward zero. If the DOWN key is kept pressed until the count reaches zero, the reset will be performed. When the value reaches zero, the heat setpoint shall display – – . The cool setpoint shall display – and the room air temperature shall display Fd. When the factory defaults have been restored, the thermostat will act as if power was cycled and return to normal operation. If the DOWN key is released early, the number will return to 10 and the reset will not occur.
Be sure to press DONE to exit installer setup mode. If the system is to be left in operation after installation is complete, use MODE button to select between HEAT, COOL, or AUTO to provide desired operation of heating, cooling, or auto. On the programmable models, the default setpoints and programmed schedule conform to the Energy Starr requirements of the U.S. Department of Energy for both heating and cooling. These provide energy saving temperature settings. Refer to Table 1.
SCHEDULE | HEAT | COOL |
Wake 6:00 AM | 68_F/20_C | 78_F/26_C |
Day 8:00 AM | 60_F/16_C | 85_F/29_C |
Evening 5:00 PM | 68_F/20_C | 78_F/26_C |
Sleep 10:00 PM | 60_F/16_C | 82_F/28_C |
If the programmed schedule is to be used, make sure the triangle icon next to the FOLLOW SCHEDULE icon is turned on. Pressing the Schedule button will cycle the triangle icon through the FOLLOW SCHEDULE, HOLD and VACATION selections. If fixed temperatures are desired, use SCHEDULE button to turn on arrow icon next to HOLD. This will maintain setpoints, not allowing them to change with the programmed schedule.
MODE | AUTO |
Fan | Auto |
Heat Setpoint | 55_F/13_C |
Cool Setpoint | 85_F/29_C |
Three-Minute Minimum on Time
In normal operation, when a stage turns on, it will not turn off for a minimum of 3 minutes. If the setpoint is changed, this timer is canceled, allowing the equipment to turn off immediately when the demand is removed.
Heat/Cool Setpoints (Desired Temperature)
A minimum difference of 1_ and maximum of 6_ is enforced between heating and cooling desired temperatures. This is done by allowing 1 setting to “push” the other, to maintain this difference. This difference is adjustable via Configuration Option.
Equipment On Indicators
When cooling equipment is on, a COOL ON icon is displayed. While cooling equipment operation is delayed by the timeguard or cycle timer, COOL ON will flash. The same is true for HEAT ON.
When the W is energized in a heat pump, the auxiliary heat on icon will be displayed.
Auto Changeover
When auto changeover mode is selected, a change from heat to cool (or vice versa) will not occur until an opposite mode demand has existed for 20 minutes. If setpoint is changed, 20-minute requirement is deleted.
Emergency Heat Mode
When AC/HP Control is configured as a heat pump and emergency heat is selected, all Y signals are locked out, and W becomes energized upon a call for heat.
Programmable Fan (programmable models only)
The fan output can be programmed based on period of the day. When programming for each day and period the fan can be set to On or AUTO. If the fan button is pressed to change from On to Auto or vice versa when programmable fan has been enabled, the manual change will only remain in effect until the next program period, when the programmable fan setting will be changed per the scheduled setting.
Dry Contact
On the programmable models, the dry contact that can be used for control of an auxiliary device. The dry contact may be configured to be closed for a specific number of minutes per hour for each period of the program schedule. This can be used to operate a ventilator, damper, system blower, or another auxiliary device. There are two terminals, D1 and D2.
If it is desired to operate a ventilator or other device, the D1 and D2 terminals can be connected directly to the equipment. This will provide a closed contact for the specified number of minutes per hour. See Option 19. If timed control of the system blower is required, the dry contact can be used for this function. The G terminal can be connected to one of the dry contact terminals with the other terminal being connected to Rc and/or Rh for timed control of the fan. Note that this is not the same as the programmable fan Option 30.
See Wiring Diagrams for more information.
Relays
This thermostat uses latching relays. When the thermostat loses power, the relays will remain in their last position until power is restored and all relays are reset to their correct position. Out of the box, the outputs may appear to be On when the thermostat is not powered. This is normal. Output states should only be checked when the thermostat is powered.
Temperature Offset After Power Cycle
To compensate for internal heat build-up from the electronics in the thermostat, the thermostat will add an offset to the actual temperature that it measures. If the thermostat power is cycled quickly, one can witness an immediate increase in the actual temperature displayed due to this added offset. The thermostat display will return to the actual room temperature after several minutes of operation.
If the display module doesn’t power up after power is applied, check the Rc/Rh and C terminals for 24VAC. If 24VAC is present, check the voltage between Vg and V+. This voltage will be approximately 12-20VDC. If voltage is present, check the polarity to make sure it is wired correctly. The display will not power up if polarity is reversed.
If dashes appear for Option 01 in config and during reboot, the problem could be the red pigtail being wired to Rc or Rh and the black pigtail being wired to C. If so, remove the two-wire pigtail and connect to the V+ and Vg terminals.
Error Codes
“- – ” – If AC/HP Control cannot properly read room temperature, display will indicate “- – ” and all outputs (except fan, if on) will turn off. In the case where the installer has selected to average the local sensor and the remote room sensor, the AC/HP display will alternate between “- – ” for the failed sensor and the temperature sensed by the working sensor every 10 seconds. The control will operate from the temperature sensed by the working sensor.
Table 3 can be used as a troubleshooting tool for determining which outputs will be active for a particular configuration and each operating mode.
When replacing a failed component such as an equipment control module or a display module, the installer should replace both parts as a matched set. It is very easy to accidentally mix an A/C or HP display with a PAC equipment control module.When this happens, some functions appear in the setup while others do not. This can be very confusing to troubleshoot. Verify that both parts have the same model and serial number when troubleshooting the thermostat.
Table 3 – Equipment Configuration Outputs
For COOL, HEAT and Emergency Heat modes, the following chart shows the state for each output in each stage of operation
Equip Config | Tstat Model | COOL STG 1 | COOL STG 2 | HEAT STG 1 | HEAT STG 2 | HEAT STG 3 | HEAT STG 4 | EM HEAT STG 1 | EM HEAT STG 2 |
SS AC Opt 1 = AC | TP- PAC TP- NAC | Y/Y2 | – – | W/W1 | – – | – – | – – | – – | – – |
SS AC Opt 1 = AC | TP- PHP TP- NHP | Y/Y2 | – – | W/W1 | W/W1 O/W2/B (if Opt. 32 = 2) | – – | – – | – – | – – |
SS HP Opt 1 = HP RVS = O Opt 10 = C | TP- PHP TP- NHP | Y/Y2, O/W2/B | – – | Y/Y2 | Y/Y2, W/W1 | Y/Y2 W/W1 | – – | W/W1 | W/W1 Y1/W2 |
SS HP Opt 1 = HP RVS = B Opt 10 = H | TP- PHP TP- NHP | Y/Y2 | – – | Y/Y2, O/W2/B | Y/Y2, W/W1, O/W2/B | Y/Y2, W/W1, Y1/W2, O/W2/B | – – | W/W1 | W/W1 Y1/W2 |
2SPD AC Opt 1 = A2 | TP- PHP TP- NHP | Y1/W2 | Y/Y2, Y1/W2 | W/W1 | W/W1 O/W2/B | – – | – – | – – | – – |
2SPD HP Opt 1 = H2 RVS = O Opt 10 = C | TP- PHP TP- NHP | Y1/W2, O/W2/B | Y1/W2 Y/Y2 O/W2/B | Y1/W2 | Y1/W2 Y/Y2 | Y1/W2, Y/Y2, W/W1 | – – | W/W1 | – – |
Equip Config | Tstat Model | COOL STG 1 | COOL STG 2 | HEAT STG 1 | HEAT STG 2 | HEAT STG 3 | HEAT STG 4 | EM HEAT STG 1 | EM HEAT STG 2 |
2SPD HP Opt 1 = H2 VS = B Opt 10 = H | TP- PHP TP- NHP | Y1/W2 | Y1/W2 Y/Y2 | Y1/W2 O/W2/B | Y1/W2 Y/Y2 O/W2/B | Y1/W2 Y/Y2 O/W2/B W/W1 | – – | W/W1 | – – |
Heat Only Unit Opt 1 = H | TP- PHP TP- NHP TP- PAC TP- NAC |
– – |
– – |
W/W1 | If HP or RH board & Opt. 32 = 2 W/W1 O/W2/B |
– – |
– – |
– – |
– – |
Cool Only Unit Opt 1 = C | TP- PHP TP- NHP TP- PAC TP- NAC | Y1/W2 | Y1/W2 Y/Y2 Ig- more for SS | – – | – – | – – | – – | – – | – – |
Installer
_________________________
Model Number
_____________________________
Date
_______________________
Copyright 2017 Carrier Corporation 7310 W Morris St. Indianapolis, IN 46231
TP – PACA – 02SI Replaces: TP – PACA – 01SI
Edition Date: 04/17
The manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations
Download Manual: Carrier TC-PAC01-A Non–Programmable Thermostat Installation Instructions
Carrier TC-PAC01-A Non–Programmable Thermostat Installation Instructions
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…