Meitay-tec MTS-X500 Touch Screen Thermostat Owner Manual

Meitay-tec logo

Meitay-tec MTS-X500 Touch Screen Thermostat 

Meitay-tec MTS-X500 Touch Screen Thermostat 

Introduction

Meitay-tec MTS-X500 Touch Screen Thermostat-1

Turning the unit ON or OFF

  • Press theMeitay-tec MTS-X500 Touch Screen Thermostat-2 button to turn the unit ON – system mode and fan speed symbols will appear on display.
  • Press again to turn the unit OFF – the symbols will disappear.Meitay-tec MTS-X500 Touch Screen Thermostat-3

Adjusting the set-point temperature 

  • While the thermostat is ON, press theMeitay-tec MTS-X500 Touch Screen Thermostat-4 buttons – the set-point temperature will flash.
  • Press again to adjust the set point.

Switching between system modes

  • Press the Meitay-tec MTS-X500 Touch Screen Thermostat-5 button switch between system modes:

Notes:

  • During demand for cooling (cooling active), theMeitay-tec MTS-X500 Touch Screen Thermostat-7 will flash.
  • During demand for heating (heating active), the Meitay-tec MTS-X500 Touch Screen Thermostat-8 will flash.

The selection of system modes may be disabled depending on the configuration of the CTU main board connected to the panel.

Switching between fan speeds

  • Press theMeitay-tec MTS-X500 Touch Screen Thermostat-9 button to switch between fan speeds:
    Note: When Auto speed Is selected, the word “AUTO” and the active fan speed will appear on the display.

The selection of fan speeds may be disabled depending on the configuration of the CTU main board connected to the panel.Meitay-tec MTS-X500 Touch Screen Thermostat-10

Fan on demand (Auto fan)

Press and hold theMeitay-tec MTS-X500 Touch Screen Thermostat-9button to activate or deactivate the fan on demand (Auto fan) function.

Notes:  

  • When activated, the fan will run with demand for cooling or heating.
  • The fan-on-demand function cannot be activated with “Fan only” mode.

This option may be disabled, depending on the type of the CTU main board connected to the panel.Meitay-tec MTS-X500 Touch Screen Thermostat-11

Faults
F8 – Communication fault with the CTU main board Check the wiring connection between the CTU and the room panel and verify the DIP Switches configuration.

Switching between temperature scales

Press and hold the Meitay-tec MTS-X500 Touch Screen Thermostat-5 button for 5 seconds to switch between temperature scales.

Installation Instructions

The MTS-X500-02 Room Module is designed for flush mounting in the room to be controlled. It should be located where the occupant can easily read the display and use the controls.
If the built-in temperature sensor is being used to measure room temperature, the panel should be placed where the temperature is representative of the general room conditions, away from cold or warm air draughts, radiant heat and direct sunlight.
The panel should not be installed on an outside wall. The standard installation height is 1.5 meters (5 feet) from the floor.

  • The MTS-X500-02 Room Module is designed for flush mounting in the room to be controlled. It should be located where the occupant can easily read the display and use the controls.
  • If the built-in temperature sensor is being used to measure room temperature, the panel should be placed where the temperature is representative of the general room conditions, away from cold or warm air draughts, radiant heat, and direct sunlight.
  • The panel should not be installed on an outside wall.
    The standard installation height is 1.5 meters (5 feet) from the floor.

WARNING: Risk of Electric Shock and Property Damage. Disconnect the power supply before making electrical connections. The installation is to be performed by a qualified electrician.
WARNING: The integrated circuits in the controller are sensitive to static currents. Take suitable precautions.

Installation procedure:

  1. separate the front display from the back plastic cover by inserting a small flat screwdriver into each of the three slots as shown in the picture and rotating it gently.
  2. Remove the front display and keep it in a safe place.
  3. Connect the wires as shown in the enclosed wiring diagram. All terminals accept 1×0.5mm2/24 AWG.
  4. If necessary, make changes to the DIP switch’s position as explained in this manual.
  5. Place the thermostat in the electrical box and tighten up the 2 screws (Gewiss Box – GW 24 203).
  6. Adapt the front frame panel into its place, by pushing it towards the wall.Meitay-tec MTS-X500 Touch Screen Thermostat-12

Wiring diagramMeitay-tec MTS-X500 Touch Screen Thermostat-13

DIP Switch settingsMeitay-tec MTS-X500 Touch Screen Thermostat-14

Switch 1 – Temperature readings from CTU or from room panelMeitay-tec MTS-X500 Touch Screen Thermostat-15

  • Switch 2 – Always OFF
  • Switch 3 – Always OFF
  • Switch 4 – Always OFF
  • Switch 5 – Always OFF
  • Switch 6 – Always OFF

Technician Settings

Enter technician settings

  • Adjust the set-point temperature to 10ºC – the buttonMeitay-tec MTS-X500 Touch Screen Thermostat-16will appear on display.
  • To enter technician settings, press and hold the Meitay-tec MTS-X500 Touch Screen Thermostat-16 button for 5 seconds.
  • Use the Meitay-tec MTS-X500 Touch Screen Thermostat-5button to advance to the next parameter.
  • Use theMeitay-tec MTS-X500 Touch Screen Thermostat-9 button to return to return to the previous parameter.
  • Press theMeitay-tec MTS-X500 Touch Screen Thermostat-2button or wait 60 seconds to exit technician and return to normal display.Meitay-tec MTS-X500 Touch Screen Thermostat-18

P1 Temperature readings calibration offset

  • Use the Meitay-tec MTS-X500 Touch Screen Thermostat-4 buttons to adjust the offset
  • Range: -6ºC…+6ºC, default 0ºC

P2 Enable/Disable dimming

  • Using theMeitay-tec MTS-X500 Touch Screen Thermostat-4buttons, select between:
  • 00 – Disable screen dimming
    01 – Enable dimming (default)
    If no key is pressed, during the time set in parameter P3, the display will dim Meitay-tec MTS-X500 Touch Screen Thermostat-19

P3 Screen dimming time delay

  • Using theMeitay-tec MTS-X500 Touch Screen Thermostat-4buttons, adjust the time delay before the screen will dim
  • Range: 0…99 sec., default: 5 sec.

P4 Dimming percentage value

  • Using theMeitay-tec MTS-X500 Touch Screen Thermostat-4buttons, adjust the dimming percentage value
  • Range: 10…90%, default: 10%Meitay-tec MTS-X500 Touch Screen Thermostat-20

P5 Display brightness

  • Using the and buttons, adjust the time display brightness
  • Range: 50…100%, default: 100%

P6 Show/Hide lighting button

  • Using the and buttons, select between:
    0 – Hide the lighting button
    1 – Show the lighting button (default)
    Note: the lighting button will only available with some CTU types. It will never appear on display when the CTU does not support the lighting featureMeitay-tec MTS-X500 Touch Screen Thermostat-21

P7 Enable/Disable the beeper

  • Using the and buttons, select between:
    0 – Disable the beeper
    1 – Make the panel beep
    whenever a button is pressed

Important! Reset the set-point temperature to the desired valueMeitay-tec MTS-X500 Touch Screen Thermostat-22

www.meitavtec.com

REFERENCE:

DOWNLOAD MANUALS:

Meitay-tec MTS-X500 Touch Screen Thermostat Owner Manual

OTHER MANUALS:

Meitay-tec MTS-X500 Touch Screen Thermostat Product Specification Guide

Meitay-tec logo

Meitay-tec MTS-X500 Touch Screen Thermostat Owner Manual

Comments

Leave a Reply

Your email address will not be published. Required fields are marked *

To respond on your own website, enter the URL of your response which should contain a link to this post’s permalink URL. Your response will then appear (possibly after moderation) on this page. Want to update or remove your response? Update or delete your post and re-enter your post’s URL again. (Find out more about Webmentions.)