Questions?
Visit: www.alarm.com/supportcenter or contact your service provider.
Buttons
Modes
Display
COOLING: Illuminated in COOL or AUTO mode when the thermostat is calling for cool.Illuminated when the thermostat is using one or more Alarm.com Temperature Sensors.
If replacing an old thermostat, the new thermostat can be mounted in its place. If a new location is desired it will be necessary to move the wiring. New installation and relocation should follow the accompanying guidelines to ensure the most accurate temperature reading and ease of use.
Test the system
Verify that the heating and/or cooling system is operating properly before you try to install the new thermostat.
CAUTION: Do not test the system by shorting electric terminals at the furnace or air conditioner. This may damage the thermostat.
Turn the power off
Turn all heating and cooling systems off. This can be done at the circuit breaker.
CAUTION: Do not remove the existing thermostat until power has been turned off at the circuit breaker. Once the power to the heating and cooling systems is off, perform the following steps:
Remove the thermostat cover
Remove the cover from the existing thermostat. Do not disconnect the wires yet.
Make sure the wires are identified correctly. If you have an unidentified wire, it may be necessary to identify the wire where it connects to the heating or air conditioning equipment.
CAUTION: Wiring can vary for each manufacturer. Identify all wiring before removing it from the existing thermostat. Take a picture of the wires before you detach them from the existing thermostat for future reference. Disconnect all of the wires and remove the existing thermostat. Remember to secure the wires so they don’t fall into the wall.
Prepare the wires
Follow these guidelines for safe and secure wire connections:
CAUTION: Verify that the system is 24 VAC. If the old system is labeled as 120 or 240 volts or has wire nuts, the system is high voltage. Do not install the thermostat to a high-voltage system. Contact a local HVAC professional for help.
Install the back plate
Use the bubble level provided on the back plate as a guide. Mark where the screws will go with a pencil through the screw holes on the back plate. Ensure the top of the back plate is facing up. If necessary, use the trim plate to cover up any marks or holes left by the old thermostat. Attach the trim plate before securing the back plate to the wall. If additional support is necessary, drill holes with a 1/4” drill bit and tap in the drywall anchors.
Wire your new thermostat
Connect the wires to the new thermostat. If you have extra wires, do not connect the to the new thermostat. Please contact your local HVAC professional for additional assistance.
NOTE: If you have a 2-wire hydronic heating system, you may need to add the power resistor to the system. Connect this resistor to your heating equipment (not the thermostat) between the C and W terminals. Additional information about the power resistor can be found in the Troubleshooting section.
Conventional system | |
Terminal | Description |
RC | Cooling power |
RH | Heating power |
Z1 | Configurable W3, H (humidifier control), DH (dehumidifier control), EX (ventilation) |
Z2 | Configurable W3, H (humidifier control), DH (dehumidifier control), EX (ventilation) |
W | Heat stage 1 |
W2 | Heat stage 2 |
C | Common wire from secondary side of heating transformer (if 2 transformers) |
Y | Cool stage 1 |
Y2 | Cool stage 2 |
G | Fan |
O | Energized in COOL mode |
B | Energized in HEAT mode |
Heat pump | |
Terminal | Description |
RC | Cooling power |
RH | Heating power |
Z1 | Configurable W3, H (humidifier control), DH (dehumidifier control), EX (ventilation) |
Z2 | Configurable W3, H (humidifier control), DH (dehumidifier control), EX (ventilation) |
W | Aux stage 1 |
W2 | Aux stage 2 |
C | Common wire from secondary side of heating transformer (if 2 transformers) |
Y | Pump stage 1 |
Y2 | Pump stage 2 |
G | Fan |
O | Energized in COOL mode |
B | Energized in HEAT mode |
Install the batteries
The thermostat can be powered by a battery or 24 VAC. If a wall transformer is used to power the thermostat, connect between C and RH.
Ensure the batteries are installed following the specified polarity markings on the thermostat.
CAUTION: BATTERY WARNING
Attach the body and back plate
Verify that any excess wire is tucked back into the wall to allow room for the thermostat to sit flush against the back plate. Return the thermostat to the wall plate by pressing the thermostat body firmly into the back plate mounted to the wall. Ensure that the pins on the body are correctly aligned with the back plate. Failure to do so could cause damage to the thermostat.
Turn the power on
Restore power to all the heating and cooling systems. This can be done at the circuit breaker.
The thermostat will automatically detect connected wires. Follow the on-screen instructions t complete the thermostat configuration.
NOTE: If the thermostat screen does not show all the connected wires, remove the thermostat from the wall and verify that all wires are properly connected. If issues persist, there may be a problem with automatically detecting your wiring. Please see the Bypassing Wire Detection information in the Troubleshooting section. Depending on the system type and configuration, the thermostat may request the following information during setup:
Heat type
Tells the thermostat whether it should turn on the fan during a heating cycle.
Backup heat type
Tells the thermostat what type of auxiliary/backup heating the heat pump uses.
Z1/Z2 terminal function
These are the “dynamic” terminals. If an auxiliary wire has been connected, please specify the function it will perform.
While the default settings online will be sufficient in most cases, you also have the option to change advanced configuration settings, such as Swing, Differential, Fan Circulation Period, Fan Circulation Duty Cycle, Maximum Setpoints, Minimum Setpoints, and Thermostat Lock.
CAUTION: Be careful when changing advanced configuration settings. These configuration settings should only be changed by those familiar with heating and cooling systems’ parameters. Contact a local HVAC professional for help.
Change the default settings
Use the following instructions if you wish to change the default settings on your thermostat.
Changing the temperature display from Fahrenheit to Celsius
Enabling motion-detected wake
This setting will enable the thermostat screen to wake when motion is detected nearby.
Note: This feature is only available if the thermostat is AC-powered.
Disabling AUTO mode
The thermostat can adjust the humidity level in your home by directly controlling an external humidifier, dehumidifier, or by using the cooling system to dehumidify. For an external humidifier or dehumidifier, the thermostat must be configured to use the Z1 or Z2 terminal. Z1 and Z2 configuration can be found in the Settings section of the Installer menu. If a cooling system is present without an external dehumidifier, the thermostat will extend your cooling cycles in an attempt to reach your dehumidification setpoint.
Changing the humidity mode
Select the mode for which you would like to control humidity.
Changing the dehumidifier setpoint
Ensure that the humidity mode selected is either DEHUMID or AUTO.
Changing the humidifier setpoint
Ensure that the humidity mode selected is either HUMID or AUTO.
NOTE: The thermostat enforces a 20% “deadband” or minimum difference between the minimum and maximum humidity setpoints. Moving one of the setpoints within 20% of the other will force the other setpoint to move automatically to maintain the 20% deadband.
The thermostat can control a ventilation system (HRV, VRV, or air baffle) using the Z1 or Z2 terminal. By default, the thermostat will operate the ventilation system for 15 minutes every hour. To change the ventilation settings, refer to the advanced configuration settings through the Customer Website or Mobile App. If the settings are not available, please contact your service provider.
If the wiring changes, or if a mistake was made during the initial configuration, the thermostat’s HVAC settings can be reconfigured. This process will not remove the thermostat from the Z-Wave network. However, all HVAC settings and configurations will be set back to their default values, and the thermostat will present the user with the initial setup screens again.
Reconfiguring the thermostat
CAUTION: Do not test the AC during cold weather or heat during hot weather. Wait for mild weather to fully test the system.
Check to heat
Check to cool
Waking the device
Changing the mode and setpoint
Changing the fan mode
The fan modes are AUTO, ON, and CIRCULATE. The thermostat will only show the fan modes if it has been configured to control a fan.
AUTO mode will automatically turn the fan on when your system is either heating or cooling. CIRCULATE will turn the fan on for 15 minutes every hour by default. The duration for CIRCULATE can be configured from the online account.
Changing the batteries
If the thermostat batteries are low, replace the batteries with two new AAA batteries.
The heating or cooling doesn’t turn on when the setpoint is above or below the room temperature To prevent damaging the compressor, the thermostat inserts a delay when cycling the compressor. If you think the system should be on and it’s not, change the setpoint to 2 degrees beyond the current setpoint and wait 5 minutes to see if the system turns on. If not, contact a local HVAC professional. A heat pump is “cooling when it should be heating” or “heating when it should be cooling” Some heat pumps use the O terminal, while others use the B terminal. Try switching the O or B wire to the opposite terminal. Contact a local HVAC professional for further assistance. The thermostat buttons flash amber and screen does not illuminate The batteries in your thermostat are extremely low. Install fresh batteries immediately.
If the automatic wire detection feature is not correctly identifying your wires, please proceed to bypass the automatic wire detection. On the wiring detection screen, select NO. The thermostat will display Check Wiring and Reinstall. Select BYPASS and continue through the remaining prompts to manually configure the thermostat. You will need to know the system type, heat type, and the number of stages to complete the installation. Locating the INSTALLER (setup) menu The initial setup menu can be accessed at any time:
Remove the thermostat from the Z-Wave network
If for some reason the thermostat must be removed from the network, follow the steps below:
The thermostat displays “Safety Delay” on the screen The thermostat will protect your compressor from short cycling and display “Safety Delay” with a timer on the screen. When the timer expires, the thermostat will automatically resume heating or cooling.
Can I keep the thermostat screen lit up at all times?
No. The thermostat display cannot be lit up indefinitely. See the section on “Enabling motion-detected wake” to have the screen light up
when a person walks up to the thermostat.
The thermostat displays “Power Resistor Required” on the screen
You have a system that requires the included power resistor to be installed on the zone valves on your HVAC equipment. See the diagram below for where to install the power resistor between terminals 1 and 2 on Taco valves.
Is my thermostat a repeater in the Z-Wave network?
The thermostat is only a repeater when it has been added to the network while it has a common wire connected and powered. If the thermostat receives a common wire after being added to the network, the thermostat will need to be removed and re-added to enable the repeater functionality.
Where do I view and change advanced features and settings for my thermostat?
Advanced thermostat configurations and features such as outdoor balance point, staging delays, venting (HRV, VRV, and air baffles), and Geo-Services require an online account and security panel or gateway. Use the Customer Website or Mobile App to configure these options.
My thermostat is displaying a fault code
Please contact your service provider. You can find their contact information on the Customer Website or Mobile App.
Resetting the thermostat to factory defaults
The thermostat can be reset back to its factory settings. This will reset all of the HVAC settings, rules, and schedules on the thermostat, and it will also remove the thermostat from the Z-Wave network.
NOTE: The panel or gateway will be unaware that this procedure was performed, so it is recommended that you follow the process in the “Remove the thermostat from the Z-Wave network” section before performing this reset.
The thermostat displays “Isolation Relay Required” on the screen
Please contact your service provider. You can find their contact information on the Customer Website or Mobile App.
FCC
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
IC
Under Industry Canada regulations, this radio transmitter may only operate using an antenna of a type and maximum (or lesser) gain approved for the transmitter by Industry Canada. To reduce potential radio interference to other users, the antenna type and its gain should
be so chosen that the equivalent isotropically radiated power (e.i.r.p. is not more than that necessary for successful communication.
Z-Wave
This product can be operated in any Z-Wave network with other Z-Wave-certified devices from other manufacturers. All non-battery-operated nodes within the network will act as repeaters regardless of vendor to increase the reliability of the network.
NOTE: The grantee is not responsible for any changes or modifications not expressly approved by the party responsible for compliance. Such modifications could void the user’s authority to operate the equipment.
Questions?
Visit: www.alarm.com/supportcente or contact your service provider.8281 Greensboro Drive Suite 100 Tysons, VA 22102 © 2019 Alarm.com. All rights reserved. Designed in the USA by Building 36, an Alarm.com company. Made in China.
Download Manual: Alarm.com ADC-T3000 Smart Thermostat User Manual
https://device.report/energystar/2333422
Alarm.com ADC-T3000 Smart Thermostat – Energy Star Certification
OTHER MANUALS:
Alarm.com Adc-t3000 Smart Thermostat Installational Manual
Alarm.com ADC-T3000 Smart Thermostat Troubleshooting Guide
Alarm.com ADC-T3000 Smart Thermostat Operational Manual
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…