Comfortheat-LOGO

Comfortheat ETN THERMOSTAT  

Comfortheat ETN THERMOSTAT   PRO

WIRING

WIRING OF ETN THERMOSTATComfortheat -ETN -THERMOSTAT  - 1
ETN & C-BUS CONTROL
The ETN Thermostat is suitable for din type switchboard mounting. The connections to the thermostat are:-

Terminal 1 & 2

Terminal 5 & 7
The heater load is normally connected directly to these terminals. Terminal 5 is the 230V Neutral and terminal 7 is the 230V Live. If the heater load is greater than 3600 Watts or 16A these terminals can be connected to the contactor coil to drive a contactor.

Terminal 8 & 9
Sensor input connections. These do not have a polarity.

Terminal 12, 13 & 14
These connections are used to drive the thermostat into setback mode. They are voltage-free contacts so when closed the setback mode operates. For single thermostat operation connect between 12 & 13. For multiple thermostat operations from the one timeclock connect the 1st thermostat across 12 & 13 and loop across to the rest between terminals 13 & 14.

C-Bus Control
To turn the floor heating On/Off (not daily control) the C-Bus can be used to switch the power supply to the ETN thermostat by breaking the 230V power supply to terminals 1 & 2. For daily control it is best to close terminals 12 &13 which will set the thermostat into ‘Setback Mode’ (i.e. a lower temperature). The C-Bus will be programmed for the ‘Setback Mode’ times.

Cable Extension
You can extend the sensor cable with a TWIN wire – Max Length 100m or similar.

WIRING OF ETN THERMOSTAT AND CONTACTOR
Where the floor heating load exceeds 3400W a contactor needs to be installedComfortheat -ETN -THERMOSTAT  - 2

ETN & C-BUS CONTROL
The ETN Thermostat is suitable for din type switchboard mounting. The connections to the thermostat are:-

Terminal 1 & 2
Terminal 1~ 230V L / Terminal 2 ~ 230V N

Terminal 5 & 7
Switched 230V output. The heater load is normally connected directly to these terminals. Terminal 5 is the 230V Neutral and terminal 7 is the 230V Live. If the heater load is greater than 3600 Watts or 16A these terminals can be connected to the contactor coil to drive a contactor.

Terminal 8 & 9
Sensor input connections. These do not have a polarity.

Terminal 12, 13 & 14
These connections are used to drive the thermostat into setback mode. They are voltage free contacts so when closed the setback mode operates. For single thermostat operation connect between 12 & 13. For multiple thermostat operation from the one timeclock connect the 1st thermostat across 12 & 13 and loop across to the rest between terminals 13 & 14.

C-Bus Control
To turn the floor heating On/Off (not daily control) the C-Bus can be used to switch the power supply to the ETN thermostat by breaking the 230V power supply to terminals 1 & 2. For daily control it is best to close terminals 12 &13 which will set the thermostat into ‘Setback Mode’ (i.e. a lower temperature). The C-Bus will be programmed for the ‘Setback Mode’ times.

Cable Extension
You can extend the sensor cable with a TWIN wire – Max Length 100m or similar.

CONTACTOR WIRING DETAILSComfortheat -ETN -THERMOSTAT  - 3

 

REFERENCE:

DOWNLOAD MANUALS:

Comfortheat ETN THERMOSTAT Wiring Diagram

OTHER MANUALS:

Comfortheat ETN Electric Programmable Thermostat Setup Manual

Comfortheat ETN Hydronic Programmable Thermostat Operating Manual

Comfortheat ETN Programmable Thermostat User Manual

Comfortheat-LOGO

Comfortheat ETN THERMOSTAT Wiring Diagram

Leave a Reply

Your email address will not be published. Required fields are marked *

Your post must include a link to this post.

How does this work?
Write a response on your own website and include a link to this post. Then submit your response’s URL here. Your response may appear here after moderation. To update or remove it, edit or delete your original post and submit the same URL again. Learn more about Webmentions.