Introduction

The tekmarNet Thermostat 554 is a communicating touchscreen thermostat designed to operate one heating stage, one cooling stage, and a fan. The heating stage can be either hydronic or forced air and the cooling stage is an air conditioner. There are two auxiliary sensor inputs available to measure room, floor, outdoor, coil or duct temperature. The optional floor sensor allows precise heating of radiant floors by controlling the floor temperature and maintaining the desired room air temperature. The large touchscreen allows you to easily adjust 7-day programmable schedules and room temperature to optimize comfort and energy savings. The 554 can connect to tekmarNet controls using two or four wires or it can operate as a stand-alone thermostat using three wires.

Tekmar-554-Thermostat-Specification-Sheet-1

Specifications

tekmarNet® Thermostat 554 One Stage Heat, One Stage Cool, One Fan
Literature 554_A, 554_C, 554_D, 554_J, 554_Q, 554_U
Control Microprocessor control. This is not a safety (limit) control.
Packaged weight 0.8 lb. (350 g)
Dimensions 5″ H x 3-1/4″ W x 15/16″ D (127 x 82 x 23 mm)
Enclosure White PVC plastic, NEMA type 1
Approvals Meets Class B: ICES & FCC Part 15
Ambient conditions Indoor use only, 32 to 122°F (0 to 50°C), RH ≤90% non-condensing
Power supply 24 V ± 10%, 60 Hz, 1.8 VA standby, NEC / CEC Class 2
Relays 24 V (ac), 2 A
Temperature sensor NTC thermistor, 10 kΩ @ 77°F (25°C ±0.2°C) ß=3892
–Included None
–Optional tekmar type # 070, 071, 072, 073, 076, 077, 079, 082, 083, 084
Warranty Limited 3 Year (See 554_D for full warranty)

Features

  • tekmarNet communication compatible Touchscreen technology
  • Radiant floor heating Programmable schedule
  • Network schedule master or member Optimum start
  • Temporary hold
  • Air group master
  • Zone synchronization
  • 2 auxiliary sensor inputs
  • Room temperature limiting
  • Away scene key

Special requirements
An auxiliary sensor must be used to measure any auxiliary sensor temperatures.

Sample application Drawing

Sample Mechanical diagram

Below is a sample application drawing for this product. This application may include other tekmar products that are required for installation. More sample applications can be found at www.tekmarControls.com.

Tekmar-554-Thermostat-Specification-Sheet-2

Sample Electrical diagramTekmar-554-Thermostat-Specification-Sheet-3

Notice: The information contained herein is not intended to replace the full product installation and safety information available or the experience of a trained product installer. You are required to thoroughly read all installation instructions and product safety information before beginning the installation of this product.

tekmar Control Systems ltd., A Watts Water Technologies Company. Head Office: 5100 Silver Star road, Vernon, B.C. Canada V1B 3K4, 250-545-7749, Fax. 250-545-0650 Web Site: www.tekmarControls.com

Product design, software and literature are Copyright ©2015 by tekmar Control Systems Ltd., A Watts Water Technologies Company

Reference:

Tekmar 554 Thermostat Specification Sheet

Other Manuls: Tekmar 554 Thermostat Quick Set-up Guide

Tekmar 554 Thermostat User Manual

Tekmar 554 Thermostat Installation and Operation Manual

TEKMAR

Tekmar 554 Thermostat Specification Sheet


Posted

in

by

Comments

Leave a Reply

Your email address will not be published. Required fields are marked *