SALUS VS35 Wired Digital Non-Programmable Thermostat Quick Guide

Salus-logo

SALUS VS35 Wired digital Non-Programmable thermostat 

SALUS-VS35-Wired-digital-Non-Programmable-thermostat-featured

Terminals description

Terminal Description
L,N Power Supply 230 V AC
NSB Night SetBack (input 230 V AC)
SL Switched output (230 V AC)
S1, S2 External temperature sensor

Proper thermostat placementSALUS-VS35-Wired-digital-Non-Programmable-thermostat-fig-1

Button FunctionsSALUS-VS35-Wired-digital-Non-Programmable-thermostat-fig-2

LCD Icon descriptionSALUS-VS35-Wired-digital-Non-Programmable-thermostat-fig-3

  1. SALUS-VS35-Wired-digital-Non-Programmable-thermostat-fig-10Current active mode
  2. Comfort mode
  3. Standard mode
  4. Economic mode
  5. Automatic mode
  6. Frost protection mode
  7. Temperature unit
  8. Manual mode / temp. override
  9. Current / set temperature
  10. Key lock
  11. Settings
  12. Additional temperature sensor
  13. Cooling
  14. Heating

Installation

The VS35 thermostat has been designed for flush mounting in a standard electrical box with a diameter of 60 mm.SALUS-VS35-Wired-digital-Non-Programmable-thermostat-fig-4

Wiring diagrams

An additional temperatur Te sensorSALUS-VS35-Wired-digital-Non-Programmable-thermostat-fig-6 is optional.

VS35 thermostat in connection with wiring centre 
In this diagram, the VS30 thermostat manages the NSB function, more details about NSB function can be found on the next page.SALUS-VS35-Wired-digital-Non-Programmable-thermostat-fig-5

Note: In the KL06 wiring centre, the SL terminal is marked with an arrow icon .
NSB function and an additional temperature sensor SALUS-VS35-Wired-digital-Non-Programmable-thermostat-fig-6 is optional.

VS35 thermostat in connection with actuator or pumpSALUS-VS35-Wired-digital-Non-Programmable-thermostat-fig-7

VS30 thermostat in connection with a boiler with a “NO” voltage free terminal through the RM-16A relay

SALUS-VS35-Wired-digital-Non-Programmable-thermostat-fig-8

Temperature setting

Press any button to highlight the screen, then follow the steps below:SALUS-VS35-Wired-digital-Non-Programmable-thermostat-fig-9

Manual mode

temperature settings
There are 4 temperature levels available. In manual mode only one temperature level is active (icon in the frameSALUS-VS35-Wired-digital-Non-Programmable-thermostat-fig-10 indicates which mode is currently choosen). For each temperature levels you can set a different temperature.

  • SALUS-VS35-Wired-digital-Non-Programmable-thermostat-fig-11Comfort mode
  • SALUS-VS35-Wired-digital-Non-Programmable-thermostat-fig-12Standard mode
  • SALUS-VS35-Wired-digital-Non-Programmable-thermostat-fig-13Economic mode
  • SALUS-VS35-Wired-digital-Non-Programmable-thermostat-fig-14Frost protection mode. Usually used in a longer period of absence or during the holidays (available only in heating mode).

Press any button to highlight the screen, then follow the steps below:SALUS-VS35-Wired-digital-Non-Programmable-thermostat-fig-15

NSB function – automatic mode
The NSB (Night SetBack) function can automatically change temperatures on VS35 daily thermostats via VS30 programmable thermostat connected to a wiring centre (or another external clock). NSB function switches between comfortable temperatureSALUS-VS35-Wired-digital-Non-Programmable-thermostat-fig-11and economic temperatureSALUS-VS35-Wired-digital-Non-Programmable-thermostat-fig-13.
To activate the automatic mode, select the icon A. On display together with the A icon, the controller indicates active temperature mode:SALUS-VS35-Wired-digital-Non-Programmable-thermostat-fig-11 or SALUS-VS35-Wired-digital-Non-Programmable-thermostat-fig-13.

Press any button to highlight the screen, then follow the steps below:SALUS-VS35-Wired-digital-Non-Programmable-thermostat-fig-16

Note: For the NSB function to work, it is necessary to connect the wirings properly. Connection diagrams can be found on the previous page.

Changing the HEATING / COOLING mode

Press any button to highlight the screen, then follow the steps below:SALUS-VS35-Wired-digital-Non-Programmable-thermostat-fig-17

Note: Heating / cooling mode can also be set using the service parameter d18.

Offset function (temperature calibration)

The VS35 thermostat allows you to adjust the displayed temperature ± 3.0°C. You can do it according to the following steps:
Press any button to highlight the screen, then follow the steps below:SALUS-VS35-Wired-digital-Non-Programmable-thermostat-fig-18

Note: You can also set the Offset temperature value using the service parameter d02.

Installer settings

Press any button to highlight the screen, then follow the steps below:SALUS-VS35-Wired-digital-Non-Programmable-thermostat-fig-19

Note: To restore the thermostat’s factory settings, in step 2 set the PSuu to 47 code, and confirm the selection with the button.

dxx Function Value Description Default value
 

d01

 

Control method temperature

0 PWM algorithm  

0

1 Span ±0.25°C
2 Span ±0.5°C
 

d02

 

Offset temperature

 

from -3.0°C to +3.0°C

If the thermostat indica- tes wrong temperature, you can correct

it by ± 3.0°C

 

0°C

 

d03

Using a floor temperature sensor (S1, S2) 0 No sensor  

0

1 Sensor is connected
 

 

d04

External sensor used for air

or floor temperature measurement (Function is active, when d03=1)

 

0

Thermostat measures the temperature only on the external sensor  

 

0

 

1

The sensor is used as a protection against overheating the floor
 

d05

Cooling mode control method 1 Span ±0.5°C  

2

2 Span ±1.0°C
 

d06

Type of thermoelectric actuator 0 NO – normally open  

1

1 NC – normally closed
 

d07

 

Valve protection

0 OFF  

1

1 ON
d08 Frost protection temperature 5-17°C Frost protection / Holiday mode temperature 5°C
 

d12

Heating temperature limit  

5-35°C

The maximum heating temperature that can be set by the user  

35°C

 

d13

Cooling temperature limit  

5-40°C

The minimum cooling temperature that can be set by the user  

5°C

 

 

d14

Maximum floor temperature

(this function is active  in heating mode when d04 = 1)

 

 

6-45°C

In order to protect the floor from overheating, heating will be turned OFF, when the maximum temperature of the floor sensor will be reached  

 

27°C

 

 

d15

Minimum floor temperature

(this function is active  in heating mode when d04 = 1)

 

 

6-45°C

In order to protect the floor, heating will be turned ON, when the minimum temperature of the floor sensor will

be reached

 

 

10°C

 

 

d16

Lower floor temperature limit for cooling

(this function is active  when d04 = 1)

 

 

6-45°C

In order to protect the floor, cooling will

be turned OFF, when the minimum temperatu-

re will be reached

 

 

6°C

 

d18

Operating mode HEATING / COOLING 0 Heating system  

0

1 Cooling system

Error codes

Error code Description
Err02 The maximum/minimum floor temperature has been exceeded
Err03 The temperature sensor is faulty
Err04 The temperature sensor is shorted

Reference

Download Manual

SALUS VS35 Wired Digital Non-Programmable Thermostat Quick Guide