NOTE: Read the entire instruction manual before starting the installation.
Improper installation, adjustment, alteration, service, maintenance, or use can cause an explosion, fire, electrical shock, or other conditions which may cause death, personal injury, or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory-authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Have a fire extinguisher available. Read these instructions thoroughly and follow all warnings and cautions included in the literature and attached to the unit. Consult local building codes and the current edition of the National Electrical Code (NEC) NFPA 70. In Canada,
refer to the current editions of the Canadian Electrical Code CSA C22.1.
Before the actual installation of a zoning system can begin, decisions need to be made to determine the number and location of zones and sensors. This affects duct and damper selections.
See the Evolution® System Zoning Design Guide for more information on specifying and designing zoning systems.
This instruction covers the physical installation and start-up of the Evolultion® Damper Control. Use this instruction to guide the actual installation process after all the airside decisions have been made. One Damper Control is capable of handling up to four zones of operation. When greater than four zones are required, a second Damper Control
The module is needed for zones 5 through 8 (8 zones maximum).
The Evolution® Zoning System allows air conditioning and heating equipment to control temperatures and humidity in up to 8 distinct spaces, or zones, within a building. Each zone has independent temperature settings. The comfort temperature settings can change automatically through the use of schedules. This allows the Evolution® System to change temperature settings in zones to reflect occupancy or usage. For example, the end-user can condition bedrooms in a home from 5:00 PM through 7:00 AM or the
kitchen from 3:00 PM through 6:00 PM. The Evolution® System uses motorized air volume control dampers (also called zone dampers) to regulate the flow of conditioned air into zones. In this manner, the system can selectively heat or cool certain portions of a building depending upon space temperature requirements.
Each zone requires a motorized zone damper to control the air supplied to it and a zone sensor to sense temperature in each zone. There are three types of zone sensors available and may be used in combination:
Be sure to select the desired sensor type for each zone. Zone sensors other than the Evolution® Connex™ wall control must be purchased separately. Installation Instructions for these sensors are included with them.
All system wiring is run back to the Evolution® Damper Control. Select a location near the Evolution® furnace or fan coil where the wiring from the Evolution® Connex™ wall control, each Remote Room Sensor or Smart Sensor, each damper actuator, and the equipment itself can come together easily. The Evolution® Damper Control is approved for indoor use only and should never be installed with any of its components exposed to the elements.
The Evolution® Damper Control (and the zone dampers) may be installed in any area where the temperature remains between – 4°F to 158°F (- 20°C to 70°C), and where there is no condensation. The cover must be installed to prevent damage from other sources. Do not locate where it will be accessible to children. It may be mounted in either vertical or horizontal positions. Remember that wiring access is likely the most important consideration.
ELECTRICAL OPERATION HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
To prevent possible damage to the Evolution® Damper Control, do not mount it on the plenum, ductwork, or flush against the surface.
The Evolution® Connex™ wall control is the command center for the Evolution® Zone System. It should be located where it is easily accessible and visible to home or business owners. It is also normally the Zone 1 sensor and as such needs to be located to properly measure the temperature in Zone 1. If these two requirements conflict, a separate Remote Room Sensor can be added for Zone 1.
When a Remote Room Sensor is connected to Zone 1 terminals (ZS1 and ZS1C) of the Evolution® Damper Control, the system automatically switches to using this sensor for Zone 1 and ignores the sensor within the Evolution® Connex™ wall control. This arrangement allows the Evolution® Connex™ wall control to be located at any convenient place within the home or business. In this arrangement, only the Zone 1 Remote Room Sensor must be located in Zone 1.
NOTE: The Evolution® Connex™ wall control also controls humidity functions. If the wall control is not used to control Zone 1 temperature, it must still be located in a suitable area where humidity control will not be affected.
For proper operation, each sensor must accurately measure the temperature within its zone. For accurate temperature measurement, the following guidelines should be followed:
The sensor should be mounted:
The sensor should NOT be mounted:
Ordinary thermostat wire is ideal when wiring the Evolution® Zoning System (shielded cable is not necessary). Use 20 AWG or larger for typical installations. Lengths over 100 ft. should use 18 AWG or larger wire. Remote Room Sensors require only two conductors, but it is recommended that at least four conductors be run. This will allow a Smart Sensor to replace the Remote Room Sensor with no wiring changes at a later date. The Evolution® Connex™ wall control requires four conductors, each damper actuator requires three conductors. Cut off or fold back and tape any unneeded wires. Plan the routing of wiring early to avoid possible problems later. Remember, all wires converge at the Evolution® Damper Control, so its location is important.
NOTE: Wiring of the ABCD bus only requires a four-wire connection; however, it is good practice to run a thermostat cable having more than four wires in the event of a damaged or broken wire during installation.
The following color code is recommended for each ABCD bus connection:
A — Green = Data A
B — Yellow = Data B
C — White = 24 VAC (Com)
D — Red = 24VAC (Hot)
It is not mandatory that the above color code be used, but each bus connection in the system MUST be wired consistently.
Install Evolution® Damper Control
The Evolution® Damper Control is designed so that wires can enter it from behind, above, or below. Plan wire routing before mounting Damper Control.
Install Master Zoning Wall Control
See the Evolution® Connex™ wall control Installation Instructions for details.
NOTE: Improper wiring of the ABCD connector will cause the Evolution® Zoning System to operate improperly. Check to make sure all wiring is correct before proceeding with installation or turning on the power.
Install Remote Room Sensors
See the Evolution® Zoning Smart Sensor Installation Instructions for details.
Install Zone Dampers
Proper selection and sizing of dampers are very important for proper system operation. Be sure to consult the Damper Product Data Sheet and Evolution® Zoning Design Guide for assistance in making these selections. Selection and sizing information is not provided in this installation instruction. Zone dampers are available in round, rectangular, and slip-in designs, and may be installed in any position. Install the damper so that the actuator is visible for inspection and accessible in the event it would need to be serviced.
The black mark on the end of the damper shaft represents the position of the damper blade. To wire the damper, locate the terminals labeled: OPN (open); COM (common); CLS (closed, and wire appropriately (see Fig. 1 for Damper 24 VAC connection).
If the duct system requires multiple dampers for a single zone, up to five dampers (maximum) may be wired in parallel. For all applications, including retrofit, it is recommended to use only current dampers with direct-drive style actuators. DO NOT use an older damper with crank-arm style actuators. If an actuator is removed from a damper for any reason, it must be properly aligned when it is reinstalled. This can be done by rotating the actuator and the blade to their closed positions and then tightening the actuator (set screw) to the shaft. This assures alignment at the closed position. (Pressing the quick blade release button allows the actuator to be manually turned.)
ELECTRICAL OPERATION HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Condensation can damage the actuator. When dampers are located in an unconditioned space, condensation is likely to occur in cooling. To prevent condensation and losses, all dampers and ductwork in unconditioned space must be insulated or otherwise protected.
Whenever condensation might occur, it is recommended that a plastic actuator cover (p/n, DAMPACTXXCOV) be used over the actuator. This cover can help prevent condensation on the actuator by helping to keep out ambient humidity. Insulation may be applied over the cover to minimize heat transfer.
To install, place the cover over the actuator and seal it in place over the surrounding insulation with duct tape on all four sides. Sealing need not be perfect because there will be positive pressure inside the cover. Do not mount the dampers with their actuators hanging directly beneath the ductwork. It is best to mount the actuator facing in either the three or nine o’clock position.
For specific duct types, follow the instructions below:
NOTE: All zone dampers and ductwork must be properly supported according to local codes or SMACNA standards.
Fig. 8 – Insulated Rectangular Fibrous Glass Ductwork
Step 5 – Final Wiring
Bring all damper and sensor wires together at the Evolution® Damper Control. Make all system wiring connections as shown in Fig. 9.
The two ABCD bus connections on the Evolution® Damper Control are in parallel with each other. Use either terminal block to connect the Master Zoning Wall Control, Smart Sensor(s), variable-speed indoor unit, and 2- speed communicating outdoor unit (if applied). If more than four zones are required (up to 8 zones maximum), see Step
6 and Fig. 10 for additional Damper Control Board Setup for Zones 5- 8.
Notes:
_ ABCD CONNECTORS ARE IN PARALLEL WITH EACH OTHER. USE EITHER TERMINAL BLOCK FOR ANY ABCD CONNECTION.
_ INSTALLING THE ZONE-1 REMOTE ROOM SENSOR WILL OVERRIDE THE USER INTERFACE TEMPERATURE SENSOR.
Zoning System Wiring Diagram Zones 1 – 4
For Zones 5-8, a second Damper Control Module must be applied
Notes:
_ FOR ZONES 5 THROUGH 8: A SECOND DAMPER CONTROL MODULE IS REQUIRED. BUS CONNECTION ABCD MUST BE CONNECTED BETWEEN BOTH DAMPER CONTROL MODULES.
_ SET BOTH DIP SWITCH POSITIONS TO ON (right position) AT SECOND MODULE ONLY TO ACTIVATE ZONES 5-8.
Zoning System Wiring Diagram Zones 5 – 8
The Evolution® Damper Control can control a Bryant Heat Recovery Ventilator or Energy Recovery Ventilator (HRV / ERV). Connect the four wires from the ventilator control board (see ventilator installation instructions for details) to the connector labeled YRGB. This label identifies the color of the wire to match the ventilator wire colors (Y=yellow, R=red, G=green, B=blue or black). If you have two Evolution® Damper Controls, connect the ventilator to the control for zones 1 through 4.
These inputs on the Evolution® Damper Control are used only for diagnostic purposes and are NOT required for regular use. Traditionally, the LAT/HPT sensors were required for temperature and equipment monitoring. The Evolution® Zoning System does not require these because the Evolution® Connex™ wall control algorithms will perform temperature and airflow management without the use of these sensors. If desired, one or both sensors may be used to monitor leaving air temperature and/or indoor coil air temperature. Consideration and/or flexibility will now permit using one of these sensors in the return air duct giving the dealer an option to view both entering and leaving air temperature at the Evolution® Connex™ wall control. If applied, connect sensors to the LAT / HPT terminals (See Fig. 9, System Wiring, for connection to the Evolution® Damper Control). LAT is monitored by both AC and HP systems. LAT and HPT are both monitored only in HP systems.
To install – Locate the LAT sensor in the main supply trunk after the heating and cooling coil and before the first branch. The LAT sensor is radiantly shielded to prevent heat from affecting the correct air temperature.
The HPT sensor (in heat pump applications) measures the temperature of the air leaving the indoor coil. The sensor is installed downstream of the indoor coil, but before the electric heaters. It can be installed through the wall of the fan coil or may be located entirely inside the fan coil near the blower inlet. The anchor is firmly in place with cable ties so that it cannot interfere with the blower wheel (See Fig. 9).
Under normal operation, the Yellow and Green LEDs will be on continuously (solid). If the Evolution® Damper Control does not receive communications with the volution® Connex™ Wall Control, the Green LED will not be on. If there are faults present, the Yellow LED indicator will blink a two-digit status code. The first digit will blink at a fast rate, and the second at a slow rate.
Status Code | Description |
16 = | Communication Failure |
24 = | Damper Fuse Failed |
45 = | Board Failure |
46 = | Low Input Voltage |
A 1A automotive-type fuse is used to protect the Evolution® Damper Control from overcurrent on the damper drive outputs. If this fuse fails, the damper wiring should be inspected for shorts. Also, no more than five damper motors should be connected to a single damper output. The fuse should always be replaced with an identical 3A automotive type.
Additional Damper Control Board Setup
If you have more than four zones, a second Evolution® Damper Control must be used and both dip switch settings on the second board supporting zones 5 through 8 must be moved to the right. The ABCD bus connector must be wired between both Evolution® Damper Controls.
Transformer Requirements
The Evolution® Zoning System has a lower power draw than the system transformer from previous controls. It also drives only two-zone damper outputs at a time. As a result, up to eight zones each with up to five dampers, plus a smart sensor, can be handled without increasing the size of the system transformer or adding a second zoning transformer.
Use of the transformer provided in the furnace or fan coil is recommended without change in all zoning applications except those having a System Access Module (SAM). The SAM requires a separate transformer.
For those who still want more transformer capacity, a 60 VA system transformer may be used in place of the supplied 40 VA part.
System Start-up
Follow the system start-up process outlined in the Evolution®
Connex™ wall control Installation Instructions for details.
Infinity® Touch Wall Control does not power up:
Evolution Connex™ Wall Control display says “Indoor Unit Not Found:”
Evolution® Connex™ Wall Control display says “Outdoor Unit Not Found” when applied with a two-speed communicating outdoor unit:
Evolution® Connex™ Wall Control cannot find Zones 5 – 8:
Evolution® Connex™ wall control can find zones 5 – 8, but not 1 – 4:
Some zones do not provide enough comfort (a noticeable difference exists between the actual room temperature and operating setpoint, or equipment does not turn on):
Some zones provide too much airflow and are noisy:
Zone dampers do not move:
Training
My Learning Center is your central location for professional residential HVAC training resources that help strengthen careers and businesses. We believe in providing high-quality learning experiences both online and in the classroom.
Access My Learning Center with your HVAC partner’s credentials at www.mlctraining.com. Please contact us a mylearning@carrier.com with questions.
Download Manual
Bryant SYSTXBB4ZC01 Evolution Damper Control Installation Guide
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…