Common problems with heating:
Common problems with cooling:
Common problem with fan:
Is it a Heat Pump or Conventional (Normal) system?
A heat pump is a standalone unit typically located outside of a home or on the rooftop of a business. Locations may vary. What makes a heat pump unique is that it can provide both heat and cool based on the position of its reversing valve. What makes it difficult to identify is that it looks exactly like an AC unit. Below are some ways to determine if the outdoor unit is a Heat Pump or an AC Unit.
Expected wires for a Conventional (Normal) system
Conventional (normal) systems include: furnace, boiler, steam or hot water radiator, radiant in floor heat.
Expected wires for a heat pump
Pre-troubleshooting steps
Thermostat does not appear on the Customer Website or app If the Alarm.com Smart Thermostat does not appear on the Customer Website or app after enrolling it, see Enrolled ZWave device is not on the Customer Website or app.
Listening for clicks
When the Alarm.com Smart Thermostat turns a component on or off, a relay closes or opens, and an audible click can be heard. The click can be faint or hard to hear in loud environments. To properly listen for clicks, change the thermostat to off mode. Change the thermostat to heat or cool mode and increase (for heat) or decrease (for cool) the target temperature until it is well above (for heat) or below (for cool) the ambient temperature of the room. Verify that you are far enough past that the swing setting is not a factor (i.e., swing is set to .5-degrees by default, so go at least three degrees above the ambient temperature). Shortly after, you should hear the clicks. A thermostat clicking means that it is opening or closing relays. If you turn the thermostat to heat or cool modes and set the temperature high or low enough (respectively), and it clicks, it means it is trying to activate the heating or cooling system.
Compressor delays
Compressor delays will affect when components are energized, so the clicks won’t happen until the delay has expired. Any call for cool, and calls for heat with a heat pump system, will be subject to a compressor delay (default five minutes).
Important: After turning the system to off mode, don’t change it to cool or heat mode until the full five-minute delay has expired.
ADC-T3000
If there is an R wire, connect it to either RC or RH and make the appropriate selection when asked which terminal is in use. This will create a digital jumper to the other R terminal that is not selected.
Example: Selecting RC only creates a digital jumper to RH. If there are both RC and RH wires, a jumper is not needed. Select that both RC and RH are present during configuration.
ADC-T2000
The thermostat jumper is located on the bottom left side of the terminal board. This jumper bridges a connection between RH and RC. RC is used to power the right side terminals (C, Y, Y2, G, O/B) and RH powers the left terminals (Z, W2, W). Most systems today only have a single R (power) wire, so we plug the R wire into either RH or RC and bridge the connection between them, so that all terminals will receive power from this single wire. Without the jumper, only the RH or RC side will receive power. Some older systems have two different R wires – one for RC, and on for RH. In this case, we need to remove the jumper so that the left and right terminals are independently powered.
Caution: Failing to remove the jumper will short out the system after some period of time.
R | Either RC or RH | No |
RC | Either RC or RH | No |
RH | Either RC or RH | No |
RC and RH | RC > RC, RH > RH | Yes |
Heating or cooling does not turn on when the set point is above or below the room temperature
To prevent damaging the compressor, the thermostat inserts a delay when cycling the compressor. If the system should be on and it’s not, then change the set point to be 2 degrees beyond the current set point and wait 5 minutes to see if the system turns on. If not, contact a local HVAC professional.
Heat pump is “cooling when it should be heating” or “heating when it should be cooling”
Some heat pumps use the O terminal, while others use the B terminal. If there is a wire in the O terminal of the ADCT3000, move it to the B terminal. If the B terminal in the ADC-T3000 has been wired, move it to the O terminal. Contact a local HVAC professional for further help with this issue.
Thermostat buttons flash amber and screen does not illuminate
The batteries in the thermostat are extremely low. Install fresh batteries immediately.
Automatic wiring detection feature is not correctly identifying wires
If the automatic wire detection feature is not correctly identifying the wires, please proceed to bypass the automatic wire detection.
Note: You will need to know the system type, heat type, and number of stages to complete the installation.
Thermostat displays “Safety Delay” on the screen
The thermostat will protect your compressor from short cycling and display “Safety Delay” with a timer on the screen. When the timer expires, the thermostat will automatically resume heating or cooling
Thermostat screen does not continuously light up
The thermostat display cannot be lit up indefinitely. See Enabling motion-detected wake to have the screen light up when a person walks up to the thermostat.
Thermostat displays “Power Resistor Required” on the screen
The customer’s system requires the included power resistor to be installed on the zone valves on their HVAC equipment. See the diagram below for where to install the power resistor between terminals 1 and 2 on Taco valves.
Thermostat displays “Isolation relay required” on the screen
If heat is not working
Is it cooling or just running the fan without heating or cooling?
Heat pumps | 1. Verify the configuration of the reversing valve (O/B terminal), as it could be backward (heating when calling for cool, cooling when calling for heat). 2. Verify the Y wire is not loose/ wrong terminal. | 1. Verify that the Y terminal is activated/wired properly with a digital multi-meter, listening to clicks, or manual test. 2. Check for no power to the terminal because of a missing jumper on the ADC-T2000. |
Normal systems | 1. Verify the HVAC system configuration, as it could be improperly set up as a Heat Pump, which would call the Y terminal, thus cooling instead of heating. 2. Verify the W wire is not loose/ wrong terminal. |
1. Verify that the W terminal is activated/wired properly with a digital multi-meter, listening to clicks. 2. Check for no power to the terminal because of a missing jumper on the ADC-T2000. |
If cool is not working:
Is it heating or just running the fan without heating or cooling?
Heat pumps | 1. Verify the configuration of the reversing valve (O/B terminal), as it could be backward (heating when calling for cool, cooling when calling for heat). 2. Verify the Y wire is not loose/ wrong terminal. | 1. Verify that the Y terminal is activated/wired properly with a digital multi-meter, listening to clicks, or manual test. 2. Check for no power to the terminal because of a missing jumper on the ADC-T2000. |
Normal systems | 1. Verify that the Y terminal is activated/wired properly with a digital multi- meter, listening to clicks. 2. Check for no power to the terminal because of a missing jumper on the ADC-T2000. |
Basic wire checking
Verify wiring with a multi-meter on an ADC-T2000
When checking the C, Y, Y2, G, and O/B wires:
When checking the Z, W2, and W wires:
Basic troubleshooting
The fan is turning on too early
This is likely due to an improper thermostat configuration. Some heating systems will turn on the fan without the help of the thermostat, and build in a delay to allow the furnace to heat up.
Fan turns on when the heat turns on but is not supposed to do so
This is also due to improper configuration. Switch the heat type configuration from fossil to electric.
The fan is not turning on with my heat when expected
ALARM.COM
DOWNLOAD MANUAL
Alarm.com ADC-T3000 Smart Thermostat Troubleshooting Guide
OTHER MANUALS:
Alarm.com adc-t3000 Smart Thermostat Installational Manual
Alarm.com ADC-T3000 Smart Thermostat User Manual
Alarm.com ADC-T3000 Smart Thermostat Operational Manual
Johnson Controls T7000e LCD Digital Thermostat Johnson Controls T7000e LCD Digital Thermostat Installation Guide
Honeywell T8635L Microelectronic Communicating Programmable Thermostat Honeywell T8635L Microelectronic Communicating Programmable Thermostat USER’s GUIDE
Hetta HS01RF WIRELESS THERMOSTAT Kit PAIRING INSTRUCTIONS Insert batteries into the Thermostat. Ensure that the…
HEAT-MAT NGT-567-0010 Underfloor Heating Thermostat Menu Introduction The NGT thermostat can switch your underfloor heating…
Honeywell RLV450 PROGRAMMABLE THERMOSTAT READ BEFORE INSTALLING DESCRIPTION * LP appears only for the first…
Honeywell RLV431 Programmable Thermostat Description The RLV431 thermostat can be used to control an electric…