SCHNEIDER ELECTRIC SE7600 thermostat
INSTALLATION
Preparation
- Remove the security screw on the bottom of Terminal Equipment Controller cover.
- Open unit by pulling on the bottom side of Terminal Equipment Controller (Fig. 1).
- Remove wiring terminals from sticker.
- Please read the FCC ID and IC label installed in the cover upon removal of cover for the wireless products.
Location
- Should not be installed on an outside wall.
- Must be installed away from any direct heat source.
- Should not be installed near an air discharge grill.
- Should not be affected by direct sun radiation.
- Nothing should restrict vertical air circulation to the Terminal Equipment Controller.
Installation
- Swing open the Terminal Equipment Controller PCB to the left by pressing the PCB locking tabs (Fig. 2).
- Pull out cables 6” out from the wall.
- Wall surface must be flat and clean.
- Insert cable in the central hole of the base.
- Align the base and mark the location of the two mounting holes on the wall.
Install proper side of base up. - Install anchors in the wall.
- Insert screws in mounting holes on each side of the base (Fig. 2).
- Gently swing back the circuit board on the base and push on it until the tabs lock it.
- Strip each wire 1/4 inch from end.
- Insert each wire according to wiring diagram.
- Gently push excess wiring back into hole (Fig. 3).
- Re-Install wiring terminals in their correct locations (Fig. 3).
- Re-install the cover (top side first) and gently push extra wire length back into the hole in the wall.
- Install security screw.
If replacing an existing Terminal Equipment Controller, label the wires before removal of the Terminal Equipment Controller.
- Electronic controls are static sensitive devices. Discharge yourself properly before manipulating and installing the Terminal Equipment Controller.
- A short circuit or wrong wiring may permanently damage the Terminal Equipment Controller or the equipment.
- All SE7000 series Terminal Equipment Controllers are designed for use as operating controls only and are not safety devices. These instruments have undergone rigorous tests and verification prior
to shipping to ensure proper and reliable operation in the field. Whenever a control failure could lead to personal injury and/or loss of property, it becomes the responsibility of the user / installer / electrical system designer to incorporate safety devices (such as relays, flow switch, thermal protections, etc…) and/or an alarm system to protect the entire system against such catastrophic failures. Tampering with the devices or unintended application of the devices will result in a void of warranty.
THEORY OF OPERATION
The SE7600 uses a Schneider-Electric proprietary adaptive logic algorithm to control the space temperature. This algorithm controls the heating and air conditioning system to minimize overshoot while still providing comfort. It provides exceptional accuracy due to its unique PI time proportioning control algorithm, which virtually eliminates temperature offset associated with traditional, differential-based On-Off Terminal Equipment Controllers.
Features overview
- 7 day schedule models, 2 or 4 events
- Gas, oil or electric system compatibility for all type of applications
- Remote indoor averaging sensing capability
- Temperature averaging with 2, 3, 4, 9 or 16 sensors
- Remote outdoor sensing capability for added flexibility
- System mode lock out
- Heat pump balance point settings
- Remote discharge air sensor input for monitoring purpose
- System efficiency feedback
- Lockable keypads for tamper proofing. No need for Terminal Equipment Controller guards
- Automatic frost protection to prevents costly freeze damage
- Anti short cycle and minimum On-Off run time protection.
Reduces wear and maximizes life span of mechanical equipment. - 2 configurable digital inputs for added flexibility. Each input can be configured as the following:
- None: No function will be associated with the input
- Service: a backlit flashing Service alarm will be displayed on the Terminal Equipment Controller LCD screen when the input is energized. It can be tied in to the AC unit control card, which provides an alarm in case of malfunction.
- Filter: a backlit flashing Filter alarm will be displayed on the Terminal Equipment Controller LCD screen when the input is energized. It can be tied to a differential pressure switch
that monitor filters. - Rem NSB: remote NSB timer clock input. Will disable the internal scheduling of the Terminal Equipment Controller.
The scheduling will now be set as per the digital input. The menu part related to scheduling is disabled and no longer accessible. It provides low cost setback operation via occupancy sensor or from a dry contact. - RemOVR: temporary occupancy contact. Disables all override menu function of the Terminal Equipment Controller.The override function is now controlled by a manual remote momentarily closed contact. When configured in this mode, the input operates in a toggle mode.
With this function enabled it is now possible to toggle between unoccupied & occupied setpoints for the amount of time set by parameter (TOccTime) temporary occupancy time. - Fan lock: used in conjunction with a local air flow sensor connected to the input. Locks out the Terminal Equipment Controller heating and cooling action and displays a local alarm if no air flow is detected 10 seconds after the fan (G terminal) is energized.
- Configurable smart fan operation saves energy during night mode
- Non volatile EEPROM memory prevents loss of parameters during power shortage
- Built in default profile set-up for easier start up and commissioning
- Configurable SPST output relay on Scheduling models for lighting, exhaust fan or fresh air control
- 6 hour typical reserve time for clock in case of power loss
- 0 to 10 VDC economizer output for more retrofit opportunities
- Built in dry bulb economizer logic using outdoor temperature sensor
- Input for supply or mixed air temperature sensor.
Heat pump model-specific features
- Selectable single or dual stage compressor stages
- High balance point:
- Locks out auxiliary heating when outside air temperature is above this value
- Low balance point:
- Locks out heat pump compressor operation when outside air temperature is below this value
- Comfort or economy mode:
- In economy mode, heat pump use is maximized before turning On auxiliary heating
- Compressor or auxiliary interlock:
- Adds flexibility by locking out heat pump operation during auxiliary heating to prevent high pressure trip when the coil is downstream of the auxiliary heat source.
MODEL CHART
Product Matrix selector for the SE7600 series staging and heat pump controllers
Please refer to the following matrix when ordering controllers:
Example:
Please note, not all combinations and variants are available. Refer to the Schneider Electric price list for a complete selection listing all available models.
Network ready
- All Schneider-Electric SE7600 series Terminal Equipment Controllers are designed for stand-alone (Network Ready) operation.
- They can be fully integrated into your choice of automation systems using the available communication adapter options.
- If required, stand-alone (Network Ready) Terminal Equipment Controllers can be field retrofitted with the following communication adapters:
- VCM7600V5045B, Terminal Equipment Controller BACnet® MS-TP communication adapter
- VCM7600V5045E, Terminal Equipment Controller Echelon® Lontalk® communication adapter
- VCM7000V5045W,Terminal Equipment Controller wireless ZigBee communication adapter
TERMINAL, IDENTIFICATION AND FUNCTION
Wiring
Screw terminal arrangement
5 pole left top connector 3 pole left top connector
8 pole bottom connector
MAIN OUTPUTS WIRING
Wiring notes:
Note
- If the same power source is used for the heating stages, install jumper across RC and RH. Maximum current is 2.0 amps.
- If auxiliary output is used to toggle occupancy of the electronic control card inside the equipment, configure the relay parameter (Aux cont) to the N.O. setting. A second relay can be added for additional functionality of the occupancy output.
- Economizer output uses a half bridge rectifier. Reference of the control signal is the common of the power supply of the Terminal Equipment Controller. (Terminal C)
- Electromechanical contacts are to be used with the digital inputs. Electronic triacs cannot be used as mean of switching for the input.
The switched leg to the input for the input to activate is terminal C (common) - The transformer of the unit provides power to the Terminal Equipment Controller and the additional loads that will be wired to the Terminal Equipment Controller.
TYPICAL APPLICATIONS
SE7656B5X45(X)
2 Heat / 2 Cool / Economizer / With Schedule
SE7652H5X45(X)
Heat pump Without Schedule
Remote sensor accessories
Model no. | Description |
S3010W1000 | Wall mounted temperature sensor |
S3020W1000 | Wall mounted temperature sensor+override button and occupancy status |
Remote mount temperature sensors use 10K type 2 NTC thermistors.
Features:
- Each sensor can be configured for various averaging combinations
- Optional occupancy led
- Optional override key
Wiring example of single remote room sensor: |
Wiring examples of 2 remote room sensors for averaging applications: |
Notes for averaging applications:
- s3010W1000 and S3020W1000 can be mixed-matched.
- S3010W1000 and S3020W1000 are to be wired in parallel.
- Respect the dip switch setting in each remote sensor.
Wiring examples of 3 remote room sensors for averaging applications: |
Temperature vs. resistance chart for 10 Kohm NTC thermistor
ºC | ºF | Kohm | ºC | ºF | Kohm | ºC | ºF | Kohm | ºC | ºF | Kohm | ºC | ºF | Kohm |
-40 | -40 | 324.3197 | -20 | -4 | 94.5149 | 0 | 32 | 32.1910 | 20 | 68 | 12.4601 | 40 | 104 | 5.3467 |
-39 | -38 | 303.6427 | -19 | -2 | 89.2521 | 1 | 34 | 30.6120 | 21 | 70 | 11.9177 | 41 | 106 | 5.1373 |
-38 | -36 | 284.4189 | -18 | 0 | 84.3147 | 2 | 36 | 29.1197 | 22 | 72 | 11.4018 | 42 | 108 | 4.9373 |
-37 | -35 | 266.5373 | -17 | 1 | 79.6808 | 3 | 37 | 27.7088 | 23 | 73 | 10.9112 | 43 | 109 | 4.7460 |
-36 | -33 | 249.8958 | -16 | 3 | 75.3299 | 4 | 39 | 26.3744 | 24 | 75 | 10.4443 | 44 | 111 | 4.5631 |
-35 | -31 | 234.4009 | -15 | 5 | 71.2430 | 5 | 41 | 25.1119 | 25 | 77 | 10.0000 | 45 | 113 | 4.3881 |
-34 | 29 | 219.9666 | -14 | 7 | 67.4028 | 6 | 43 | 23.9172 | 26 | 79 | 9.5754 | 46 | 115 | 4.2208 |
-33 | -27 | 206.5140 | -13 | 9 | 63.7928 | 7 | 45 | 22.7861 | 27 | 81 | 9.1711 | 47 | 117 | 4.0607 |
-32 | 26 | 193.9703 | 12 | 10 | 60.3980 | 8 | 46 | 21.7151 | 28 | 82 | 8.7860 | 48 | 118 | 3.9074 |
-31 | 24 | 182.2686 | -11 | 12 | 57.2044 | 9 | 48 | 20.7004 | 29 | 84 | 8.4190 | 49 | 120 | 3.7607 |
-30 | 22 | 171.3474 | 10 | 14 | 54.1988 | 10 | 50 | 19.7390 | 30 | 86 | 8.0694 | 50 | 122 | 3.6202 |
-29 | 20 | 161.1499 | -9 | 16 | 51.3692 | 11 | 52 | 18.8277 | 31 | 88 | 7.7360 | 51 | 124 | 3.4857 |
-28 | 18 | 151.6239 | -8 | 18 | 48.7042 | 12 | 54 | 17.9636 | 32 | 90 | 7.4182 | 52 | 126 | 3.3568 |
-27 | -17 | 142.7211 | -7 | 19 | 46.1933 | 13 | 55 | 17.1440 | 33 | 91 | 7.1150 | 53 | 127 | 3.2333 |
-26 | -15 | 134.3971 | -6 | 21 | 43.8268 | 14 | 57 | 16.3665 | 34 | 93 | 6.8259 | 54 | 129 | 3.1150 |
-25 | 13 | 126.6109 | -5 | 23 | 41.5956 | 15 | 59 | 15.6286 | 35 | 95 | 6.5499 | 55 | 131 | 3.0016 |
-24 | -11 | 119.3244 | -4 | 25 | 39.4921 | 16 | 61 | 14.9280 | 36 | 97 | 6.2866 | 56 | 133 | 2.8928 |
-23 | -9 | 112.5028 | -3 | 27 | 37.5056 | 17 | 63 | 14.2629 | 37 | 99 | 6.0351 | 57 | 135 | 2.7886 |
-22 | -8 | 106.1135 | -2 | 28 | 35.6316 | 18 | 64 | 13.6310 | 38 | 100 | 5.7950 | 58 | 136 | 2.6886 |
-21 | -6 | 100.1268 | -1 | 30 | 33.8622 | 19 | 66 | 13.0307 | 39 | 102 | 5.5657 | 59 | 138 | 2.5926 |
S2000D1000, remote duct mounted temperature sensor complete with junction box.
This sensor can be used for:
- Remote return air temperature sensing with the sensor mounted on the return air duct.
- Outside air temperature sensing with the
- sensor installed in the fresh air plenum.
- Supply air temperature sensor
S2060A1000, remote averaging duct mounted temperature sensor complete with junction box.
This sensor can be used for:
- Remote averaging return air temperature sensing with the sensor mounted on the return air duct.
- Outside air temperature averaging sensing with the sensor installed in the fresh air plenum.
- Mixed air temperature averaging sensor for economizer models with the sensor in the mixing plenum.
S2020E1000, outdoor air temperature sensor
This sensor can be used for:
- Outside air temperature sensing with the sensor installed directly exposed to the elements.
- Sensor uses a water resistant NEMA 4 ABS enclosure for outdoor applications.
S3010W1000 remote wall mounted temperature sensor, dip switch location
Wiring S2000D1000, S2060A1000 and S2020E1000 |
User menu flow chart
NOTE: Prompts may not all be present depending on model selected
CONFIGURATION AND STATUS DISPLAY INSTRUCTIONS
Status display
The Terminal Equipment Controller features a two-line, eight-character display. There is a low level backlight level that is always active and can only be seen at night.
When left unattended, the Terminal Equipment Controller has an auto scrolling display that shows the actual status of the system.
Each item is scrolled one by one with the back lighting in low level mode. Pressing any key will cause the back light to come on to high level.
Manual scroll of each menu item is achieved by pressing the Yes (scroll) key repetitively. The last item viewed will be shown on the display for 30 seconds before returning to automatic scrolling. Temperature is automatically updated when scrolling is held.
Sequence of auto-scroll status display
ROOM TEMPERATURE |
CLOCK STATUS |
SYSTEM MODE |
SCHEDULE STATUS |
OUTDOOR TEMPERATURE |
ALARMS |
x.x °C or °F XX % RH | Monday 12:00 AM | Sys mode auto | Occupied | Outdoor
x.x °C or °F |
Service |
Sys mode off | Occupied Hold | Frost ON | |||
Sys mode cool | Unoccup | SetClock | |||
Sys mode heat | Filter | ||||
Sys mode emer- gency | Fan lock |
Outdoor air temperature
- Outdoor air temperature display is only enabled when outdoor air temperature sensor is connected.
- A maximum range status display of 50 °C (122 °F) indicates a shorted sensor. Associated functions, such as mode lockouts and economizer function are automatically disabled.
- A minimum range status -40 °C (-40 °F) is not displayed and indicates a opened sensor or a sensor not connected. Associated functions, such as mode lockouts and economizer function are automatically disabled.
Alarms
- If alarms are detected, they will automatically be displayed at the end of the status display scroll.
- During an alarm message display, the back lit screen will light up at the same time as the message and shut off during the rest of the status display.
- Two alarms maximum can appear at any given time.
- The priority for the alarms is as follows:
Frost On | Indicates that the heating is energized by the low limit frost protection room temperature setpoint 5.6 °C (42 °F) |
SetClock | Indicates that the clock needs to be reset. There has been a power failure which has lasted longer than 6 hours |
Service | Indicates that there is a service alarm as per one of the configurable digital input (DI1 or DI2) |
Filter | Indicates that the filters are dirty as per one of the configurable digital input (DI1 or DI2) |
Fan lock | Indicates that the heating and cooling action are locked out due to a defective fan operation |
Three status LEDs on the Terminal Equipment Controller cover are used to indicate the status of the fan, a call for heat, or a call for cooling.
Fan coil models
When any of the fans are ON, the FAN LED will illuminate | FAN
o |
When heating is ON, the HEAT LED will illuminate | HEAT
o |
When cooling is ON, the COOL LED will illuminate | COOL
o |
LED OPERATION |
HEATPUMP MODELS SE76XXH |
MULTISTAGE AND SINGLE STAGE MODELS
SE7600A, SE7652A, SE7600B & SE7652B |
MULTISTAGE ECONOMIZER MODELS SE7605B & SE7656B |
Fan LED on | When G Fan terminal operates | When G Fan terminal operates | When G Fan terminal operates |
Heating LED on | When Y1 and or W1 terminal(s) operate in heating mode | When W1 terminal operate in heating mode | When W1 terminal operate in heating mode |
Cooling LED on | When Y1 terminal operate in cooling mode | When Y1 terminal operate in cooling mode | When Y1 terminal op-erate in cooling mode and or economizer output is in function |
USER INTERFACE
User configuring instructions menu
The SE7600 series of Terminal Equipment Controller feature an intuitive, menu-driven, back-lit LCD display that walks users through the configuring steps, making the configuring process extremely simple. This menu is typically accessed by the user to set the parameters such as temperature and time events, system mode,fan mode, etc.
It is possible to bring up the user menu at any time by depressing the MENU key. The status display automatically resumes after exiting the user-configuring menu.
If the user pauses at any given time during configuring, Auto Help text is displayed to help and guide the user through the usage and configuring of the Terminal Equipment Controller.
Ex.:
Press yes key to change cooling temperature setpoint
Use the up or down arrow to adjust cooling setpoint
Local keypad interface
Each of the sections in the menu is accessed and configured using 5 keys on the Terminal Equipment Controller cover.
The priority for the alarms is as follows:
The YES key is used to confirm a selection, to move onto the next menu item and to manually scroll through the displayed information. | |
The NO key is used when you do not desire a parameter change, and to advance to the next menu item. Can also be used to toggle between heating and cooling setpoints. | |
The MENU key is used to access the Main User Menu or exit the menu. | |
The down arrow key is used to decrease temperature setpoint and to adjust the desired values when configuring the Terminal Equipment Controller. | |
The up arrow key is used to increase temperature setpoint and to adjust the desired values when configuring the Terminal Equipment Controller. |
When left unattended for 45 seconds, the display will resume automatic status display scrolling.
To turn on the back light, press any key on the front panel. The back lit display will turn off when the Terminal Equipment Controller is left unattended for 45 seconds
Sequence of user menu:
OVERRIDE RESUME | TEMPERATURE SETPOINTS | SYSTEM MODE SETTING | FAN MODE SETTING | SCHEDULES SETTING | CLOCK SETTING | SCHEDULE HOLD |
Override schd Y/N | Temperat Set Y/N | Sys mode set Y/N | Fan mode set Y/N | Schedule set Y/N | Clock set Y/N | Schedule hold Y/N |
Override schd Y/N | Appears only on stand-alone (Network Ready) models | |||||
Appears only in unoccupied mode | ||||||
Cancel ovrd Y/N | ||||||
Appears only in override mode |
Occupied setpoints adjustments
There is a default profile set in the Terminal Equipment Controller from the factory.
This enables the Terminal Equipment Controller to operate as a non-scheduling unit in day mode operation at start up.
DEFAULT TEMPERATURE SETPOINTS: | DEFAULT MODES: | |
Occupied cooling setpoint = 24 °C (75 °F) | System mode = Auto | |
Occupied heating setpoint = 22 °C (72 °F) | Fan mode = Smart (for models with a communication module
or scheduling network-ready models) Fan mode = Auto (for non-scheduling network ready models) |
|
Unoccupied cooling setpoint = 28 °C (82°F) | ||
Unoccupied heating setpoint = 18 °C (65°F) | DEFAULT SCHEDULES: | |
Fahrenheit scale | Monday through Sunday | |
Setpoint type = permanent | Occupied time is: 12 00 AM | |
Unoccupied time is: 11:59 PM |
There will be a 1 minute unoccupied period every night at 11:59 PM with this default configuration.
A) Override an unoccupied period
- Override
- schd Y/N
This menu will appear only when the Terminal Equipment Controller is in unoccupied mode. The unoccupied mode is enabled either by the internal timer scheduling or by a remote NSB contact via DI1 or DI2.
If DI1 or DI2 is configured to operate as a remote temporary override contact, this menu will be disabled.
Answering yes to this prompt will cause the Terminal Equipment Controller to go into occupied mode for an amount of time equal to the parameter “TOccTime” (1 to 12 hours).
B) Resume regular scheduling
- Cancel
- ovrd Y/N
This menu does not appear in regular operation. It will appear only when the Terminal Equipment Controller is in Unoccupied override mode.
Answering “Yes” to this question will cause the Terminal Equipment Controller to resume the regular setpoints & scheduling.
C) Temperature setpoints
Permanent setpoint changes
- Temperat
- set Y/N
This menu permits the adjustment of all permanent temperature setpoints (occupied and unoccupied) as well as the desired temperature units (°F or °C). Permanent setpoints are written to RAM and EEPROM.
Temporary setpoint changes
Temporary setpoints can be modified through the Up arrow key (▲) and the Down arrow keys (▼).
User will be prompted with the present mode (Heating or Cooling) of the Terminal Equipment Controller and its setpoint.
The Up (▲) arrow key will increment the setpoint by 0.5 degree (F or C).
The Down (▼) arrow key will decrement the setpoint by 0.5 degree (F or C).
Press the Yes key to accept the new setpoint.
Local changes to the heating or cooling setpoints made by the user directly using the up or down arrow are temporary.
They will remain effective for the duration specified by ToccTime.
Setpoints will revert back to their default value after internal timer ToccTime expires.
If a permanent change to the setpoints is required, use the Temperat set ? menu
D) System mode setting
- Sys mode
- set Y/N
This menu is accessed to set system mode operation
Use ▲▼ to set value, Yes key to confirm
Sys mode auto | Automatic mode
Automatic changeover mode between heating and cooling operation |
Sys mode cooling | Cooling mode
Cooling operation mode only |
Sys mode heating | Heating mode
Heating operation mode only |
Sys mode emergency | Emergency heat mode ( heat pump models only ) Forced auxiliary heat operation mode only |
Sys mode off | Off mode Normal cooling or heating operation disabled
If enabled in installer parameters, only the automatic heating frost protection at 50 °F ( 10 °C ) is enabled |
E) Fan mode setting
- Fan mode
- set Y/N
This section of the menu is permits the setting of the fan mode operation.
Use ▲▼ to set value, Yes key to confirm.
F) Schedule set (2 events)
Scheduling can have 2 or 4 events per day. This is set in the configuration menu as per parameter (2/4 event)
- Schedule
- set Y/N
This section of the menu permits the user to set the whether 2 or 4 events is needed.
Each day can be tailored to specific schedules if needed.
- 2 events can be scheduled per day.
- Occupied and unoccupied periods can be set for each day.
Typical examples of a 2 event office schedule
Ex. #1 Office building closed all weekend
Event | Period #1 – Event #1 | Period #1 – Event #2 | ||||
Occupied | Unoccupied | |||||
Setpoint | Cool
72 °F |
Heat
70 °F |
Cool
80 °F |
Heat
62 °F |
Daily
Occupancy |
|
Monday | 7.00 AM | 6.00 PM | Day time only | |||
Tuesday | 7.00 AM | 6.00 PM | Day time only | |||
Wednesday | 7.00 AM | 6.00 PM | Day time only | |||
Thursday | 7.00 AM | 6.00 PM | Day time only | |||
Friday | 7.00 AM | 6.00 PM | Day time only | |||
Saturday | 12.00 PM * | 12.00 PM * | Unoccupied | |||
Sunday | 12.00 PM * | 12.00 PM * | Unoccupied |
Programming consecutive events to the same time will cause the thermostat to choose the last event as the time at which it will set its schedule. In the above example, the thermostat will control to the unoccupied set point until 7:00 AM Monday.
Ex. #2 Office building open all weekend
Event | Period #1 – Event #1 | Period #1 – Event #2 | ||||
Occupied | Unoccupied | |||||
Setpoint | Cool
72 °F |
Heat
70 °F |
Cool
80 °F |
Heat
62 °F |
Daily
Occupancy |
|
Monday | 7.00 AM | 6.00 PM | Day time only | |||
Tuesday | 7.00 AM | 6.00 PM | Day time only | |||
Wednesday | 7.00 AM | 6.00 PM | Day time only | |||
Thursday | 7.00 AM | 6.00 PM | Day time only | |||
Friday | 7.00 AM | 6.00 PM | Day time only | |||
Saturday | 12.00 AM | 11.59 PM ** | Occupied |
G) Schedule set (4 events)
- Schedule
- set Y/N
This section of the menu permits the user to set the whether 2 or 4 events is needed. Each day can be tailored to specific schedules if needed.
- 4 events can be scheduled per day.
- Occupied and Unoccupied periods can be set for each day.
- Scheduling the 3rd. & 4th. Events to the same time will cancel the last period.
Ex. #1 Four event retail establishment schedule
Event | Period #1 –
Event #1 |
Period #1 –
Event #2 |
Period #2 –
Event #3 |
Period #2 –
Event #4 |
|||||
Occupied | Unoccupied | Occupied | Unoccupied | ||||||
Setpoint | Cool
72 °F |
Heat
70 °F |
Cool
80 °F |
Heat
62 °F |
Cool
72 °F |
Heat
70 °F |
Cool
80 °F |
Heat
62 °F |
Daily
Occupancy |
Monday | 7.00 AM | 5.00 PM | 12.00 PM * | 12.00 PM * | Day time only | ||||
Tuesday | 7.00 AM | 5.00 PM | 12.00 PM * | 12.00 PM * | Day time only | ||||
Wednesday | 7.00 AM | 5.00 PM | 12.00 PM * | 12.00 PM * | Day time only | ||||
Thursday | 7.00 AM | 5.00 PM | 7.00 PM | 10.30 PM | Day/evening time only | ||||
Friday | 7.00 AM | 5.00 PM | 7.00 PM | 10.30 PM | Day/evening time only | ||||
Saturday | 12.00 PM * | 12.00 PM * | 12.00 PM * | 12.00 PM * | Occupied | ||||
Sunday | 12.00 PM * | 12.00 PM * | 12.00 PM * | 12.00 PM * | Occupied |
Programming events to the same time will cancel the last period and leave the thermostat in unoccupied mode
Ex. #2 Residential
Event | Period #1 –
Event #1 |
Period #1 –
Event #2 |
Period #2 –
Event #3 |
Period #2 –
Event #4 |
|||||
Occupied | Unoccupied | Occupied | Unoccupied | ||||||
Setpoint | Cool
72 °F |
Heat
70 °F |
Cool
80 °F |
Heat
62 °F |
Cool
72 °F |
Heat
70 °F |
Cool
80 °F |
Heat
62 °F |
Daily
Occupancy |
Monday | 6:00 AM | 8:00 AM | 4:00 PM | 10:00 PM | Day/evening time only | ||||
Tuesday | 6:00 AM | 8:00 AM | 4:00 PM | 10:00 PM | Day/evening time only | ||||
Wednesday | 6:00 AM | 8:00 AM | 4:00 PM | 10:00 PM | Day/evening time only | ||||
Thursday | 6:00 AM | 8:00 AM | 4:00 PM | 10:00 PM | Day/evening time only | ||||
Friday | 6:00 AM | 8:00 AM | 4:00 PM | 11:30 PM | Day/evening time only | ||||
Saturday | 8:00 AM ** | 8:00 AM ** | 8:00 AM ** | 11:59 PM ** | Day time only | ||||
Sunday | 12:00 AM ** | 12:00 AM ** | 12:00 AM ** | 11:59 PM ** | Occupied all day |
Programming consecutive events to the same time will cause the thermostat to choose the last event as the time at which it will set its schedule.
In the above example for Saturday, the thermostat will control to the occupied set point from 8:00 AM until 11:59 PM. Since it is desired to be in occupied mode throughout the night, then it is necessary to program the first event on Sunday at 12:00 AM. The thermostat will force a one minute unoccupied period for a one minute period (between 11:59 PM and 12:00 AM on Saturday).
H) Clock/Day Settings
- Clock
- set Y/N
This section of the menu permits the user to set the time and day.
Time setting | Day setting | Time format setting | |||
Time set? Y/N | No next →
Yes down ↓ |
Day set? Y/N | No next →
Yes down ↓ |
12/24hrs set? Y/N | No = exit Yes down ↓ |
Time 0:00 | Use ▲▼
To set value |
Day Monday | Use ▲▼
To set value |
12/24hrs 12 hrs | Use ▲▼
To set value |
I) Schedule hold
Schedule
hold Y/N
- This menu will only appear on stand-alone (Network Ready) Terminal Equipment Controller, i.e. without a BACnet® Echelon® module.
- This section of the menu permits the user to set a permanent schedule hold, which bypasses the internal Terminal Equipment Controller scheduling.
- The permanent schedule hold function is typically used for nonscheduled events that extend for various periods of time.
- Enabling a permanent occupied or permanent unoccupied schedule hold will cancel any active override.
- The use of temporary setpoints during permanent hold is permitted. The duration of the temporary setpoint is as set per the TOccTime parameter.
- Ex. 3 hours
Use ▲▼ to set value, yes key to confirm
Schedule resume | Resume regular scheduling cancels the permanent hold and re-enables the regular scheduling as set per internal schedule or as per remote NSB via one of the DI’s configured as remote NSB.
This action can also by accomplished by using the Resume menu. Any temporary setpoint that are active will be left active for the duration of the period as set per the TOccTime parameter. |
Schedule occ hold | Hold permanent occupied forces the Terminal Equipment Controller into a permanent occupied mode using the occupied setpoints. All timed scheduling functions are by-passed.
The PERMANENT OCCUPIED status will appear in the automatic status scroll. To resume to regular scheduling, user must scroll to the Schedule Hold menu and select the Schedule resume option. |
Schedule uno hold | Hold permanent unoccupied forces the Terminal Equipment Controller into a permanent unoccupied mode using the unoccupied setpoints. All timed scheduling functions are by-passed.
The PERMANENT UNOCCUPIED status will appear in the automatic status scroll. To resume to regular scheduling, user must scroll to the Schedule Hold menu and select the Schedule resume option. |
- Configuration can be done through the network or locally at the Terminal Equipment Controller.
- To enter configuration, press and hold the middle button “Menu” for 8 seconds
- If a password lockout is active, “Password” is prompted. Enter password value using the “up” and “down” arrows and press “Yes” to gain access to all configuration properties of the Terminal Equipment Controller. A wrong password entered will prevent local access to the configuration menu.
- Once in the configuration menu, press the “No” button repetitively to scroll between all the available parameters.
When the desired parameter is displayed, press “Yes” to adjust it to the desired value using “up” and “down” arrows. Once set,press “Yes” to scroll to the next parameter.
CONFIGURATION PARAMETERS DEFAULT VALUE |
SIGNIFICANCE AND ADJUSTMENTS |
PswrdSet Configuration parameters menu access password Default value = 0 Range is: 0 to 1000 | This parameter sets a password access to prevent unauthorized access to the configuration menu pa- rameters. A default value of “0” will not prompt a password or lock the access to the configuration menu. Range is: 0 to 1000 |
Com Addr
Terminal Equipment Controller networking address Default value = 254 Range is: 0 to 254 |
Conditional parameter to BACnet® MS-TP models SE76xxX5x45B Conditional parameter to Wireless models SE76xxX5x45W
This parameter will only appear when a BACnet® or wireless network adapter is present. If the Terminal Equipment Controller is installed as a stand-alone (Network Ready) unit or with an Echelon® adapter, this parameter will not be used or displayed For BACnet® MS-TP models, the valid range to is from 1 to 127. Default value of 254 disables BACnet® communication for the Terminal Equipment Controller. For wireless models valid range is 0 to 254 with a maximum of 30 Terminal Equipment Controllers per VWG |
PAN ID
Personal Area Network Identification Default value = 0 Range is: 0 to 500 |
Conditional parameter to Wireless models SE76xxX5x45W
This parameter will only appear when a wireless network adapter is present. If the Terminal Equipment Controller is installed as a stand-alone (Network Ready) unit or with a BACnet® or Echelon® adapter, this parameter will not be used or displayed. This parameter (Personal Area Network Identification) is used to link specific Terminal Equipment Control- lers to a single specific Schneider-Electric wireless gateway (VWG). For every Terminal Equipment Control- ler reporting to a gateway (maximum of 30 Terminal Equipment Controllers per gateway), be sure you set the SAME PAN ID value both on the gateway and the Terminal Equipment Controller(s). The default value of 0 is NOT a valid PAN ID. The valid range of available PAN ID is from 1 to 500. |
Channel
Channel selection Default value = 10 Range is: 10 to 26 |
Conditional parameter to Wireless models SE76xxX5x45W
This parameter will only appear when a wireless network adapter is present. If the Terminal Equipment Controller is installed as a stand-alone (Network Ready) unit or with a BACnet® or Echelon® adapter, this parameter will not be used or displayed. This parameter (Channel) is used to link specific Terminal Equipment Terminal Equipment Controllers to specific Schneider-Electric wireless gateway(s) (VWG). For every Terminal Equipment Terminal Equipment Controller reporting to a gateway (maximum of 30 Terminal Equipment Controllers per gateway), be sure you set the SAME channel value both on the gateway and the Terminal Equipment Controller(s). Schneider-Electric recommends using only channels 15 and 25. The default value of 10 is NOT a valid channel. The valid range of available channel is from 11 to 26 |
Get From
Terminal Equipment Controller Get From another device configuration utility Default value = 0 Range is: 0 to 254 |
Conditional parameter to Wireless models SE76xxX5x45W
Entering a MAC address enables an automatic routine that automatically fetches all the required configura- tion properties of the current device from another already configured device and copies the same required configured property values. If a value other than the default value of 255 is entered, user will then be prompted to exit the Configuration Menu thus leaving all other parameter configuration to be copied from the referenced Terminal Equipment Controller MAC address. Ex.: If you are currently configuring MAC12 and the settings matches exactly the settings of ZN MAC5, then enter 5 as the current parameter value. If the process is successful and all required configuration properties have been copied, the value will revert back to 255 If the process is NOT successful and all required configuration properties have NOT been copied ( either the reference device is NOT the same model number or is offline or does not exists ) the value will revert back to 254 to indicate the failure of the process Leaving the Get From parameter to 255 means that every configuration parameters will be set manually. |
DI 1
Digital input no.1 configuration Default value = None |
(None): No function will be associated with the input. Input can be used for remote network monitoring.
(Rem NSB): remote NSB timer clock input. The scheduling will now be set as per the binary input. It pro- vides low cost setback operation via a dry contact Contact opened = Occupied Contact closed = Unoccupied (RemOVR): Temporary override remote contact. Disables all override menu function of the Terminal Equipment Controller. The override function is now controlled by a manual remote momentarily closed contact. When configured in this mode, the input operates in a toggle mode. With this function enabled it is now possible to toggle between unoccupied & occupied setpoints for the amount of time set by parameter (TOccTime) temporary occupancy time. When Override is enabled, an Override status message will be displayed (Filter): a back-lit flashing Filter alarm will be displayed on the Terminal Equipment Controller LCD screen when the input is energized (Service): a back-lit flashing Service alarm will be displayed on the Terminal Equipment Controller LCD screen when the input is energized (Fan lock): a back-lit flashing Fan lock alarm will be displayed on the Terminal Equipment Controller LCD screen when the input is not energized. Used in conjunction with a local airflow sensor connected to the input. Locks out the Terminal Equipment Controller heating and cooling action if no airflow is detected 10 seconds after the fan ( G terminal ) is energized. Open contact = no airflow Closed contacts = airflow present |
DI 2
Digital input no. 2 configuration Default value = None |
Same as above. It is possible to configure both inputs to have the same function. |
MenuScro
Menu scroll Default value = On = Scroll active |
Removes the scrolling display and displays the room temperature/humidity to the user. With this option enabled, no mode, schedule and outdoor temperature status is given.
On = Scroll active Off = Scroll not active |
Lockout
Keypad lockout levels Default value = 0 No lock |
Removes the scrolling display and displays the room temperature/humidity to the user. With this option enabled, no mode, schedule and outdoor temperature status is given.
On = Scroll active Off = Scroll not active |
USER KEY FUNCTIONS | ||||||||
LEVEL |
Resume/ Override scheduling |
Permanent Occupied and Unoccupied Setpoints |
Temporary setpoints using arrows |
System mode setting |
Fan mode setting |
Schedules setting |
Clock setting |
Permanent hold |
0 | ||||||||
1 | ||||||||
2 | ||||||||
pwr del
Power-up delay Default value = 10 seconds |
On initial power up of the Terminal Equipment Controller (each time 24 Vac power supply is removed & re-applied) there is a delay before any operation is authorized (fan, cooling or heating). This can be used to sequence start up multiple units / Terminal Equipment Controller in one location.
10 to 120 seconds |
|||||||
Frost pr
Frost protection enabled Default value = Off |
Off: no room frost protection
On: room frost protection enabled in all system mode at: 42 °F ( 5.6 °C ) Frost protection is enabled even in system Off mode Off or On On heat pump models the system mode will be forced to EMERGENCY mode if frost protection is activated |
|||||||
Heat max
Maximum heating setpoint limit Default value = 90 °F (32 °C) |
Maximum occupied & unoccupied heating setpoint adjustment. Heating setpoint range is: 40 to 90 °F (4.5 to 32.0 °C) | |||||||
Cool min
Minimum cooling setpoint limit Default value = 54 °F (12 °C) |
Minimum occupied & unoccupied cooling setpoint adjustment. Cooling setpoint range is: 54 to 100 °F (12.0 to 37.5 °C) | |||||||
Pband
Proportional band setting Default value 2 = 2.0 °F (1.1 °C) |
Adjust the proportional band used by the Terminal Equipment Controller PI control loop.
Note that the default value of 2.0 °F (1.1 °C) gives satisfactory operation in most normal installation cases. The use of a proportional band different than the factory one is normally warranted in applications where the Terminal Equipment Controller loca- tion is problematic and leads to unwanted cycling of the unit. A typical example is a wall mounted unit where the Terminal Equipment Controller is installed between the return and supply air feeds and is directly influenced by the supply air stream of the unit. |
|||||||
Anticycle
Minimum On-Off operation time for stages Default value = 2 minutes |
Minimum On-Off operation time of cooling & heating stages.
IMPORTANT, anti-short cycling can be set to 0 minutes for equipment that posses their own anti cycling timer. Do not use this value unless the equipment is equipped with such internal timer. Failure to do so can damage the equipment. 0, 1, 2, 3, 4 & 5 minutes Anti-short cycling can be set to 0 minutes for equipment that posses their own anti cycling timer. Do not use that value unless the equipment is equipped with such internal timer. Failure to do so can damage the equipment. |
Heat cph
Heating stages cycles per hour Default value = 4 C.P.H. |
Will set the maximum number of heating stage cycles per hour under normal control operation. It repre- sents the maximum number of cycles that the equipment will turn ON and OFF in one hour.
Note that a higher C.P.H will represent a higher accuracy of control at the expense of wearing mechanical components faster. 3, 4, 5, 6,7 & 8 C.P.H. For multi stage models, heat cph applies to W1 & W2 For heat pump models, heat cph applies to W1 only (Emergency heat ) |
Cool cph
Cooling stages cycles per hour Default value = 4 C.P.H. |
Will set the maximum number of cooling stage cycles per hour under normal control operation. It represents the maximum number of cycles that the equipment will turned on and off in one hour.
Note that a higher C.P.H will represent a higher accuracy of control at the expense of wearing mechanical components faster. 3 or 4 C.P.H. For multi stage models, cool cph applies to Y1 & Y2 For heat pump models, cool cph applies to Y1 & Y2 in cooling and heating independently of the reversing valve position |
Deadband
Minimum deadband Default value = 2.0 °F (1.1 °C) |
The minimum deadband value between the heating and cooling setpoints. When modified, it will take effect only when any of the setpoints are modified again.
Range is: 2, 3, or 4 °F, 1.0 °F increments (1.0 to 2.0 °C, 0.5 °C increments) |
Fan cont
Fan control Default value = On |
Fan control in heating mode.
When selecting On; the Terminal Equipment Controller in all cases will always control the fan (terminal G). Valid for On or Auto fan mode When selecting Off; the fan (terminal G), when heating stages (terminals W1 & W2) are solicited, will not be energized. The fan in this case will be controlled by the equipment fan limit control. Valid only for Auto fan mode. On fan mode will leave the fan always on. ON OR OFF For multi stage models, fan control applies to W1 & W2 For heat pump models, fan control applies to W1 only (Emergency heat) |
Fan del
Fan delay Default value = Off |
Fan delay extends fan operation by 60 seconds after the call for heating or cooling ends. Valid only for Auto fan mode. “On” fan mode will leave the fan always on.
Off or On |
TOccTime Temporary occupancy time
Default value = 2 hours |
Temporary occupancy time with occupied mode setpoints when override function is enabled.
When the Terminal Equipment Controller is in unoccupied mode, function is enabled with either the menu or UI2 configured as remote override input. Range is: 0,1, 2, 3, 4, 5, 6, 7, 8, 9, 10, & up to 24 hours |
Cal RS
Room temperature sensor calibration Default value = 0.0 °F or °C |
Offset that can be added/subtracted to the actual displayed room temperature
± 5.0 °F, (± 2.5 °C) |
Cal OS
Outside air temperature sensor calibration Default value = 0.0 °F or °C |
Offset that can be added/subtracted to the actual displayed outdoor temperature.
± 5.0 °F, (± 2.5 °C) |
H stage
Number of heating stages. Applicable to 2 stage models only Default value = 2 stages |
Will revert the operation of 2 stages Terminal Equipment Controller to single stage operation only when the second heating step is not needed.
1 or 2 stages For heat pump models, H stage is limited to 1 stage only (W1 – Aux. Heat) |
C stage or HP stage Number of cooling stages
2 stages model only Default value = 2 stages |
Will revert the operation of 2 stage Terminal Equipment Controller to single stage operation only when the second cooling step is not needed.
1 or 2 stages For heat pump models, HP stage selects the number of compressor stages |
H lock
Outside air temperature heating lockout Default value = 120 °F (49 °C) |
Disables heating stage operation based on outdoor air temperature.
Function will only be enabled if OS ( outside air temperature sensor ) is connected. From -15 °F up to 120 °F (-26 °C up to 49 °C) |
C lock
Outside air temperature mechanical cooling lockout. Default value = -40 °F (- 40 °C) |
Disables cooling stage operation based on outdoor air temperature. On economizer model, free cooling will not be disabled by this function.
Function will only be enabled if OS (outside air temperature sensor) is connected. From -40 °F up to 95 °F ( -40 °C up to 35 °C ) |
Unocc TM Unoccupied Timer value
Default 0.5 hours |
Time delay between the moment where the Terminal Equipment Controller toggles from occupied to unoccupied after the last movement has been detected by the PIR.
Range is: 0.5 to 24.0 hours in 0.5 hour increments |
2/4event Number of events configuration
Default value = 2 event |
2 events, will set up scheduling for the following Event 1 is for Occupied setpoints
Event 2 is for Unoccupied setpoints 4 events, will set up scheduling for the following Event 1 is for Occupied setpoints Event 2 is for Unoccupied setpoints Event 3 is for Occupied setpoints Event 4 is for Unoccupied setpoints |
Aux cont Auxiliary contact configuration
Default value = N.O. normally open |
This contact can be used to energize peripheral devices such as: lighting equipment, exhaust fans, econo- mizers, etc.
This contact will operate in parallel with the internal occupied/unoccupied schedule of the Terminal Equip- ment Controller or the remote NSB contact if DI1 or DI2 is used. When the system is in OFF mode, the contact will remain in its unoccupied status independently of the occupied / unoccupied schedule. |
Prog rec Progressive recovery enabled
Default value = Off Progressive recovery is automatically disabled if DI 1 and / or DI 2 are configured remote NSB |
Off, = no progressive recovery
The occupied schedule time is the time at which the system will restart. On, = progressive recovery active. The occupied schedule time is the time at which the desired occupied temperature will be attained. The Terminal Equipment Controller will automatically optimize the equipment start time. In any case, the latest a system will restart is 10 minutes prior to the occupied period time. |
Heat Pump models only | |
High bp
High balance point Default value = 90 °F (32.0 °C) Function will only be enabled if OS (outside air temperature sensor) is connected. |
In Heating or Auto mode, it is the outside air temperature value at which the auxiliary heat will be cut off. Above that value, only the heat pump will be used to maintain the heating setpoint
34 to 90 °F (1.0 to 32.0 °C) |
Low bp
Low balance point Default value = -12 °F (-24 °C) Function will only be enabled if OS (outside air temperature sensor) is connected. |
In Heating, Cooling or Auto mode, it is the outside air temperature value at which the heat pump operation will be cut off. Below that value, only the auxiliary heat will be used to maintain the heating setpoint
-40 to 30 °F (-40 to -1.0 °C) |
Comf/eco
Comfort or economy mode Default value = Comfort |
Sets the operation and interaction mode of the heat pump with the auxiliary heat.
Comfort mode. In Heating mode. If the heat pump is not able to satisfy the heating setpoint, the auxiliary heat will be energized to satisfy the same heating setpoint. Economy mode. In Heating mode. If the heat pump is not able to satisfy the heating setpoint, the auxiliary heat will be energized to satisfy only when the temperature has dropped 2.0 °F ( 1.1 °C ) below the heating setpoint. Selecting economy mode will add a deadband between the heatpump & auxiliary heat in heating mode. The actual temperature main- tained will be lower than the true heating setpoint to maximize the heat pump operation. When the outdoor air temperature drops below the low balance point, the deadband will be eliminated and the auxiliary heat will maintain the true heating setpoint alone. Economy mode. In Emergency mode. If Emergency heat mode is selected, the setpoint maintained, will be the heating setpoint. |
Re valve Reversing valve operation
O/B Default value = O |
Heat pump reversing valve operation
O will energize the valve in cooling operation. B will energize the valve in heating operation O OR B |
Comp/aux Compressor/auxiliary interlock
Default value = Off |
Sets the operation and interaction mode of the heat pump with the auxiliary heat.
Interlock Off. In Heating mode. If the heat pump is not able to satisfy the heating setpoint, the auxiliary heat will be energized at the same time as the heat pump stage. Typically applies when the air handler heat pump coil is installed before the auxiliary heat (all electric systems). Interlock On. In Heating mode. If the heat pump is not able to satisfy the heating setpoint, the auxiliary heat will be energized and the heat pump will be cut off. Typically applies when the air handler heat pump coil is installed after the auxiliary heat (add on systems). There is a 2 minute delay to restart the heat pump, when the auxiliary heat is shut down Off or On |
Notes for Heat Pump models: When the outside air sensor is not connected or is shorted, the Terminal Equipment Controller bypasses the heating / cooling lockouts and the low / high balance points. Also Heat Pump model when set in Emergency system mode bypasses heating lockout and permits auxiliary heating whenever a heating demand occurs. |
chngstpt
Changeover setpoint Default value = 55 °F (13.0 °C) |
In Cooling mode.
The outside air temperature value at which the cooling will be switched over from mechanical ( compressor ) to free cooling (economizer) 14 to 70 °F ( -10.0 to 21.0 °C ) |
min pos
Minimum position Default value = 0% |
Outside air damper minimum position.
Will be active only when fan is on ( G terminal ) and the internal or remote scheduling is in occupied mode. When internal or remote scheduling is in unoccupied mode and/or fan is off, minimum position will be set to 0% 0 to 100 % = 0 to 10 VDC output range |
C mech
Mechanical cooling allowed Default value = Off |
In Cooling mode.
Allows the operation of the mechanical cooling if the free cooling ( economizer ) cannot maintain the cooling setpoint. Off Typically applies when the MS ( mixed air temperature sensor ) is installed after the mechanical cooling refrigeration coils. In this case, mechanical cooling will never operate at the same time as free cooling. On Typically applies when the MS (mixed air temperature sensor) is installed before the mechanical cooling refrigeration coils in the mixing plenum. In this case, mechanical cooling is allowed when the free cooling (economizer operation) cannot maintain the cooling setpoint. Off or On |
Mix stpt
Mixed air setpoint Default value = 55 °F (13.0 °C) |
Free cooling mixed air setpoint when economizer mode is enabled.
50 to 90 °F (10.0 to 32.0 °C) |
MS dis
Display mixed air temperature |
Used as diagnostic / service help to troubleshoot and diagnose economizer operation. |
TROUBLESHOOTING GUIDE
All models
Symptom | Possible Cause | Corrective Action |
No display on the Terminal Equipment Controller |
Absent or incorrect supply voltage | Check power supply voltage between C & RC to be from 19-30 VAC Check for tripped fuse or circuit breaker |
Overloaded power transformer |
Verify that the transformer used is powerful enough (enough VA’s) to supply all controlled devices including the Terminal Equipment Controller | |
Keyboard menu does not access all functions | Keyboard locked | Change configuration parameter LOCKOUT to value “0” to access all levels of the menu |
Temperature setpoints revert to original value after a certain time period |
Temporary setpoint option se- lected |
1. The Terminal Equipment Controller needs to be in Permanent setpoint mode for the new setpoint to be kept and memory and used all the time
2. Go to the Set temperature menu. 3. The last prompt is setpoint type. Set it to Permanent setpoint |
Terminal Equipment Controller will not call for heating |
Wrong mode selected | Select heating mode |
Terminal Equipment Controller in Unoccupied mode | Select Occupied Hold in Schedule hold or Override to force the Terminal Equipment Controller Occupied heating setpoint | |
Anticycle delay active | Wait, the anticycling period will end and the equipment will start | |
Heating setpoint is satisfied | Raise the Heating setpoint | |
Heating lockout attained | 1. Mode is locked out based on outside air temperature
2. Change configuration parameter H Lock to value 120 °F ( 49 °C ) to by-pass lockout |
|
Wiring error |
1. Start the Fan by forcing the Fan ON mode
2. Put a jumper across terminals RH & W1. The heating should come ON. If it does not, verify wiring and check if a jumper is required between RC & RH |
|
Terminal Equipment Controller will not call for cooling |
Wrong mode selected | Select cooling mode |
Terminal Equipment Controller in Unoccupied mode | Select Occupied Hold in Schedule hold or Override to force the Terminal Equipment Controller Occupied cooling setpoint | |
Anticycle delay active | Wait, the anticycling period will end and the equipment will start | |
Cooling setpoint is satisfied | Lower the cooling setpoint | |
Cooling lockout attained |
1. Mode is locked out based on outside air temperature
2. Change configuration parameter C Lock to value -40 °F ( -40 °C ) to bypass lockout |
|
Wiring error |
1. Start the Fan by forcing the Fan ON mode
2. Put a jumper across terminals RC & Y1. The cooling should come ON. If it does not, verify wiring |
|
The Terminal Equipment Controller will not turn on the fan |
Wrong mode selected | 1. Start the Fan by forcing the Fan ON mode
2. Put a jumper across terminals RC & G. The fan should come ON. If it does not, verify wiring |
Wiring error | ||
Digital display shows missing digits or erratic segments |
Defective display |
Replace Terminal Equipment Controller |
Heat pump models
Symptom | Possible Cause | Corrective Action |
Auxiliary heat does not operate |
Wrong mode selected | Select emergency heat mode |
Terminal Equipment Controller in Unoccupied mode | Select Occupied Hold in Schedule hold or Override to force the Terminal Equipment Controller Occupied heating setpoint | |
Anticycle delay active | Wait, the anticycling period will end and the equipment will start | |
Heating setpoint is satisfied | Raise the Heating setpoint | |
High Balance point attained |
1. Mode is locked out based on outside air temperature
2. Change configuration parameter High BP to value 90 °F (32 °C) to by-pass lockout |
|
Heating lockout attained |
1. Mode is locked out based on outside air temperature
2. Change configuration parameter H Lock to value 120 °F ( 49 °C ) to bypass lockout |
|
Wiring error |
1. Start the Fan by forcing the Fan ON mode
2. Put a jumper across terminals RH & W1. The heating should come ON. If it does not, verify wiring and check if a jumper is required between RC & RH |
|
Heat pump does not operate in heating mode |
Wrong mode selected | Select heating mode |
Terminal Equipment Controller in Unoccupied mode | Select Occupied Hold in Schedule hold or Override to force the Terminal Equipment Controller Occupied heating setpoint | |
Anticycle delay active | Wait, the anticycling period will end and the equipment will start | |
Heating setpoint is satisfied | Raise the Heating setpoint | |
Low Balance point attained |
1. Mode is locked out based on outside air temperature
2. Change configuration parameter Low BP to value -12 °F (-24 °C) to bypass lockout |
|
Heating lockout attained |
1. Mode is locked out based on outside air temperature
2. Change configuration parameter H Lock to value 120 °F ( 49 °C ) to bypass lockout |
|
Wiring error |
1. Start the Fan by forcing the Fan ON mode
2. Put a jumper across terminals RH & W1. The heating should come ON. If it does not, verify wiring and check if a jumper is required between RC & RH |
|
Wrong reversing valve configuration |
1. Wrong selection of parameter Re Valve
2. Select O will energize the valve in cooling operation. Valve is normally heat. 3. Select B will energize the valve in heating operation. Valve is normally cool. |
Schneider Electric- Small Building Systems
Tel. Americas: North Andover, MA 1-800-225-0962 Tel. Europe: Malmö, Sweden +46 40 38 68 50 Tel. Asia Pacific: Hong Kong +852 2565 0621
II-SE7600-A4.EN.6.2011.v1
www.schneider-electric.com/buildings
References:
Download Manual
SCHNEIDER ELECTRIC SE7600 thermostat Installation Guide
OTHER MANUAL
SCHNEIDER ELECTRIC SE7600 thermostat Product Specification Guide
Leave a Reply