SCHNEIDER ELECTRIC SE8650 Thermostat
Safety Information
IMPORTANT INFORMATION
Read these instructions carefully and inspect the equipment to become familiar with the device before trying to install, operate, service or maintain it. The following special messages may appear throughout this bulletin or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.The addition of this symbol to a “Danger” or “Warning” safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed. This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
DANGER
DANGER indicates a hazardous situation that, if not avoided, will result in death or serious injury. WARNING
WARNING indicates a hazardous situation that, if not avoided, could result in death or serious injury. CAUTION
CAUTION indicates a hazardous situation that, if not avoided, could result in minor or moderate injury.
NOTICE
NOTICE is used to address practices not related to physical injury. The safety alert symbol shall not be used with this signal word.
PLEASE NOTE
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. A qualified person is one who has skills and knowledge related to the construction, installation, and operation of electrical equipment and has received safety training to recognize and avoid the hazards involved.
Before You Begin
LOSS OF CONTROL
WARNING
LOSS OF CONTROL
- The designer of any control scheme must consider the potential failure modes of control paths and, for certain critical control functions, provide a means to achieve a safe state during and after a path failure. Examples of critical control functions are emergency stops and travel stop.
- Separate or redundant control paths must be provided for critical control functions.
- System control paths may include communication links. Consideration must be given to the implications of anticipated transmission delays or failures of the link.1
- Each implementation of equipment utilizing communication links must be individually and thoroughly tested for proper operation before being placed into service. Failure to follow these instructions can result in death, serious injury, or equipment damage.
ELECTROSTATIC DISCHARGE
NOTICE
STATIC SENSITIVE COMPONENTS
Circuit boards and option cards can be damaged by static electricity. Observe the electrostatic precautions below when handling controller circuit boards or testing components.
Failure to follow these instructions can result in equipment damage. Observe the following precautions for handling static-sensitive components:
- Keep static-producing materials such as plastic, upholstery, and carpeting out of the immediate work area.
- Store static-sensitive components in protective packaging when they are not installed in the drive.
- When handling a static-sensitive component, wear a conductive wrist strap connected to the component or drive through a minimum of 1 megohm resistance.
- Avoid touching exposed conductors and components lead with skin or clothing.
SECTION 1
Introduction
This guide shows the user interface instructions for the SpaceLogic SE8350 Series Room Controller (RC) firmware revision 2.5.1 for users and integrators.
User and Integrator Screens
The SpaceLogic SE8350 Room Controller has dynamic screens that show adjustable parameters and read-only status information. Some screens and parameters only show when a corresponding parameter is selected. Some screens only show on models with onboard ZigBee, optional ZigBee add-on module (VCM8000), optional Wi-Fi module (VCM8002) or paired ZigBee wireless sensor end devices (SED). The LUA selection on the Setup screen only shows if an LUA script is uploaded to the Room Controller. See below legend screen details.
NOTE: When any change is made to a parameter, the value is automatically saved in memory when the next parameter is selected or another screen is opened. This event is true only if a parameter was changed locally on the RC. Making changes through BACnet will not have the same outcome. If changes need to be done remotely through BACnet, use priority 1, 2 or 3, or write to relinquish default (priority 17).
Disclaimer
Standby screen: The Room Controller incorporates TFT-type LCD technology, and therefore, necessary precautions are required to prevent the phenomenon of image retention (residual image) from occurring. Image retention may occur when a static image is displayed on the screen for a prolonged period of time. This can cause a faint outline of the image to remain visible on the screen when the screen is changed via the user menu, or a different image is uploaded and selected to be displayed. To minimize and prevent image retention, it is recommended to select the Screen Save setting on the Standby screen selection from the setup menu Display 1/2. This setting switches the display during periods of inactivity from the Home Screen.It is recommended to use a black or medium gray image, or one with light color contrasts as
the screen saver to prevent this phenomenon from occurring. If the display still exhibits this phenomenon, loading an all-black or all-medium gray image as the screen saver and displaying it for upwards of 5 hours continuously minimizes this effect.
NOTE: Avoid placing the Room Controller in poorly ventilated areas, or in areas that may create excess heat around the display.
HMI Display
The User Human Machine Interface (HMI) is configurable and allows display functions such as Date, Time, Humidity, CO2 levels, Outdoor Temperature, and Setpoint to be enabled or disabled by setting various parameters.
Enter Setup Screen
SETUP 1/2
SETUP 2/2
SECTION 2
User HMI for Hospitality
- Setpoint adjustment
- System mode setting
- Fan mode setting
- Local unit scale adjustment
- Local user language
- User help menu
- Setpoint adjustment
- System mode setting
- Fan mode setting
- User help menu
- Setpoint adjustment
- Local unit scale adjustment
- Local user language
- User help menu
- Setpoint adjustment
- user help menu
NOTE: Parameters are model dependent and may not appear on certain models.
- Fully locked interface with no user settings
- Setpoint adjustment
- System mode setting
- User help menu
- Setpoint adjustment
- System mode setting
- Fan mode setting
- Local unit scale adjustment
- User help menu
User HMI for Commercial
- Setpoint adjustment
- system mode setting
- a mode setting
- unoccupied mode overdrive
- ser help menu
- Setpoint adjustment
- unoccupied mode override
- Local user language
- User help menu
- Setpoint adjustment
- Unoccupied mode override
- User help menu
- Unoccupied mode override
- Setpoint adjustment
- system mode setting
- unoccupied mode override
- User help menu
- Offset setpoints adjustment
- System mode setting
- Local user language
- Fan mode setting
- User help menu
NOTE: The day/night setback button appears only in unoccupied mode in the Commercial HMI 7 to 11. If UI17 input is configured as “override”, the day/night setback button does not show.
NOTE: Parameters are model dependent and may not appear on certain models
User HMI Show/Hide Options
User HMI displays can be customized further by hiding the system status, fan status or help button. Each show/hide option is applicable to all User HMI configurations where the option is shown. To hide the option, select disabled for each display setup screen parameter. Refer to Display Screens in Section 3.
System Mode
Mode | Significance and Adjustments |
System mode Off | Off
Heating, Cooling and Dehumidification demands are ignored. |
System mode Auto | Auto
Room Controller automatically toggles between Heating and Cooling modes to satisfy both Heating and Cooling demands. Dehumidification is allowed. |
System mode Cool | Cool
Room Controller only satisfies Cooling demands, Heating demands are ignored. Dehumidification is allowed. |
System mode Heat | Heat
Room Controller only satisfies Heating demands, Cooling demands are ignored. Dehumidification is allowed. |
Fan Mode Settings
The Fan mode settings displayed on the home screen must be configured in the Fan menu tab of the Configuration menu. The possible options are Low, Med, High, Auto, and On.
Heating Only Configuration
Setpoint Adjustment for Cooling Mode
In Cooling mode, the setpoint displayed in the bar is the currently occupied cooling setpoint. During occupied setpoint adjustment, the large digits are temporarily used to show the occupied cooling setpoint while it is adjusted. Normal temperature display resumes after the setpoint is adjusted and the actually occupied cooling setpoint shows in the setpoint bar.
Setpoint Adjustment for Automatic Mode
In automatic mode, the setpoint showing at the top of the set point bar located directly under the red line represents the actually occupied cooling setpoint. During occupied setpoints adjustment, large digits are temporarily used to display the occupied Cooling Setpoint or occupied Heating Setpoint. The actual setpoint is dependent on the last effective demand (heating or cooling). The setpoint on top of the blue line represents the actually occupied heating setpoint. The differential between the occupied heating and cooling setpoint is defined by the minimum deadband configuration parameter. Normal temperature display resumes after setpoints are adjusted and the actually occupied heating and cooling setpoints show in the setpoint bar.
Other Functions
Local humidity shows when the RH display is enabled on the setup display screen, from either the internal onboard sensor or a wireless sensor end device selected by the RH sensor parameter on the setup configuration screen. CO2 shows when CO2 display is enabled on the setup display screen, from either the optional CO2 detection sensor module or a wireless sensor end device selected by the CO2 source parameter on the setup configuration screen. Outdoor temperature shows when receiving a valid networked outdoor temperature value or a temperature sensor connected to UI23.
Customizable Color Options
SECTION 3
Network Screens
Users can select wired BACnet / Modbus / ZigBee wireless protocol (when the ZigBee feature is available).
NOTICE
UPGRADE OF ZIGBEE 24 TO 30
The upgrade from ZigBee 24 to 30 will not support the Green Power Sensor (SED-CO2-G-5045 or SED-TRH-G-5045). It will therefore need to be recommissioned. There is also a new “Security Levels” parameter for the Zigbee network (see page 21):
- Low (default value) is fully backward compatible with ZigBee Home Automation 1.2 devices, and therefore compatible with all of our sensors.
- Normal (needs to be selected by the user) is only compatible with Green Power and ZigBee 30 (Leedarson sensors).
- If the Normal Security Level is selected with old NYCE or Centralite sensors, they will be removed from the network.
- Failure to follow these instructions can result in equipment being disconnected from the network.
PARAMETER DETAILS
Configuration Parameters Default Value | Significance and Adjustments |
Onboard prot. Read Only | Onboard Protocol
Onboard ZigBee detection
Display Readings: None, ZigBee |
Optional prot. Read Only | Optional Protocol
Requires ZigBee add-on module (VCM8000) or Wi-Fi module (VCM8002).
None: No module detected ZigBee: ZigBee module detected IP: Wi-Fi module detected BAC. IP: Wi-Fi module detected and BACnet/IP enabled
Display Readings: None, ZigBee, IP or BAC. IP |
Wired protocol
Default value: None |
Wired Protocol
None: No wired protocol configured BAC MSTP: BACnet MS/TP network protocol Modbus: Modbus network protocol
Choices: None, BAC MSTP or Modbus |
ZIGBEE NETWORK 1/2
The ZigBee Network screen shows only in models with onboard ZigBee or optional ZigBee add-on modules. When creating a ZigBee network, there must be one and only one device with its Node Type set to Coordinator. For a ZigBee network with a single Room Controller (RC), the RC is set as a Coordinator to pair with the Sensor End Devices (SED). Setting the RC back to Router will remove the paired SEDs.For a ZigBee network with a Multi-Purpose Manager (MPM) paired to multiple RCs, the MPM is set as Coordinator and the RCs are set as Router. The Coordinator MPM controls the pairing of the Router RCs to the SEDs
Note: Before pairing any ZigBee devices, the network must first be created by the Coordinator.
PARAMETER DETAILS
Configuration Parameters Default Value | Significance and Adjustments |
Node type
Default: Router |
Node Type
Sets device to act as Router or Coordinator in a network. Coord.: Creates the network and manages the binding of wireless devices. Router: Joins a network created by a coordinator (Coordinator permit join must be set to ‘ON’). Choices: Coord. or Router |
PAN ID
Default value: 0 |
ZigBee Pan ID
Personal Area Network Identification that links specific Room Controllers to spe- cific ZigBee coordinators. For every Room Controller reporting to a coordinator, set the SAME PAN ID value both on the coordinator and the Room Controller. Note: The default value of 0 is NOT a valid PAN ID and causes ZigBee to be disabled. Range: 1 to 65535 |
Channel
Default value: 10 |
ZigBee Channel
The channel (wireless frequency) on which the ZigBee network transmits and receives data. The channel of the Coordinator must match that of the routers to exchange data. The default value of 10 is NOT a valid channel and causes ZigBee to be disabled. The valid range of available channels is from 11 to 25. Using channels 15, 20, and 25 is recommended. Channel 25 is considered as be- ing the best one because it is furthest from the Wi-Fi channels. Range: 10 to 25 |
Configuration Parameters Default Value | Significance and Adjustments |
Security
Default value: Low |
Security Levels
Note: Changing between ZigBee Security levels does not require re-creating the ZigBee network, or re-commissioning sensors. Low: Disables new security features in ZigBee 3.0 to be fully backwards compat- ible with ZigBee Home Automation 1.2 devices, and therefore compatible with all of our sensors.
Normal: Enables the typical new features of ZigBee 3.0. This means that legacy ZigBee Home Automation 1.x devices cannot join a Normal security network. Compatible with the following sensors: • SED-WDS-P-5045 • SED-WDC-G-5045 • SED-CMS-P-5045 • SED-WMS-P-5045 • SED-MTH-G-5045 • SED-TRH-G-5045 • SED-C02-G-5045 Important! Selecting the Normal Security option will result in the removal of legacy sensors from the network. Choices: Low or Normal |
Network Status Read Only | ZigBee Network Status
Shows the current status of the ZigBee network. No NWK: ZigBee configured but no network joined Joined: ZigBee network joined Online: Communicating (Exchanging data) Display Readings: No NWK, Joined, Online |
Permit join
Default value: Off |
Permit Join
Changing this value to “Off” on the Coordinator prevents any new ZigBee devices from joining the network. Permit join can be On/Off when the Room Controller is a Coordinator, however the parameter is read only when the Room Controller is a router. If not set to off manu- ally the Permit join will stay On for 3 hours. Choices: On or Off |
ZIGBEE NETWORK 2/2
PARAMETER DETAILS
Configuration Parameters Default Value | Significance and Adjustments |
COM address
Default value: 254 |
COM Address
Room Controller networking address. For wireless models, the use of the COM ad- dress is not mandatory. The COM address is an optional way to identify a device on the network and is recommended if used with an MPM. It is Mandatory for BACnet. Range: 0 to 254 |
Short address Default value: 0 Read Only | ZigBee Short Address
The unique ZigBee short address is generated once a wireless device joins a ZigBee network. |
IEEE address Read Only | IEEE Address
The extended IEEE address (MAC address) is a unique worldwide identifier of the onboard ZigBee or optional ZigBee add-on module. |
ZigBee revision Read Only | Communication Module Revision Number
Shows the ZigBee firmware revision number. |
BACNET NETWORK SETTINGS
The BACnet network screen shows when BACnet MS/TP is selected in the wired protocol parameter
Configuration Parameters Default Value | Significance and Adjustments |
COM address
Default value: 254 |
Communication Address
Room Controller networking address.
Default value of 254 disables BACnet communication for the Room Controller.
Range: 0 to 254 |
Network units
Default value: SI |
Measurement Units
Network units transmitted over the BACnet network.
NOTE: Use the Temperature scale parameter to change the display units locally on the Room Controller. Imperial: Network units shown as Imperial units. SI: Network units shown as International Metric units.
Choices: Imperial or SI |
Network lang.
Default value: English |
Network Language
Network language/object names transmitted over network.
Choices: English, French or Spanish |
Baud rate
Default value: Auto |
BACnet Baud Rate
Leave the value at Auto unless instructed otherwise as this automatically detects BACnet baud rate. Choices: Auto, 115200, 76800, 57600, 38400, 19200 and 9600 |
BACnet status Read Only | BACnet Status
Read Only value shows if a BACnet Network is detected or not.
Display Readings: Online or Offline |
BACnet PRate
Default value: 4 |
BACnet Poll Rate
Rate at which a BACnet stack is processed, in milliseconds.
Range: 1 to 5. |
BACNET INSTANCE NUMBER
The default BACnet instance number is generated by the model number and COM address of the Room Controller. For example, the instance number of a SE8350U5B00 with a COM address of 57 is generated as “83057”.The default instance number appears first. To change the instance number, use the number pad and press Accept and save. Tap the “R” icon to reset to automatic instance addressing.
MODBUS NETWORK SETTINGS
Modbus network screen shows when Modbus is selected in the wired protocol parameter.
PARAMETER DETAILS
Configuration Parameters Default Value | Significance and Adjustments |
COM address
Default value: 254 |
Communication Address
Valid address range is set at 1 to 247 and each Modbus device must have a unique address. Other values not recommended for Modbus.
Default value of 254 disables Modbus communication for the Room Controller.
Range: 0 to 254 |
Network units
Default value: SI |
Measurement Units
Network units transmitted over the BACnet network.
NOTE: Use the Temperature scale parameter to change the display units locally on the Room Controller. Imperial: network units shown as Imperial units. SI: network units shown as International Metric units.
Choices: Imperial or SI |
Baud rate
Default value: 19200 |
Modbus Baud Rate
Automatically detects Modbus baud rate.
Choices: 57600, 38400, 19200, 9600 and 4800 |
Parity
Default value: Even |
Parity
Determines how the parity bit of the character’s data frame is set to detect any errors in the sent/receives frame.
Choices: None, Odd and Even |
Wi-Fi 1/5
The Wi-Fi Network screen shows only in models with optional Wi-Fi module (VCM8002).
PARAMETER DETAILS
Configuration Parameters Default Value | Significance and Adjustments |
Module status Read Only | Module Status
Displays the current status of the Wi-Fi module. It would normally display Ready when the Wi-Fi module is operational.
Status value: Offline, Booting, Initializing, Ready, Fail |
Wi-Fi 2/5
PARAMETER DETAILS
Configuration Parameters Default Value | Significance and Adjustments |
Access point
Default value: Disabled |
Access Point
On this screen, the access point can be enabled or disabled as needed.
Choices: Enabled or Disabled |
Wi-Fi 3/5
PARAMETER DETAILS
Configuration Parameters Default Value | Significance and Adjustments |
Wi-Fi status Read Only | Wi-Fi Status
When not connected to a Wi-Fi network the status remains Idle. Once the RC is on your preferred Wi-Fi network, the status will be displayed as Ready, or Online if it has an internet connection.
Status value: Idle, Connected, Associate, Config, Ready, Online, Disconn, Failure |
Signal strength Read Only | Signal Strength
Signal strength of the Wi-Fi network.
Range: 0 to 100% |
SMTP status Read Only | SMTP Status
Status of the email SMTP server.
Status value: Disabled, Offline, Online |
Wi-Fi 4/5
PARAMETER DETAILS
Configuration Parameters Default Value | Significance and Adjustments |
Facility Expert Read Only | Facility Expert
Shows whether the Facility Expert system is Disabled or Enabled.
Status value: Disabled or Enabled |
Status Read Only | Status
Shows the current status of the Facility Expert system.
Range: Disabled, Offline, Connect., Online, Failure, Unknown. |
Wi-Fi 5/5
Configuration Parameters Default Value | Significance and Adjustments |
Factory reset?
Default value: No |
Erase All
Accepting Yes for both and then tapping ‘Push to accept’ will restore the Wi-Fi module to the factory settings, erase all configuration data and revert the Wi-Fi module firmware to the factory firmware version.
NOTES: • If you lose or forget your password for the Configuration Web Page, you must do a Factory Reset of the Wi-Fi module. • If your Wi-Fi module was connected to Facility Expert, you will need to contact your Facility Expert Administrator before the device can be reconnected after a Factory Reset. |
Are you sure?
Default value: No |
Wi-Fi BACNET NETWORK SETTINGS
BACnet network screens are shown when the wired protocol is set to BACnet or a Wi-Fi module is installed with BACnet/IP enabled. Only one BACnet protocol can be used at a time, either the wired protocol BACnet MS/TP (BACnet Network screens), or the Wi-Fi BACnet IP (Wi-Fi screens).
Configuration Parameters Default Value | Significance and Adjustments |
Network units
Default value: SI |
Measurement Units
Network units transmitted over the BACnet network.
NOTE: Use the Temperature scale parameter to change the display units locally on the Room Controller. Imperial: Network units shown as Imperial units. SI: Network units shown as International Metric units.
Choices: Imperial or SI |
Network lang.
Default value: English |
Network Language
Network language/object names transmitted over network.
Choices: English, French or Spanish |
Port
Default value: 0 Read Only |
Port
The unique short address of Wi-Fi BACnet IP |
BACNET INSTANCE NUMBER
The default BACnet instance number is generated by the model number and COM address of the Room Controller. For example, the instance number of a SE8350U5B00 with a COM address of 57 is generated as “83057”. The default instance number appears first. To change the instance number, use the number pad and press Accept and save. Tap “R” icon to reset to automatic instance addressing.
Configuration Screens
CONFIGURATION 1/9
Configuration Parameters Default Value | Significance and Adjustments |
UI16 config
Default value: None |
Universal Input Configuration No. 1
None: No function will be associated with the input. Input can be used for remote network monitoring. Rem NSB: Remote night setback (NSB) timer clock input. The scheduling gets set as per the binary input and provides low cost setback operation via a dry contact Motion NO and Motion NC: Advanced PIR occupancy functions using a Normally Open (NO) or Normally Closed (NC) remote PIR motion sensor. Window: Forces system to disable any current heating or cooling action by Room Controller when window is open. Choices: None, Rem NSB, Motion NO, Motion NC, Window |
UI17 config
Default value: None |
Universal Input Configuration No. 2
None: No function associated with input Door Dry: Room Controller goes to standby mode when door is opened then closed followed by no presence detection for the next 10 seconds if the local PIR is used in this application. The “Occupancy command” in the Options screen must be set to “Local Occupancy” and “Occupancy Source” must be set to “Motion”. Override: A closed contact forces the Room Controller to go in occupied mode. An open contact keeps the current occupancy mode. Filter: backlit flashing filter alarm shows on the Room Controller screen when input is energized Service: backlit flashing Service alarm shows on Room Controller screen when input is energized.
Choices: None, Door Dry, Override, Filter and Service |
Configuration Parameters Default Value | Significance and Adjustments |
UI19 config
Default value: None |
Universal Input Configuration No. 3
None: no function associated with input though input can be used for remote network monitoring COC/NH: change over dry contact normally heat. Used for hot/cold water or air change over switching in 2-pipe systems COC/NC: change over dry contact normally cool. Used for hot/cold water or air change over switching in 2-pipe systems COS: change over sensor. Used for hot/cold water or air changeover switching in 2 pipe systems Choices: None, COC/NH, COC/NC and COS |
Occupancy src
Default value: Motion |
Occupancy Source
Motion: Occupancy status received from motion sensor. Schedule: Occupancy status determined by the schedule. Mot. Occ: Occupied when scheduled occupied AND when motion is detected. Mot. Unoc: Occupied when scheduled occupied OR when motion is detected.
Choices: Motion, Schedule, Mot. Occ., Mot. Unoc. |
Smart recovery
Default value: Off |
Enable Smart Recovery
Off: No smart recovery. The occupied schedule time is the time at which the system will restart. On: Smart recovery active. The occupied schedule time is the time at which the desired occupied temperature will be attained. The Room Controller automatically optimizes the equipment start time. In any case, the latest a system will restart is 10 minutes prior to the occupied period time.
Smart recovery is automatically disabled if BI16 is configured to remote NSB.
Choices: Off or On |
Setpoint func.
Default value: Dual SP |
Setpoint Function
Local setpoint settings to set the local setpoint interface for the User.
Dual SP: “Minimum” Deadband, Heat and Cool Setpoints can be adjusted independently. Attach SP: “Fixed” Deadband in occupied mode, Heat and Cool setpoints always follow each other, separated by Deadband value (acts like a single setpoint). Choices: Dual SP or Attach SP |
CONFIGURATION 2/9
Configuration Parameters Default Value | Significance and Adjustments |
Mode button
Default value: Normal |
Mode Button
Changes the behavior of the system mode button functionality and hides/shows temperature setpoints on main screen.
Normal: System mode button switches between ‘Off’, ‘Auto’, ‘Cool’ and ‘Heat’. Also displays temperature Setpoints on main screen. Off-Auto: System mode button switches between ‘Off’ and ‘Auto’. Hides temperature Setpoints on main screen. NOTE: Setting ‘Mode button’ to ‘Off-Auto’ forces the ‘Setpoint func.’ parameter to ‘Attach SP’. Choices: Normal or Off-Auto |
Auto mode
Default value: Disabled |
Auto Mode Enable
Enables auto function for the mode button. For sequences 2, 4, and 5 only.
Enabled: auto active (Off-Cool-Heat-Auto) Disabled: auto not active (Off-Cool-Heat)
Choices: Enabled or Disabled |
Standby mode
Default value: Absolute |
Standby Mode Configuration
Standby setpoints used for control.
Absolute: Standby entered values are used for standby mode. Offset: Occupied setpoints +/- Standby diff. used for standby mode.
Choices: Absolute or Offset |
Configuration Parameters Default Value | Significance and Adjustments |
Standby diff.
Default value: 4°F (2°C) |
Standby Temperature Differential
When Standby mode is set to ‘offset’, standby setpoints are calculated as follows:
Standby cool: Cool setpoint + Standby diff. Standby heat: Heat setpoint – Standby diff.
Range: 1 to 5°F (0.5 to 2.5°C) |
Fan cont. heat
Default value: On |
Fan Control in Heating Mode
Configures the operation of the fan when system is heating.
On:Fan on Off-Auto: Fan off if fan mode is auto Off-All: Fan off
Choices: On, Off-Auto or Off-All |
CONFIGURATION 3/9
Configuration Parameters Default Value | Significance and Adjustments |
Fan menu
Default value = On-Auto |
Fan Sequence
Fan Sequence configuration applies to “3 speed” and “ECM” fan type The selected fan sequence in this menu dictates the Fan button options displayed on the Home screen of the room controller. On-Auto: Single Speed configuration. Auto selection will activate fan on demand. On selection will keep the fan On in occupied, standby and override mode, and will activate fan based on demand in unoccupied mode. L-M-H: 3-Speed configuration L-H: 2-Speed configuration L-M-H-A: 3-Speed configuration with Auto fan speed. Auto Mode operation is dependent on Auto Fan parameter. L-H-A: 2-Speed configuration with Auto fan speed mode. Auto Mode operation is dependent on Auto Fan parameter.
Choices: On-Auto, L-M-H, L-H, L-M-H-A and L-H-A |
Auto fan func.
Default value: AS |
Automatic Mode Fan Function
Fan Sequence configuration applies to “3 speed” and “ECM” fan type Auto Speed Fan Mode operation for Fan Menu (L-M-H-A) or (L-H-A).
AS: In Occupied, Standby and Override modes, the Fan stays ON at low speed even if there is no demand for Heating or Cooling. In Unoccupied mode the Fan turns Off when there is no demand for Heating or Cooling. AS/AD: In any Occupancy mode, the Fan turns Off all speeds when there is no demand for Heating or Cooling. Choices: AS or AS/AD |
Configuration Parameters Default Value | Significance and Adjustments |
Fan type
Default value: 3 speed |
Fan Type
Fan type configuration determines the fan control method for the fan coil unit
3 Speed: Fan control using 3 binary outputs (Low, Medium, High) ECM: Fan control using 0-10 Vdc Modulating output.
Choices: 3 speed or ECM |
ECM low volt.
Default value: 2.2 Vdc |
Point only displayed if “Fan type” is set to “ECM”
Voltage to be applied on 0-10 Vdc output when Low fan speed is selected. The points are configurable in units of 0.1 Vdc
Range: 2.0 to 4.0 Vdc |
ECM med. volt.
Default value: 6.0 Vdc |
Point only displayed if “Fan type” is set to “ECM”
Voltage to be applied on 0-10 Vdc output when Medium fan speed is selected. The points are configurable in units of 0.1 Vdc
Range: 4.1 to 7.0 Vdc |
ECM high volt.
Default value: 8.6 Vdc |
Point only displayed if “Fan type” is set to “ECM”
Voltage to be applied on 0-10 Vdc output when High fan speed is selected. The points are configurable in units of 0.1 Vdc
Range: 7.1 to 10.0 Vdc |
CONFIGURATION 4/9
Configuration Parameters Default Value | Significance and Adjustments |
Standby time
Default: 0.5 hours |
Standby Time
Time between the moment where the PIR cover detects last movement in the area, and the time which the Room Controller stand-by setpoints become active.
Note: This parameter is not active when the “Door” function is used (wired or wireless). Range: 0.5 to 24.0 hours (0.5 hour increments) |
Unocc. time
Default: 0.0 hours |
Unoccupied Time
Time between the moment where the Room Controller toggles to stand-by mode, and the time which the Room Controller unoccupied mode and setpoints become active.
Note: Default value of 0.0 hours disables the unoccupied timer. This prevents the Room Controller from being able to switch from stand-by mode to unoccupied mode when PIR functions are used.
Range: 0.0 to 24.0 hours (0.5 hour increments) |
Temp. occ. time
Default value: 2.0 hours |
Temporary Occupancy Time
The time the Room Controller stays in override mode before reverting back to unoccupied mode. When the Room Controller is in unoccupied mode, pressing the on-screen Override icon or closing the contact on UI17, configured as “Remote Override”, sets the Room Controller to Override mode for defined time period, and uses the Occupied Cooling and Heating setpoints.
Range: 0.0 to 24.0 hours |
Configuration Parameters Default Value | Significance and Adjustments |
Deh. hysteresis
Default value: 5 % RH |
Humidity Control Hysteresis
Used only if dehumidification sequence is enabled.
Range: 2 to 20% RH |
Deh. max. cool.
Default value: 100% |
Dehumidification Maximum Cooling Limit
Maximum cooling valve position when dehumidification is enabled. This can be used to balance smaller reheat loads installed in regards to the capacity of the cooling coil.
Range: 20 to 100% |
Deh. lockout
Default value: Disabled |
Dehumidification Lockout
Enables or disables dehumidification based on central network requirements from the BAS front end.
Enabled: Dehumidification Authorized Disabled: Dehumidification Not Authorized
Choices: Enabled or Disabled |
CONFIGURATION 5/9
Configuration Parameters Default Value | Significance and Adjustments |
CPH
Default value: 4 |
Cooling Output Cycles Per Hour
CPH is used to “modulate” On/Off outputs controlling equipment such as compressors. When the Room Temperature is within the Proportional Band, the output performs 3 or 4 CPH. A higher CPH represents a higher accuracy of control at the expense of wearing mechanical components faster.
Note: The CPH does not limit the number of Cycles Per Hour. It is limited by the “Anti short cycle” parameter. 4 CPH is typical for Rooftop applications. Range: 3 to 8 CPH |
Ctrl. type out1
Default value: On/Off |
Control Output for FCU Valves
Defines type of control output for type of valves installed for the FCU application
0-10V DA: Direct Acting analog heating output signal for modulating control of 2-10 Vdc valves. DA = 0 to 100% = 0 to 10 Vdc 0-10V RA: Reverse Acting analog heating output signal for modulating control of 2-10 Vdc valves. RA = 0 to 100% = 10 to 0 Vdc On/Off: normally opened or normally closed 24 VAC 2 position valves Floating: modulating 3 wires control of 24 VAC floating valves
Choices: 0-10V DA, 0-10V RA, On/Off and Floating |
Ctrl. type out2
Default value: Same as 1 |
Control Output for FCU Valves
Defines type of control output for type of valves installed for the FCU application
0-10V DA: Direct Acting analog heating output signal for modulating control of 2-10 Vdc valves. DA = 0 to 100% = 0 to 10 Vdc 0-10V RA: Reverse Acting analog heating output signal for modulating control of 2-10 Vdc valves. RA = 0 to 100% = 10 to 0 Vdc Same as 1: On/Off: normally opened or normally closed 24 VAC 2 position valves Floating: modulating 3 wires control of 24 VAC floating valves
Choices: 0-10V DA, 0-10V RA, Same as 1, On/Off and Floating |
Configuration Parameters Default Value | Significance and Adjustments |
BO8 out time
Default value: 15 min. |
BO8 Aux Output Time Base
Sets reheat output time base. Valid only if reheat sequences are enabled.
Choices: 10 sec. or 15 min. |
BO8 aux. config
Default value: Reheat NO |
BO8 Aux Output Configuration
Aux contact function used for reheat if sequence is set to use BO8 for reheat through network or local. Output directly follows occupancy of Room Controller.
Reheat NO: Contact closes on call for reheat, used for Normally Closed Valve or heat relay. Reheat NC: Contact opens on call for reheat, used for Normally Opened Valve. Aux NO: Occ or St-By = Contact Closed / Unoccupied = Contact Opened Aux NC: Occ or St-By = Contact Opened / Unoccupied = Contact Closed. Output to follow directly main occupancy and Fan on command. Typically used for 2 position fresh air damper applications. Aux F&NO: Occ or St-By & Fan On = Contact Closed / Unoccupied and Fan On or Off = Contact Opened Aux F&NC: Occ or St-By & Fan On = Contact Opened / Unoccupied and Fan On or Off = Contact Closed Choices: Reheat NO, Reheat NC, Aux NO, Aux NC, Aux F&NO and Aux F&NC |
Floating Time
Default value: 1.5 min |
Floating Actuator Timing
Floating actuator stroke timing value. Maximum stroke time of floating valve actuator.
Range: 0.5 to 9.0 minutes (0.5 minute increments) |
Configuration Parameters Default Value | Significance and Adjustments |
Prop. band
Default value: 3.0 |
Proportional Band Setting
Adjusts proportional band used by Room Controller PI control loop. Note: Default value of 3 gives satisfactory operation in most normal installation cases. The use of a superior proportional band different than the factory value is normally warranted in applications where Room Controller location is problematic and leads to unwanted cycling of the unit. A typical example is a wall mounted Room Controller installed between return and supply air feeds and is directly influenced by the supply air stream of unit. Range: 3.0 to 10.0 |
No. of pipes
Default: 2 |
Number of Pipes
Defines the type of system installed.
Choices: 2 or 4 |
Configuration Parameters Default Value | Significance and Adjustments |
Operation seq.
Default: Heat only |
Sequence of Operation
Selects the initial sequence of operation required by the installation type and the application.
Cool only: cooling only Heat only: heating only Cool-rht: cooling with reheat Heat-rht: heating with reheat Cool/heat: cooling and heating Cl/ht-rht: cooling and heating with reheat
When “Pipe Number” is set to 2 and UI19 is set to COC-NH, COC-NC or COS the “Sequence of operation” is as follows: • “Cool only” or “Heat only” will be determined by the UI19 contact status or sensor temperature. • For 2-Pipe application (no reheat): set “Sequence of operation” to “Cool only” or “Heat only” • For 2-Pipe application (with reheat): set “Sequence of operation” to “Cool-rht” or “Heat-rht” Choices: Cool only, Heat only, Cool-rht, Heat-rht, Cool/heat and Cl/ht-rht |
Purge sample
Default: 2.0 hrs |
Purge Sample Period
Time interval between valve samples. Will open valve for a short period adjusted by “Purge open” parameter to sample pipe temperature to decide between heating or cooling mode.
Adjustable: 0.0 to 4.0 hours (0 hours disables the function) |
Purge open
Default: 2 min |
Purge Open
Time the valve opens to sample pipe temperature to decide between heating or cooling mode.
Adjustable: 1 to 3 minutes |
Temp. sensor
Default value: Wired |
Room Temperature Sensor
Sets the source of the indoor room temperature. This parameter allows the user to designate either the Room Controller or any of the paired wireless devices that support temperature to act as the source for the room temperature.
Wired: sets the thermistor connected to UI20 (RS) as the source to report room temperature. Internal: sets the Room Controller as the source for the room temperature. WL 1 to WL 20: sets the selected ZigBee wireless device as the source for the room temperature. Only one device can be selected. Note: The Room Controller uses the internal temperature sensor only if the UI20 (RS) terminal is empty. If a valid temperature sensor is connected to the UI20 terminal, the Room Controller will use the sensor as the control point. Disconnecting the sensor, or if the sensor is faulty, the Room Controller will automatically revert to its internal temperature sensor.
Choices: Wired, Internal and WL 1 to WL 20 |
CONFIGURATION 7/9
Configuration Parameters Default Value | Significance and Adjustments |
Main password
Default value: 0 |
Main Password
Sets a protective access password to prevent unauthorized access to configuration menu parameters. A default value of “0” will not prompt for a password or lock access to the configuration menu.
Range: 0 to 9999. |
User password
Default value: 0 |
User Password
Sets a protective access password to prevent User unauthorized access to main screen adjustments. A default value of “0” will not prompt for a password.
Range: 0 to 9999. |
Schedule menu
Default value: Enabled |
Schedule Menu
Toggles activation of schedule menu direct access.
Enabled: Schedule Menu is directly accessible from the main screen via a touch in the upper corner. Disabled: Schedule Menu can only be accessed through the Setup Menu screens. En.no.clk: Schedule Menu is directly accessible from the main screen via a touch in the upper corner. Clock does not show. Dis.no.clk: Schedule Menu can only be accessed through the Setup Menu screens. Clock does not show. Choices: Enabled, Disabled, En.no.clk and Dis.no.clk |
Configuration Parameters Default Value | Significance and Adjustments |
USB access
Default value: Enabled |
USB Access
Enables/disables USB communication with the SE8000.
Enabled: USB communication with the SE8000 is enabled, so the Uploader tool can be used to upgrade firmware, standby images, LUA script etc. Disabled: USB communication with the SE8000 is disabled, so the Uploader tool cannot be used with the device. it is recommended to disable USB access once the Room Controller has been commissioned to prevent unauthorized access.
Choices: Ensabled and Disabled |
NOTICE
To prevent unauthorized access to the Room Controller via USB, it is recommended that:_
- ”USB access” is set to “Disabled” to prevent changing of firmware, standby image, configuration or LUA scripts via
- ”Main password” is set to a non-zero value to limit configuration menu access to authorized users
Failure to follow these instructions may lead to unauthorized users modifying the firmware or the configuration of the Room Controller.
CONFIGURATION 8/9
Configuration Parameters Default Value | Significance and Adjustments |
Calib. temp.
Default value: 0°F (0°C) |
Calibration Room Temperature Sensor
Room temperature sensor calibration. Offset can be added or subtracted to actual displayed room temperature.
Range: ± 5.0°F (± 2.5°C) |
Calib. humid.
Default value: 0.0 %RH |
Calibrate Humidity Sensor
Offset that can be added or subtracted to actual displayed humidity.
Range: ± 15.0% RH |
RH sensor
Default value: Internal |
Relative Humidity Sensor
Sets the source of the indoor room humidity. This parameter allows the user to designate either the Room Controller or any of the paired wireless devices that support humidity to act as the source for the room humidity.
Internal: Sets the Room Controller as the source for the room humidity. WL 1 to WL 20: Sets the selected ZigBee wireless device as the source for the room humidity. Only one device can be selected. Choices: Internal and WL 1 to WL 20 |
CO2 source
Default value: Local |
CO2 Sensor Source
Sets the source of the indoor CO2. This parameter allows the user to designate either the optional CO2 detection sensor module (VCM8001) or any of the paired wireless devices that support CO2 to act as the source for the room CO2.
None: CO2 source disabled. Local: Sets the optional CO2 detection sensor module as the source for the room CO2. WL 1 to WL 20: Sets the selected ZigBee wireless device as the source for the room CO2. Only one device can be selected. Choices: None, Local and WL 1 to WL 20 |
CONFIGURATION 9/9
Configuration Parameters Default Value | Significance and Adjustments |
Erase all?
Default value: No |
Erase All
Accepting Yes for both and then tapping ‘Push to accept’ returns all values to the factory default settings with the exception of the following: |
• COM address
• Network Units • Network Language • Baud Rate • BACnet Instance • Device Name • Screen Contrast • Lua Script |
|
Are you sure?
Default value: No |
|
Note: Node type in ZigBee Network screen returns to default value (Router). |
Setpoints Screens
SETPOINTS 1/2
Configuration Parameters Default Value | Significance and Adjustments |
Unocc. cool
Default value: 80°F (27°C) |
Unoccupied Cool Setpoint
Cooling Temperature setpoint used by the Room Controller when in Unoccupied mode.
Range: 54 to 100°F (12.0 to 37.5°C) |
Standby cool.
Default value: 78°F (25.5°C) |
Standby Cooling Setpoint
Cooling Temperature setpoint used by the Room Controller when in Standby mode.
Range: 54 to 100°F (12.0 to 37.5°C) |
Occ. cool
Default value: 75°F (24°C) |
Occupied Cool Setpoint
Cooling Temperature setpoint used by the Room Controller when in Occupied or Override mode.
Range: 54 to 100°F (12.0 to 37.5°C) |
Occ. heat.
Default value: 72°F (22°C) |
Occupied Heating Setpoint
Heating Temperature setpoint used by the Room Controller when in Occupied or Override mode.
Range: 40 to 90°F (4.5 to 32.0°C) |
Standby heat.
Default value: 69°F (20.5°C) |
Standby Heating Setpoint
Heating Temperature setpoint used by the Room Controller when in Standby mode.
Range: 40 to 90°F (4.5 to 32.0°C) |
Unocc. heat.
Default value: 62°F (17°C) |
Unoccupied Heating Setpoint
Heating Temperature setpoint used by the Room Controller when in Unoccupied mode.
Range: 40 to 90°F (4.5 to 32.0°C) |
SETPOINTS 2/2
Configuration Parameters Default Value | Significance and Adjustments |
Default heat
Default value: 72°F (22°C) |
Default Heating Setpoint
Used for hospitality applications in stand-alone mode only to reset the occupied setpoints when a new guest enters the room.
When the Room Controller is in unoccupied mode, any movement detected by a wired, wireless or local PIR sensor changes the occupancy mode to occupied modes and uses the “Default Heating Setpoint” as the new occupied setpoints.
NOTE: This functionality is only valid when Stand-by mode = Offset and “Setpoint Func” is set to “Attached”. Range: 65 to 80°F (18.5 to 26.5°C) |
Min. deadband
Default value: 3°F (1.5°C) |
Minimum Deadband
Temperature offset between the Cooling and Heating setpoints to ensure that Cooling setpoint is always warmer than the Heating setpoint. Cooling setpoint ³ (Heating setpoint + Deadband) Range: 2 to 5°F (1.0 to 2.5°C) |
Max heating
Default value: 90°F (32°C) |
Heating Setpoint Limit
Maximum Occupied, Unoccupied, Standby and Override Heating setpoints limit.
Range: 40 to 90°F (4.5 to 32.0°C) |
Min. cooling
Default value: 54°F (12°C) |
Cooling Setpoint Limit
Minimum Occupied, Unoccupied, Standby and Override Cooling setpoint limit.
Range: 54 to 100°F (12.0 to 37.5°C) |
Dehum. SP
Default value: 50%RH |
Dehumidification Setpoint
Used only if dehumidification sequence is enabled.
Range: 30 to 95% RH |
Display Screens
DISPLAY 1/3
Configuration Parameters Default Value | Significance and Adjustments |
User HMI
Default value: 0 |
User HMI
Sets layout of icons on the home screen for various applications. Refer to Customized screen for more information.
Range: 0 to 12 |
Color
Default value: White |
HMI Color
Change background color of the display screen.
Choices: White, Green, Blue, Grey or Dark Grey, Pink, Purple, Red, Orange, Black |
Main display
Default value: Temp. |
Main Display
Shows temperature or setpoint on main display.
Choices: Temperature or Setpoint |
Standby screen
Default value: No |
Standby Screen
When the device is left unattended for 150 seconds, the standby image will appear. A custom image can be uploaded using the Uploader Tool.
No: No Stand by image (Screen dims when no motion is detected) Yes: Stand by Image is displayed after 150 seconds Occ. only: Standby image displays after 150 seconds. Screen turns off after 30 minutes only in occupied or override mode. Screen: Standby image displays after 150 seconds. Screen turns off after 30 minutes only in unoccupied or standby mode Choices: No, Yes, Occ. Only or Screen |
Configuration Parameters Default Value | Significance and Adjustments |
Lock screen
Default value: No |
Lock Screen
Prevents the user from accessing the Room Controller until a password is entered. Screen lockout starts 150 seconds after no activity on the Room Controller (when standby image appears).
This functionality is enabled only if the below conditions are met:
• Standby image loaded • Standby Screen = “Yes” or “Screen” • User Password = not 0
Choices: No or Yes |
Contrast
Default value: 0 |
Contrast
Control screen contrast and brightness.
Range: -5 to 5 |
DISPLAY 2/3
Configuration Parameters Default Value | Significance and Adjustments |
Language
Default value: English |
Display Language
Select language for main display.
Choices: English, French, Spanish, Chinese, Russian, Arabic, Bulgarian, Czech, Danish, Dutch, Finnish, German, Hebrew, Hungarian, Indonesian, Italian, Japanese, Norwegian, Polish, Portuguese, Slovak, Swedish and Turkish |
Units
Default value: °C |
Temperature Scale
Changes the local display units. Refer to Network Units to change the network units broadcasted over the network.
Choices: °C for SI or °F for Imperial. |
Low backlight
Default value: 60% |
Low Backlight
Sets display backlight intensity. This feature is activated (screen dims) 150 seconds after no activity on the Room Controller.
Adjustable: 0 to 100%. |
Night backlight
Default value: 5% |
Night Backlight
Sets backlight display intensity. Parameter only available for models with motion/ light detectors. The screen backlight progressively decreases down to this setting when room is dark.
This feature is used mostly in hospitality applications when a darker non obtrusive lighting level is desired when room is dark. Adjustable: 0 to 100%. |
Configuration Parameters Default Value | Significance and Adjustments |
RH display
Default value: Disabled |
Relative Humidity
Shows humidity level in room in %RH.
Enabled: Display %RH Disabled: Do not display %RH
Choices: Enabled or Disabled |
CO2 display
Default value: Disabled |
CO2 Levels Display
Shows carbon dioxide level in room in ppm.
Enabled: Display CO2 level Disabled: Do not display CO2 level
Note: The CO2 value will only be displayed on the Room Controller home screen if an optional CO2 detection sensor module is installed or a ZigBee wireless CO2 device is paired, and if there is a valid value.
Choices: Enabled or Disabled |
DISPLAY 3/3
Configuration Parameters Default Value | Significance and Adjustments |
Fan status
Default value: Enabled |
Fan Status Display
Hides the fan status in the upper right corner of the User HMI display. Applicable to all User HMI configurations where the fan status is shown. Refer to the User HMI Show/Hide Options in Section 2. Choices: Enabled or Disabled |
System status
Default value: Enabled |
Systen Status Display
Hides the system status in the upper right corner of the User HMI display. Applicable to all User HMI configurations where the system status is shown. Refer to the User HMI Show/Hide Options in Section 2.
Choices: Enabled or Disabled |
Help button
Default value: Enabled |
Help Button Display
Hides the help button in the lower right corner of the User HMI display. Applicable to all User HMI configurations where the help button is shown. Refer to the User HMI Show/Hide Options in Section 2.
Choices: Enabled or Disabled. |
Service View Screens
The service view screens show the current status of certain points locally on the Room Controller. These points can also be viewed through the network. Service view values are Read Only values that allow a service contractor to visualize the status of key functionality to correctly diagnose operational system issues.
SERVICE VIEW 1/9
Configuration Parameters Default Value | Significance and Adjustments |
Room temp. Read Only | Room Temperature
Shows the current room temperature from the configured temperature source. |
UI19 changeover| Read Only | Changeover Temperature Sensor
Shows the temperature of the changeover sensor connected to UI19 terminal. |
UI20 temp. Read Only | Room Temperature Sensor
Shows the temperature of the sensor connected to UI20 (RS) terminal. |
Outdoor temp. Read Only | Outdoor Temperature
Shows the outdoor temperature on the main screen. |
Room humidity Read Only | Room Humidity
Shows the current room humidity percentage from the configured humidity source. |
SERVICE VIEW 2/9
Configuration Parameters Default Value | Significance and Adjustments |
Effective occ. Read Only | Effective Occupancy
Shows as occupied, unoccupied, standby or override.
Display Readings: Occupied, Unoccupied, Override and Standby |
PI cool demand Read Only | Proportional Integral Cooling Demand
Display Readings: 0-100% |
PI heat demand Read Only | Proportional Integral Heat Demand
Display Readings: 0-100% |
Cool dem. limit Read Only | Cooling Demand Limit
Display Readings: 0-100% |
Heat dem. limit Read Only | Heat Demand Limit
Display Readings: 0-100% |
Supply temp. Read Only | Supply Temperature
Shows supply air temperature as measured by the sensor. |
SERVICE VIEW 3/9
Configuration Parameters Default Value | Significance and Adjustments |
UI16 binary Read Only | Universal Input Configuration No. 1
Shows status of input.
Display Readings: Activated or Not Activated |
UI17 binary Read Only | Universal Input Configuration No. 2
Shows status of input.
Display Readings: Activated or Not Activated |
UI19 binary Read Only | Universal Input Configuration No. 3
Shows status of input.
Display Readings: Activated or Not Activated |
Zigb. PIR inst. Read Only | ZigBee Passive Infrared Sensor Installed
Shows if ZigBee wireless motion sensor is paired to a Room Controller or not.
NOTE: This parameter is for ZigBee wireless motion sensors only.
Display Readings: Off or On |
Zigb. sens. mot. Read Only | ZigBee Sensor Motion
Shows if motion is detected by any of the ZigBee wireless motion sensors.
NOTE: This parameter is for ZigBee wireless motion sensors only.
Display Readings: Motion or No Motion |
SERVICE VIEW 4/9
Configuration Parameters Default Value | Significance and Adjustments |
Window alarm Read Only | Window Alarm
Shows On if there is a Window alarm and shows Off if there is no Window alarm. This feature is for both wired and wireless sensors.
Display Readings: On or Off |
Service alarm Read Only | Service Alarm
Shows On if there is a Service alarm and shows Off if there is no Service alarm.
Display Readings: On or Off |
Filter alarm Read Only | Filter Alarm
Shows On if there is a Filter alarm and shows Off if there is no Filter alarm.
Display Readings: On or Off |
Recovery Read Only | Recovery Status
Shows if Smart Recovery is active or not.
Display Readings: On or Off |
Local motion Read Only | Local Motion
Shows if Motion alarm is active or not.
Display Readings: Motion or No Motion |
Deh. status Read Only | Dehumidification Status
Shows if dehumidification is active or not.
Display Readings: On or Off |
SERVICE VIEW 5/9
Configuration Parameters Default Value | Significance and Adjustments |
UO9 config Read Only | UO9 Configuration
Display Readings: Analog, Binary, Relay RC or Relay RH |
UO10 config Read Only | UO10 Configuration
Display Readings: Analog, Binary or Relay RC |
UO11 config Read Only | UO11 Configuration
Display Readings: Analog or Binary |
UO12 config Read Only | UO12 Configuration
Display Readings: Analog or Binary |
Term. 24 10V Read Only | UI24 Analog
Shows the analog value of the UI24 generic Universal Input (in Volts). |
SERVICE VIEW 6/9
Configuration Parameters Default Value | Significance and Adjustments |
UI19 type Read Only | UI19 Input Type
Display Readings: Thermistor, Binary or Voltage |
UI20 type Read Only | UI20 Input Type
Display Readings: Thermistor, Binary or Voltage |
UI22 type Read Only | UI22 Input Type
Display Readings; Thermistor, Binary or Voltage |
UI23 type Read Only | UI23 Input Type
Display Readings: Thermistor, Binary or Voltage |
UI24 type Read Only | UI24 Input Type
Display Readings: Thermistor, Binary, Voltage or Reserved |
SERVICE VIEW 7/9
Configuration Parameters Default Value | Significance and Adjustments |
CO2 eff. source Read Only | CO2 Effective Source
Shows the configured source of the indoor CO2.
Display Readings: None, Local or WL 1 to WL 20 |
CO2 err. code Default value: 0 Read Only | CO2 Error Code
Error code 0x0001 shows if there is an error with the sensor. |
CO2 level Read Only | CO2 Level
Shows CO2 level in PPM.
Display Readings: 0 to 5000 PPM |
CO2 FW rev. Read Only | CO2 Firmware Revision
Shows the Firmware version of the installed CO2 sensor module. |
CO2 S/N
Read Only |
CO2 Serial Number
Shows the serial number of the installed CO2 sensor module. |
SERVICE VIEW 8/9
Configuration Parameters Default Value | Significance and Adjustments |
Eff. sys. mode Read Only | Effective System Mode
Shows the current operating mode of the system. For example, when the system is in Auto mode, this parameter shows whether it is currently heating or cooling.
Display Readings: Cool or Heat |
Eff. setpoint Read Only | Effective Temperature Setpoint
Shows the tempertature setpoint value currently in use by the system. |
SERVICE VIEW 9/9
The Device Name (BACnet name) consists of the model number followed by the COM address (MAC address). The BACnet name can be changed via the BACnet front end and the new name appears on the above screen. For example, when a SE8350U5B00 Room Controller with a MAC address of 41 is connected to a network, its default Device Name is SE8350U5B00-41and its default BACnet Device ID is 83041. Firmware Revision shows the Firmware version currently installed on the Room Controller. Upgrading to a newer Firmware version deletes the previous Firmware version, however, it is possible to set the Room Controller to an earlier Firmware version with the Uploader Tool. ZigBee Revision shows the Firmware version of an onboard ZigBee or optional ZigBee add-on module.
Test Outputs Screens
TEST OUTPUTS
NOTICE |
SAFE OPERATION ENVIRONMENT
Use high caution when manually enabling outputs so as to not cause damage to equipment. It is the responsibility of the Installer or Service Contractor to maintain a safe operation environment during usage. Failure to follow these instructions can result in equipment damage. |
Note 1: The Test Outputs screen allows manual override of specified outputs. After any output state is overridden, the command is canceled after 1 minute of screen inactivity (auto exit to main screen) or when page is exited.
Note 2: These parameters can also be changed via BACnet and the changed parameter background will turn red to indicate the parameter’s value had been overridden. The overridden value remains even if the user exits the main screen
Note 3: Test Outputs values are LIVE. Any output gets displayed immediately for any value change according to the following:
- If any BACnet priority array (1 – 16) includes a value, the displayed state background shows in
- When toggling a value on the screen, the output directly energizes according to the selected
- After any output state gets modified, all overrides get canceled after 1 minute of button inactivity, or if you scroll from one screen to another screen.
Note 4: Test Outputs UO9 to UO12 are dependent on control type configuration. If the mode is set to Float or On/Off, binary options show. If mode is set to Analog, analog options show.
Language Selection Screens
LANGUAGE SELECTION
Only English, French, Spanish, Chinese, and Russian are enabled by default and are accessible to users cycling through languages on the display settings menu screen. To change the language selection settings, tap a language on the screen and then use the arrow buttons to disable or enable it.
NOTE: English is always enabled.
Clock – Schedule Screens
SCHEDULE MENU
Note: The Clock – Schedule Menu screen is directly accessible from the main setup screen.
CLOCK
The Clock settings screen allows the device’s internal time settings to be changed (current time, day, month, year and weekday options), as well as to choose between a 12 hour AM / PM display or 24-hour display
Configuration Parameters Default Value | Significance and Adjustments |
Time format
Default value: AM-PM |
Time Format
Current time display format. Choice between 12 hour (AM – PM) time format or 24 hour time format.
Note: Changing the value of this parameter automatically changes the format of the displayed value of the time parameter. Choices: AM-PM or 24 Hours |
Time
Default value: current time at power up |
Time
Standard time display, 12 hour AM-PM or 24 hour format determined by the Time Format parameter value. |
Year
Default value: 2019 |
Year
Current year
Range: 2000 – 2100 |
Month
Default value: Jan. |
Month
Current month
Range: Jan. – Dec. |
Day
Default value: 1 |
Date
Current date
Range: 1 – 31 |
Weekday
Default value: Monday Read Only |
Current Day
Automatically set based on data received from Year/Month parameters.
Range: Monday – Sunday |
Time source Default value: Local Read Only | Time Source
Shows the source that most recently set the time on the Room Controller.
Display Readings: None, Local, BACnet, NTP or Cloud |
SCHEDULE
There are seven different schedule-setting screens, one for each day of the week. Each day can have different scheduled events where the Room Controller is set to Occupied status or back to Unoccupied status. The Room Controller can use the appropriate setpoints (back and forth) up to three times per day.
Configuration Parameters Default Value | Significance and Adjustments |
Occupied 1 – 3
Default value: None |
Occupied 1 – 3
Defines a time when the Room Controller is automatically set to use the Occupied setpoint.
Note: There are 3 separate Occupied parameter entries
Range: 00:00 – 23:59 |
Unoccupied 1 – 3
Default value: None |
Unoccupied 1 – 3
Defines a time when the Room Controller is automatically set to use the Unoccupied setpoint.
Note: There are 3 separate Occupied parameter entries
Range: 00:00 – 23:59 |
OPTIONS
The options settings allow the Room Controller to function in Occupied or Unoccupied mode following a defined Schedule type set by the user
Configuration Parameters Default Value | Significance and Adjustments |
Occupancy cmd
Default value: Occupied |
Occupancy Command
Loc occ: occupancy is determined by local sequences (either PIR or schedule, as configured under Occ. source). Occupied: force occupied mode. Unocc: force unoccupied mode. Choices: Loc occ, Occupied or Unocc. |
Schedule type
Default value: 7 days |
Schedule Type
7 days: Independent scheduling identified by day of the week (Sunday – Saturday) 5+1+1 days: Weekdays scheduling and Independent Weekend scheduling identified as Weekdays, Saturday and Sunday 5+2 days: Weekdays scheduling and Weekend scheduling identified as Weekdays and Weekend
Choices: 7 days, 5+2 days or 5+1+1 day |
Automatic Demand Response (ADR) Screen
Automatic Demand Response (ADR) feature is used to reduce energy load when electric grid contingencies threaten the supply-demand balance
Configuration Parameters Default Value | Significance and Adjustments |
Permission
Default value: Off |
Automatic Demand Response Permission
Used to permit the ADR to be applicable or not to change the Room Controller setpoints setting or not.
Off: The Load Shedding Demand will not be permitted. On: The Load Shedding Demand will be permitted.
Choices: On or Off |
Shed status Default value: Off Read Only | Load Shedding Status
Displays the status of the Load Shedding Demand, whether it is active (On) or not (Off).
The Load Shedding status is On when the Permission is On, Shed demand is On, and the Shed Override is Off.
Off: Load Shedding Demand is not activated. On: Load Shedding Demand is activated.
Display Readings: On or Off |
Shed demand Default value: Off Read Only | Load Shedding Demand
Sets the request to initiate Load Shedding. This demand can only be set through BACnet by the local Utility company.
Off: No Load Shedding Demand is received or the Shedding demand is disabled. On: Received the Load Shedding Demand or received the signal to activate Load shedding. Display Readings: On or Off |
Configuration Parameters Default Value | Significance and Adjustments |
Shed offset
Default value: 4°F (2°C) |
Load Shedding Offset
Used to change the effective setpoints in occupied, standby and unoccupied modes.
For example, when “Shed status” is On and Room Controller is in occupied mode:
The cooling setpoint is calculated as follows: Occupied cooling setpoint = occupied cooling setpoint + Load shedding offset.
The heating setpoint is calculated as follows: Occupied heating setpoint = occupied heating setpoint – Load shedding offset.
Choices: 4°F to 10°F (2°C to 5.5°C) |
Shed override Default value: Off Read Only | Load Shedding Override
Displays whether the user disabled the ADR request by the utility company. When the demand shed is applied, the user can override the ADR settings from its original setpoints settings.
On: Rejects or cancels shed load demand request from utility company (setpoints remain the same). Off: Allows shed load demand request from utility company (setpoint will change according to shed offset) Display Readings: On or Off |
Wireless Screens
WIRELESS MENU
The Wireless screen shows only in models with onboard ZigBee or optional ZigBee add-on module
ECOSYSTEM SETTINGS
The Ecosystem Settings screens show the network status, the number of paired devices as well as information for each paired device. A maximum of 20 ZigBee wireless devices can be paired to each Room Controller. Tap the forward arrow to obtain information on each paired ZigBee device.
Configuration Parameters Default Value | Significance and Adjustments |
Network status Default value: Not det. Read Only | ZigBee Network Status
Shows current status of ZigBee network.
Pwr on: ZigBee module detected but not configured No NWK: ZigBee configured but no network joined Joined: ZigBee network joined Online: Communicating
Display Readings: Pwr on, No NWK, Joined and Online |
Permit join
Default value: Off |
Permit Join
Setting to ‘On’ allows the Room Controller to pair with a ZigBee device. Value must be set to ‘On’ to pair with initial device and then set to ‘Off’ if user wants to prevent additional ZigBee devices from joining the network. Changing this value to “Off” on the Coordinator prevents any new ZigBee devices from joining the network.
Permit join can be On/Off when the Room Controller is a coordinator, however the parameter is read only when the Room Controller is a router. Permit join stays On for 3 hours.
On: Allows Room Controller to pair with ZigBee wireless device Off: Prevents Room Controller from pairing with ZigBee wireless device, or prevent any additional ZigBee devices from joining network.
Choices: On or Off |
Configuration Parameters Default Value | Significance and Adjustments |
Permit timeout Default value: 0 Read Only | Permit Join Timeout
Allows ZigBee devices to join the Coordinator Room Controller for 180 minutes from the moment it is set to ON. Once the timer elapses, no devices will be able to join the network.
NOTE: Permit Join parameter must be set to ‘On’ to enable this feature.
Range: 0 or 180 minutes |
Paired devices Default value: 0 Read Only | Paired ZigBee Devices
Shows the number of ZigBee wireless devices currently paired with the Room Controller. A maximum of 20 ZigBee wireless devices can be paired with each Room Controller.
Display Readings: 0 to 20 devices |
DEVICE 1-20
This screen is a subset of the Ecosystems screen and shows data for each paired ZigBee device. The Status, Temperature, Humidity and CO2 values will only be visible if they are supported by the device.
NOTE: Device X pages will only show up once devices have been paired.
Configuration Parameters Default Value | Significance and Adjustments |
Function
Default value: None |
ZigBee Wireless Device Function
Shows status of installed ZigBee wireless device.
None: No status reported to Room Controller Window: Window sensor installed Door: Door sensor installed Motion: Device set to detect motion Env. data: Temperature, Humidity, CO2 sensor installed Remove: Removes device from Device list Water: Water leak sensor installed Refrig.: Refrigerator temperature sensor installed Freezer: Freezer temperature sensor installed
Choices: None, Window, Door, Motion, Env. data, Remove, Water, Refrig. and Freezer |
Comm. status Default value: Offline Read Only | Communication Status
Shows if device is communicating with Room Controller
Not paired: Device not paired Online: Device paired and online Offline: Device paired but offline Invalid: Device was paired and Room controller detected a communication error (selected function does not match paired sensor functionality). Display Readings: Not paired, Online, Offline and Invalid |
Battery
Default value: None Read Only |
Wireless Device Battery
Shows current status of battery in wireless device.
Display Readings: None, Normal or Low |
Configuration Parameters Default Value | Significance and Adjustments |
Addr. Read Only | Wireless Device Address
Shows unique IEEE (MAC) address of ZigBee wireless device |
Device values Read Only | Device Values
Shows the ZigBee wireless device values. Values displayed will be different depending on type of device: • Door and Window Sensors: Closed or Open • Motion Sensor: No Motion or Motion • Water Leak Sensor: Normal or Leak • Temperature Sensor: XX.X °C • Humidity Sensor: XX %RH • CO2 Sensor: XXX PPM |
DEVICE GROUPS
The Device Groups screen shows if a particular ZigBee wireless sensor is paired with the Room Controller.
Configuration Parameters Default Value | Significance and Adjustments |
Door installed Default value: No Read Only | Door Contact Installed
Shows if Door sensor is installed.
Display Readings: Yes or No |
Win. installed Default value: No Read Only | Window Contact Installed
Shows if Window sensor is installed.
Display Readings: Yes or No |
Water installed Default value: No Read Only | Water Leak Sensor Installed
Shows if Water Leak sensor is installed.
Display Readings: Yes or No |
TEMPERATURE ALARMS CONFIGURATION
The Temperature Alarms Configuration screens show the values that trigger an alarm only for ZigBee wireless sensors with temperature measurement
Configuration Parameters Default Value | Significance and Adjustments |
Enable
Default value: Off |
Temperature Alarm Enabled
Enables wireless device to alert Room Controller if temperature value reaches defined value in a particular paired device.
Choices: On or Off |
Hysteresis
Default value: 2.0 °F (1.0 °C) |
Temperature Alarm Hysteresis
Choices: 0 to 10 °F (0 to 5.5 °C) |
Ambient high
Default value: 86.0 °F (30.0 °C) |
Temperature Alarm Ambient High
Range: 75 to 122 °F (24 to 50 °C) |
Ambient low
Default value: 40.0 °F (4.5 °C) |
Temperature Alarm Ambient Low
Range: 32 to 45 °F (0 to 7 °C) |
Refrig. high
Default value: 40.0 °F (4.5 °C) |
Temperature Alarm Refrigerator High
(only present if a refrigeration sensor is installed)
Range: 32 to 50 °F (0 to 10 °C) |
Refrig. low
Default value: 32.0 °F (0.0 °C) |
Temperature Alarm Refrigerator Low
(only present if a refrigeration sensor is installed)
Range: 32 to 50 °F (0 to 10 °C) |
Freezer high
Default value: 0.0 °F (-17.5 °C) |
Temperature Alarm Freezer High
(only present if a freezer sensor is installed)
Range: -40 to 32 °F (-40 to 0 °C) |
ALARMS
The Alarms screen shows data for paired Zigbee wireless devices
Configuration Parameters Default Value | Significance and Adjustments |
Low battery Default value: Off Read Only | Low Battery Alarm
Shows if any wireless paired device has a low battery status (On) or no paired device has low battery (Off).
Display Readings: On or Off |
Water leak Default value: Off Read Only | Water Leak Sensor Status
Shows if any water sensor paired device has detected a water leak (On) or no leak detected in any of the water sensor paired devices (Off).
Display Readings: On or Off |
Low temp. Default value: Off Read Only | Low Temperature Alarm
Shows if any temperature sensor paired device has detected a low temperature (On) or no low temperature detected in any of the temperature sensor paired devices (Off).
Display Readings: On or Off |
High temp. Default value: Off Read Only | High Temperature Alarm
Shows if any temperature sensor paired device has detected a high temperature (On) or no high temperature detected in any of the temperature sensor paired devices (Off).
Display Readings: On or Off |
LUA Screens
The LUA settings screens show information about any custom LUA script uploaded to the Room Controller. LUA scripts are not programmable on the Room Controllers. LUA scripts can be uploaded to the Room Controller via the Uploader Tool or via BACnet
Configuration Parameters Default Value | Significance and Adjustments |
Program cmd
Default value: Run |
Program Command
Run: LUA script activated and runs continuously until deactivated Stop: LUA script deactivated
Choices: Stop or Run |
Program status Default value: Idle Read Only | Program Status
Running: LUA script active Halted: LUA script stopped and not active Idle: LUA script is running but not currently performing any actions Waiting: LUA script running and waiting for a response Uploading: LUA script currently unloading from Room Controller Loading: LUA script currently loading to Room Controller Display Readings: Idle, Loading, Running, Waiting, Halted, Unloading |
Program error Default value: No error Read Only | Program Error
No error: No errors in LUA script Syntax: Syntax error in LUA script detected Runtime: Runtime error occurred while running LUA script Memory: Device has run out of memory for the script
Display Readings No error, Syntax, Runtime, Memory |
LUA GENERIC PARAMETERS
The LUA settings include twelve generic parameters that do not have a specific function or pre-configured functions. These parameters can be used in custom Lua scripts to store a value. They are also user configurable in their default state, but when assigned a value via a LUA script or via BACnet (Priority 1-16), they become read only (not configurable locally by the user) and the display color of the parameter changes to red. These parameters can also be configured via ZigBee, however they can still be modified locally by the user
Configuration Parameters Default Value | Significance and Adjustments |
Parameter A
Default value: 0 |
AV25
The value of this parameter depends on what is assigned to it from a BAS or LUA script. |
Parameter B
Default value: 0 |
AV26
The value of this parameter depends on what is assigned to it from a BAS or LUA script. |
Parameter C
Default value: 0 |
AV27
The value of this parameter depends on what is assigned to it from a BAS or LUA script. |
Parameter D
Default value: 0 |
AV28
The value of this parameter depends on what is assigned to it from a BAS or LUA script. |
Parameter E
Default value: 0 |
AV29
The value of this parameter depends on what is assigned to it from a BAS or LUA script. |
Parameter F
Default value: 0 |
AV30
The value of this parameter depends on what is assigned to it from a BAS or LUA script. |
Parameter G
Default value: 0 |
AV225
The value of this parameter depends on what is assigned to it from a BAS or LUA script. |
Parameter H
Default value: 0 |
AV226
The value of this parameter depends on what is assigned to it from a BAS or LUA script. |
Parameter I
Default value: 0 |
AV227
The value of this parameter depends on what is assigned to it from a BAS or LUA script. |
Parameter J
Default value: 0 |
AV228
The value of this parameter depends on what is assigned to it from a BAS or LUA script. |
Configuration Parameters Default Value | Significance and Adjustments |
Parameter K
Default value: 0 |
AV229
The value of this parameter depends on what is assigned to it from a BAS or LUA script. |
Parameter L
Default value: 0 |
AV230
The value of this parameter depends on what is assigned to it from a BAS or LUA script. |
SECTION 4
Appendix A: Terminal Correspondence
The terminals of a SpaceLogic SE8350 are identified differently and have a wider range of possible functions compared to those of any of the SE7300 series Room Controllers. Nonetheless, there is a direct correspondence of functions between the terminals of the SE7300 series and the SE8350 series. Consult the table below to verify the appropriate term when replacing a SE7300 Room Controller with a SE8350 Room Controller.
SE7300 | SE8350 | ||
Terminal name | Terminal ID | Terminal name | Terminal ID |
Binary Input 1 | BI1 | Universal Input 16 | UI16 |
Binary Input 2 | BI2 | Universal Input 17 | UI17 |
Universal Input 3 | UI3 | Universal Input 19 | UI19 |
Sensor Common | Scom | Terminal 18 Common | COM |
Remote Sensor | RS | Universal Input 20 | UI20 – RS |
Sensor Common | Scom | Terminal 21 Common | COM |
Mix/Supply Sensor | MS | Universal Input 22 | UI22 – SS |
Technical Support
For any issues with SmartStruxure Solution or SmartStruxure Lite, contact Schneider Electric Technical Support according to your region. North America (NAM) Product Support
Building Management Systems (BMS): www.nampss.com Global Product Support Building Management Systems (BMS): [email protected] Schneider Electric
CS 30323 F-92506 Rueil-Malmaison Cedex France
Schneider Electric is leading the Digital Transformation of Energy Management and Automation in Homes, Buildings, Data Centers, Infrastructure, and Industries.
- With a global presence in over 100 countries, Schneider is the undisputable leader in Power Management
- Medium Voltage, Low Voltage, and Secure Power, and in Automation Systems. We provide integrated efficiency solutions, combining energy, automation, and software.
- In our global Ecosystem, we collaborate with the largest Partner, Integrator, and Developer Community on our
- Open Platform to deliver real-time control and operational efficiency.
We believe that great people and partners make Schneider a great company and that our commitment to Innovation, Diversity, and Sustainability ensures that Life Is On everywhere, for everyone, and at every moment.
References:
Download Manual
SCHNEIDER ELECTRIC SE8650 thermostat User Guide
OTHER MANUAL
SCHNEIDER ELECTRIC SE8650 thermostat Installation Guide
Leave a Reply