The weekly programmable thermostat, suitable for all heating and/or cooling system, is fitted with a large and clear backlit display to keep all its functions under control in real time. The programmable thermostat is pre-programmed in the factory for operation defined as standard, therefore, right after connection to the utility to control, battery insertion, mandatory current date and hour setting and confirmation of automatic daylight saving time/standard time change (EURO=Italy and Central Europe UTC+1), it is ready for immediate use, displaying current date and time, daily profile/standard time in Winter mode (heating). The fundamental feature is its easy to use menu navigation, which makes it extremely user-friendly despite its comprehensive range of functions. Two winter and two summer programs are already set in its permanent memory with 3 temperature levels+antifreeze feature, designed to offer the utmost comfort, although changing them only takes few seconds to select the desired temperatures throughout the day (even every 30 minutes!) and for every day of the week. The programmable thermostat is factory-set to adjust temperature in a Differential ON/OFF manner and hysteresis can be set from 0.2°C to 1.2°C to adapt to the thermal inertia of your specific installation. Alternatively, modulating Proportional operation may be selected with settable duration cycles (from 7 to 20 minutes): this system ensures the desired temperature is maintained more stable, increasing user comfort and is particularly suitable for installations with high thermal inertia such as, for instance, for underfloor radiant panels. The set temperature scale is in degrees Centigrade (Celsius) with the option to calibrate room temperature measurement setting a correction value (from -3 to +3 °C); when switching to the Fahrenheit scale all displayed temperature values are updated accordingly. The programmable thermostat can be connected to a separate remote controllable temperature probe (optional) which may then be set according to one’s installation needs: remote, floor, external. Special attention was devoted to energy saving: temporary or permanent override with independent SET temperature from the current weekly program, the Holiday program, pausing for household cleaning, optional Set temperature (MAX/MIN) lock, adjustable anti-freeze temperature value, control through an external contact (e.g. optional telephone programmer), are conducive to avoiding wasting energy with consequent savings. See the following pages for a description of these as well as of other features.
WARNINGS!
DISPOSAL OF OLD ELECTRICAL AND ELECTRONIC EQUIPMENT
1 – TECHNICAL DATA | |
Power supply | n° 2 Alkaline batteries 1,5 V type AA (LR6) |
Autonomy: | Approx. 2 years |
Battery life after the “battery low” symbol starts flashing on the display: | Approx. 15 days |
White color backlight: | timed 6 sec. (default) / always off |
Type of action, disconnection and device: | 1 / B / U / Electronic |
Type of output: | voltage free relay with COM / NO / NC changeover contact, max 5(3)A/250 V ~ |
Software: | class A |
Rated impulse voltage: | 4 kV |
Cross-section of wires to terminals: | 1,5 mm2 ÷ 2,5 mm2 |
Contact input for remote switching on: | for NO or NC contact free from potential |
Input for separate remote probe: | yes – probe may be set depending on use: remote, floor, external |
Type of insulation: | class II |
Degree of protection: | IP 30 |
Pollution rating: | normal |
Number of temperature levels: | no. 3 « comfort», «activity» (pre-comfort), «economy» + antifreeze |
Ambient temperature display range: | – 5.0 °C ÷ + 37.7 °C (+ 23 °F ÷ +99.9 °F) |
Floor probe threshold display range: | – 0.0 °C ÷ + 60.0 °C (+ 32 °F ÷ +140 °F) |
External probe display range: | – 9.9 °C ÷ + 60.0 °C ( +14.2 °F ÷ +140 °F) |
Relay ON signal: | Flashing + ON (winter) or + ON (summer) |
Room temperature indicator resolution: | 0.1 °C (0.1 °F) |
Temperature Set adjustment range (t1/t2/t3): | +5 °C ÷ +37.7 °C (+41.0°F ÷ +99.9 °F) limitable |
Setting temperature Set: | adjustable by 0.1 °C / 0.1 °F sets |
Temperature correction (Offset): | adjustable from -3.0 °C (5.4°F) to +3.0 °C (5.4°F) default 0.0 °C/0,0 °F |
Antifreeze temperature: (t ): | adjustable + 5 °C ÷ <t3 (41,0 °F ÷ <t3) default 6 °C (42.8 °F) |
Type of temperature adjustment: – DIFFERENTIAL ON/OFF (default) – Proportional with the control period | adjustable from 0.2 °C to 1.2 °C (from 0,3 °F to 2.1 °F) default 0,3 °C (0,4°F) cycles adjustable from 7 to 20 minutes (default 10 minutes) |
Thermal gradient: | max 1°K / 15 min |
Temperature reading tolerance: | ± 0,5°C (± 0,9°F) |
Operating temperature limits: | 0 °C ÷ +45 °C |
Storing temperature limits: | -10 °C ÷ +60 °C |
Reference regulations for CE markings: | LVD – EMC EN60730-2-7 EN60730-2-9 |
The data entered in the programmable thermostat called «FACTORY SETTINGS» refer to an operation defined as «Standard». The following chapters describe all customizable functions, in order to satisfy any ambient comfort need.
Parameter | Default | Restore «reset» |
Language | IT (Italian) | To confirm |
Year/month/day/hour-minutes | To set | To confirm |
Daylight saving/ Standard time | Euro (UTC+1) | Last value |
Active season | Winter | Default |
Temperature unit of measure | °C (Celsius) | Last value |
Set Winter t1 | 20.0°C | Default |
Set Winter t2 | 18.0°C | Default |
Set Winter t3 | 15.0°C | Default |
Set antifreeze t$ | 6.0°C | Default |
Set Summer t1 | 24.0°C | Default |
Set Summer t2 | 27.0°C | Default |
Set Summer t3 | 33.0°C | Default |
Temp. locks Winter | Disabled | Default |
Temp. locks Summer | Disabled | Default |
Weekly hourly profile | P01 | Default |
Weekly hourly profile | P03 (not active) | Default |
Temp. adjustment mode | DIFF. ON/OFF | Default |
Differential hysteresis | 0.3°C | Default |
Modulating proportional | Prop (not active) | Default |
Modulating period | 10 min. (not active) | Default |
Room temp. correction | 0,0 °C | Default |
Room temp. correction | 0,0 °C | Default |
Anti-scale protection cycle | Disabled | Last value |
Display contrast | Level 6 | Default |
Display back-lighting | Timed 6 sec. | Default |
Parameter | Default | Restore «reset» |
Remote probe | (not active) | Last value |
External input | (not active) | Last value |
User password | none | Default |
Installer password | none | Default |
Password reset code | 0927 | Default |
FACTORY SETTINGS TABLE (default)
RESTORE «Installer RESET»
Restore many factory settings (default) RESTORE brings the programmable thermostat back to factory settings with the exception of some items as shown in the table; to perform the operation follow the instructions in paragraph 11.15.
RESTART
It does not cancel the entered settings Should the programmable thermostat feature malfunction, wrong displays, or other incorrect conditions, perform a «User reset». Simultaneously press for 4 sec. the Menu and
Press simultaneously for 4 seconds
Backlit display
Touching any key activates back-lighting, displaying the selection and navigation of the words, press the desired key within 6 sec. to vary the settings (touching any key reactivates a 6-sec timeout).
DIMENSIONS
INSTALLATION EXAMPLE
Switch off mains power 230V~ to device
Fasten the base of the programmable thermostat with the screws supplied: to the wall, to the rounded or rectangular recessed box via the relatively paired holes A.
Important: the installation and electrical connection of the devices and appliances must be implemented by qualified personnel and in conformity with current laws and regulations. The manufacturer declines all liability in connection with the use of products subject to special environmental and/or installation standards.
Examples of electrical connections
PROCEDURE TO FASTEN OR REMOVE THE PROGRAMMABLE THERMOSTAT TO/FROM THE WALL-MOUNTED BASE
After having made the electrical connections:
Removing the programmable thermostat from the wall base
Unhook the programmable thermostat from the wall base, using a screwdriver in the specific slot (D) in the lower part of the device for leverage, then remove it
Convenient programming
All programming operations may be performed before fastening the device to the wall base; this means programming may be carried out while comfortably seated. the flashing ON indication with fixed winter or summer symbol indicates that the programmable thermostat is detached from the wall base. Should programmable thermostat programming take place before fastening towall base, upon completing installation the ON indication (off or flashing) on the display might not correspond to the actual relay status. Within 1 minute at the most after fastening the programmable thermostat to the wall base, the relay activates with the indication ON (off or flashing) displayed.
SIGNALLING BATTERIES LOW OR DOWN
When the
INSERTING OR REPLACING BATTERIES
ONLY USE GOOD QUALITY ALKALINE BATTERIES
(Duracell or Energizer batteries are recommended
Upon first inserting the batteries, the programmable thermostat performs a lamp test by switching on all display segments, displaying the installed software version for a few seconds. When this phase is over, the programmable thermostat asks to select the language of use. Select the desired language by scrolling through the available languages using the keys. Confirmpressing the OK key. The selectable languages are:
ITALIAN=It (default), ENGLISH=En, FRENCH=Fr, GERMAN=dE, SPANISH=ES
IMPORTANT: in order to be able to work PROPERLY, the programmable thermostat requires you to enter the current year, month, day, hour and minutes, automatic daylight saving time/standard time change and vice versa, see the complete procedure in paragraph 11.4.
The programmable thermostat is immediately operative, displaying: the current day, hour, and minutes, Winter «heating» mode, and standard time/thermal profile for every day of the week (PROGRAMP01).
From normal programmable thermostat operation in stand-by, pressing a key light up the display (unless back-lighting has been disabled) and the selection and navigation of the words appear. Within 6 sec., a variation is made the second time the desired key is pressed.
Temporary override operation (see complete description in par.10.2.1.A)
At the end of the set number of hours, the programmable thermostat will resume normal operation from the program running before the temporary override.
It is however possible to quit the temporary override by pressing the back key.
Program pause for household cleaning (see complete description in par. 10.2.2.)
Available Menu structure:
SET TEMP
PROFILE
PROGRAM (display, change, copy programmed time profiles)
USER PASSWORD
USER PASSWORD (set user password
CONFIGURE (installer or skilled user menu)
From the normal programmable thermostat operation press the Menu key to access the first available menu.
In the event the factory Set temperatures:
In the presence of max and min. temperature locks (see paragraph 11.8) it is not possible to set a Set t higher or lower than the entered locks. The display will signal impossibility to per form the operation by displaying .
Programmable thermostat «PROFILES» menu
Two override operating modes are possible temporary or permanent with a pause in the current program. Both overrides have their own modifiable set temperature and completely independent fromthe current program.
Temporary override operation
Permanent override operation
Disabling permanent override operation
To go back to automatic operation from the program, through the path: Menu button -> SEt PROFILE -> display item OVERRIDE OFF, confirm by pressing OK. The temperature scale will be displayed and the relevant Set points of the current day, according to the program in use before permanent override operation was enabled.
This program is useful in the event one should need to leave the house for several days (temperature control pause); your habitual program in use (winter or summer) will be re-enabled at the end of the period set with the HOLIDAY program, so you may find the desired temperature on your return. All the settings required by the HOLIDAY program must be confirmed by pressing OK, otherwise the programmable thermostat goes back to normal operation after 3 minutes have elapsed and the modifications will not be stored. Through the button pathMenu ->SEt PROFILE ->select the item SEt HOLIDAY then press OK. The HOLIDAY program will adopt the «Winter » or «Summer » season of the program in use.
Holiday start setting «OUT» (leaving the home)
Upon completing the data entry, two different views may be displayed (depending on the data entered):
OUT Date the same as the current one
The programmable thermostat starts the countdown (e.g. in the figure: 388 hours) until exhausting the programmed hours; in WINTER mode the connected user will only be activated if the room temperature should go below the Set antifreeze temperature point (default 6.0 °C). At the end of the countdown, the HOLIDAY program will reactivate your usual program
OUT Date after the current one
The programmable thermostat goes back to the program running before entering the data in the HOLIDAY program, pending its activation. The screen of the HOLIDAY program will appear on the display for 2 seconds every minute as a reminder that it is in stand-by.
When the HOLIDAY program is running:
LIST OF PRE-SET PROGRAMS
The box shows factory-entered programs with relevant time profiles: P01 and P02 WINTER; P03 and P04SUMMER. In the event none of the pre-set programs should meet your needs, they may be modified (see next paragraphs).
PROGRAM SELECTION
MODIFY PROGRAM
There are 4 available programs, all freely programmable for every hour of the day (with half-hour steps) and different for every day of the week, on 3 different temperature levels: t1 comfort (upper digits), t2 activity (intermediate digits), t3 economy (lower digits), plus one level of antifreeze temperature t for the winter mode (digits not visible), or cooling system switched off for the summer mode.
USER MENU
After the time/temperature profile of one day has been completed (either in the SET or INFO condition), it will be possible to:
After completing the modification of the temperature/time profile of one day (see previous paragraph) it is possible to copy it over one or more days. Press OK, and confirmation will be asked whether to copy the modification over other days (LOAD YES/LOAD NO): choose the desired option with the keys
If LOAD NO is confirmed, no copy operation will be performed, the display will go back to the INFO screen showing the day after the modified one.
If LOAD YES is confirmed, you will be asked on what other days to copy the modification: press OK to confirm copying over the indicated day (e.g. TUESDAY) and moving to the next day, whereas if you press, you will skip the next day and exclude it from copying. The sequence will be requested until completing the week, signaled by the wording END.
In this condition, you may:
No code is set in the factory configuration.
The programmable thermostat enters normal operation
From now on, the password will be required when the menu key is pressed Certain quickly activated functions may be used in any case from the normal operation condition (stand by) of the programmable thermostat (see chapter 7
Password modification or cancellation
Press MENU, and enter the previously set password; follow the procedure described above to access the User PASSWORDSEt menu: – set 4 hyphens (- – – -), the password will be canceled, – set another number and it will be modified.
Access to the configuration menu
Through the Menu -> path select the CONFIGURE SEt menu and confirm with OK: access the 1st item LANGUAGE SEt of the menu (see Chapter 8 for the list of available items).
If only an installer password was entered the display requests entering the 4 digits, which may be selected using the
The season may be changed by selecting an already set program for the other season (see par. 10.4.1/10.4.2), or through the Menu, -> CONFIGURE SEt -> path under item SEt SEASON confirm with OK. Select with the keys the WINTER (heating) or SUMMER (cooling) mode and confirm with OK. In this case, the last program used for the season about to be set will be automatically selected. Press the «back» key to exit.
IMPORTANT: in order to be able to WORK PROPERLY, the programmable thermostat requires you to enter or update the current year, month, day, hour and minutes, automatic daylight saving/standard time change and vice versa (default EURO=Italy and central Europe).
Use the
Press the
When TIME SEt is displayed, press «back» to quit.
TYPE TEMPERATURE ADJUSTMENT METHODS
The programmable thermostat is factory set to work in THERMAL DIFFERENTIAL mode ON/OFF with a preset thermal differential value (Hysteresis) of 0,3 °C. Note: adjustable from 0,2 °C to 1,2 °C (from 0,3 °F to 2,1 °F). The hysteresis value must be set according to the system’s thermal inertia; a low value is recommended for systems with radiators made of e.g. cast iron and a high value for systems with fan coils As opposed to the thermal differential, the temperature can be adjusted MODULATING PROPORTIONALLY (PROP) setting cycles from 7 to 20 minutes (default 10 minutes). This system maintains the desired temperature more stable, whilst increasing the user’s comfort sensation and saving on energy consumption. A long cycle is recommended for systems with high thermal inertia (cast iron radiators, floor systems) and a short cycle for systems with low thermal inertia (fan coils).
SELECTION OF THE TEMPERATURE ADJUSTMENT MODE (DIFFERENTIAL ON/OFF OR PROPORTIONAL
Through the path Menu->CONFIGUR SEt->, select item RULE SEt. Press OK to confirm. It will be possible to select temperature adjustment mode between Thermal differential (On: OFF) factory setting or Modulating proportional (PrOP) operation. Use the
Setting hysteresis for thermal differential ON-OFF
Setting period duration for modulating Proportional
CHANGE UNIT OF MEASURE FOR TEMPERATURE READING
The programmable thermostat is pre-set in the factory to display temperatures in degrees Centigrade (Celsius), it is possible to switch to the Fahrenheit scale or vice versa with the following procedure
If for any reason the programmable thermostat must be installed in a position where the measured room temperature might be affected (e.g. perimeter wall which is on average colder in winter and warmer in summer than the rest of the dwelling) the device has 2 separate parameters to adjust the room temperature measured in the Winter and Summer modes
OFFSET for winter mode (
MAX AND MIN SET TEMPERATURE LOCK (Winter and Summer mode)
General rule
In addition to the internal probe of the programmable thermostat, it is possible to connect to terminals 6 and 7 «AUX 1 » (see wiring diagrams in ch. 5.4) a supplementary probe (optional) which may be set to read the temperature in various modes.
Through pathMenu ->CONFIGUR SEt ->PROBE SEt, press OK to enter the menu. Selectable functions are as follows:
PROBE NO | The separate probe is not read, it is disabled (factory setting upon first witch on). |
REMOTE PROBE | It measures the temperature of a room in replacement to the internal probe of the programmable thermostat. |
FLOOR PROBE | It measures the floor temperature and switches off the connected load if it exceeds a certain set threshold. Room temperature control is managed by the internal programmable thermostat probe. |
EXTERNAL PROBE | It measures the temperature outside the home without affecting internal room temperature control. |
Select the desired type of probe with the keys and confirm with OK.
NO CONNECTION TO A SEPARATE PROBE
Should you wish to disable the previously active separate temperature probe and go back to using the standard internal one (default), follow this procedure: through path Menu -> CONFIGURE SEt -> PROBE SEt ->select itemPROBE nO (NO) and press OK to confirm. Press the back key to exit
SETTING SEPARATE REMOTE PROBE
This is a remote probe to detect the temperature in a different room from the one where the programmable thermostat is installed, for instance in the event of unfavorable installation or in premises unsuitable to reading and adjusting the temperature. The remote probe has the same parameters and reading range as the internal probe. Reading range: -5.0°C÷+37,7°C (+23°F÷+99,9°F). It completely replaces the internal programmable thermostat probe and the product will control room the temperature through this remote probe. After connecting the remote temperature probe to the programmable thermostat, it may be activated through the path:Menu key ->CONFIGUR Set ->PROBE SEt ->select itemREMOTE. Press «OK» to confirm. Press the back key to exit.
SETTING FLOOR PROBE (over-temperature protection function)
This is a separate and remote controllable temperature probe, buried in the screed of an underfloor heating system with radiating panels, to monitor the temperature and turn off the system in case the temperature read exceeds a pre-set threshold value After connecting the separate temperature probe to the programmable thermostat, it may be activated through the pathMenu key ->CONFIGUR SEt ->PROBE SEt ->select itemFLOOR
The programmable thermostat displays and controls the room temperature detected by the internal probe:
at the same time, the separate probe also detects the floor temperature, which will be compared with the threshold set by the installer, to prevent this temperature from exceeding the safety threshold. Should this occur the programmable thermostat will switch off the system even if the Set t temperature is not reached; the display signals this condition by displaying the code tP and the set threshold value flashes
SETTING SEPARATE EXTERNAL PROBE
This is an additional probe to read the temperature outside the dwelling (tE). It does not have any home temperature control features, which are controlled by the internal programmable thermostat probe. After connecting the external temperature probe to the programmable thermostat, it may be activated through the path: Menu key ->CONFIGUR Set ->PROBE Set ->select itemEXTERNAL. Press «OK» to confirm. Press the back key to exit
CONNECTION TO EXTERNAL CONTACT FOR REMOTE PROGRAMMABLE THERMOSTAT SWITCHING ON/OFF
A remote device may be connected to the programmable thermostat (e.g. telephone programmer, hourly switch, switch) able to remotely enable/disable the programmable thermostat. Through the pathMenu ->CONFIGUR SEt ->, select itemINPUT SEt. PressOKto confirm.
Various operation modes may be selected depending on the type of contact-free from potential (NO or NC) and type of device connected to the terminals 8 and 9 «AUX 2» (see par. 5.4 electrical connections):
INPUT nO = Input exclusion (factory setting);
ACTIVATION / DISABLING WITH A TELEPHONE PROGRAMMER
Example of remote programmable thermostat switching on/off, connected to a telephone programmer with
«nA» Duty – for normally open contact (NO)
By selecting this function it is possible to connect a NO remote contact which upon closing sets the programmable thermostat in the OFF mode with antifreeze temperature t , unless it has been previously disabled. In this condition, it will not be possible to act on the programmable thermostat keys to change the operation status. Open the contact and the programmable thermostat resumes normal operation from the program active before overriding. FrompathMenu key ->CONFIGUR SEt ->INPUT SEt ->select items DUTY.Press «OK» to confirm. Press the back key to exit
e.g. Switch | Programmable thermostat operation |
in OFF mode with t antifreeze | |
operation from running program |
«nC» DUTY – for normally closed contact (NC)
e.g. Switch | Programmable thermostat operation |
operation from running program | |
in OFF mode with t antifreeze |
If the function is activated, the programmable thermostat activates every day of the year at 12:00, for 2 minutes. It activates the controlled device (pump, valve etc.) to prevent scaling or jamming caused by prolonged inactivity. From path Menu key ->CONFIGUR SEt ->PUMP ON SEt ->press «OK» and with the keys select the desired item: PUMP ON nO (NO) or PUMP ON 2′. Press «OK» to confirm. Press the back key to exit.
8 adjustment levels are available. Level 6 is set in the factory. From path Menu key -> CONFIGURE SEt -> use keys to select item CONTRAST SEt. Press OK to confirm. Select the desired level with the keys. The contrast variation obtained will be visible at every selection. Press OK to confirm. Press the back key to exit.
BACKLIGHTING
It lets you enable or disable timed display backlighting. From path Menu key -> CONFIGURE SEt ->use keys to select itemBACKLIGHTING Set. Press OK to confirm With the keys select the desired item: timed backlighting 6sec or disabled backlighting nO (NO). Press OK o confirm. Press the back key to exit
Some functions of this programmable thermostat may be protected by a user Password (Ut) and/or installer (Inst), so that they may be only modified by authorized persons. No password is active in factory settings.
ENTERING THE NEW PASSWORD
From the pathMenu key ->CONFIGUR Set ->PASSWORD SEt ->press «OK» to access the screen to create a secret User code (PASSWORD SEt Ut), confirm with OK, or select item PASSWORD SEt InSt with the , keys and confirm with OK to create the Installer code Using the keys enter 4 digits (dashes not included) between 0000 and 9999, and individually confirm them with «OK The «User» password lets you access available functions through the Menu key.
If an installer password is also present the CONFIGUR SEt menu may not be accessed. The «Installer» password lets you access all «Configurations» (CONFIGURE SEt) menu functions as well as User settings With a password, certain quickly activated functions may still be used (see Chapter 7).
PASSWORD MODIFICATION OR CANCELLATION
SYSTEM SOFTWARE INFORMATION
From normal programmable thermostat operation, simultaneously pressing for 4 sec. the keys Menu and (RESTART) in the display shows for few seconds the screen INFO SW concerning some information on the installed firmware.
Caleffi 738 Digital room chrono-thermostat Instruction Manual
Caleffi 738 Digital room chrono-thermostat Instruction Manual
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…