IEC-LOGO

IEC E055-71520325 Programmable Fan Coil Thermostat

IEC- E055-71520325- Programmable- Fan- Coil- Thermostat -PRO

Glossary of Terms

Front Panel

IEC- E055-71520325- Programmable- Fan- Coil- Thermostat -1

The Thermostat Backplate

To remove the thermostat backplate: Gently separate the display from the base by pulling from the centerIEC- E055-71520325- Programmable- Fan- Coil- Thermostat -2

IEC- E055-71520325- Programmable- Fan- Coil- Thermostat -3

Wiring Diagram

4-Pipe, Low Voltage Valves, Duct Temperature Sensor & Dry ContactIEC- E055-71520325- Programmable- Fan- Coil- Thermostat -4,

4-Pipe, Low Voltage Valves, Dehumidification Duct, Temperature Sensor and Dry Contact

IEC- E055-71520325- Programmable- Fan- Coil- Thermostat -5,

2-Pipe, Low Voltage Valves, H2O Changeover Sensor

IEC- E055-71520325- Programmable- Fan- Coil- Thermostat -6

Connect to Wi-Fi

Connect to Skyport
The steps below illustrate account creation from a browser. To create a Skyport account, a thermostat must be joined to the account. If the thermostat is connected to the local Wi-Fi Access Point, but you do not have a Skyport account, you may create an account and join the thermostat to the account by doing the following:

Join a Thermostat to Skyport
If the thermostat is connected to the local Wi-Fi access point but not yet joined to an existing Skyport account, you may join the thermostat to the account by doing the following:

Wi-Fi Status Screens
Press and hold the FAN button on the thermostat for 5 seconds. When “Wi-Fi Setup” appears on the display, press the MODE button. Pressing the UP or DOWN button will sequence through the following information:

Display LegendIEC- E055-71520325- Programmable- Fan- Coil- Thermostat -9

Basic Operation

Auto-Changeover Mode
Pressing the UP or DOWN buttons in AUTO mode will adjust both the heat and cool setpoints simultaneously. To adjust the heat and cool setpoints individually, choose HEAT mode to adjust the heat setpoint, and COOL mode to adjust the cool setpoint, then return to AUTO modeIEC- E055-71520325- Programmable- Fan- Coil- Thermostat -14

Heat or Cool Mode
Pressing the UP or DOWN buttons in HEAT or COOL mode will adjust only the heat or cool set temperature.IEC- E055-71520325- Programmable- Fan- Coil- Thermostat -15

Using the FAN Button
Pressing the FAN button will run the fan in low, medium, or high speed continuously. If the FAN is not on the display, then the fan is in AUTO mode and will run only when necessary to heat or cool

Using the FAN button for FAN OperationIEC- E055-71520325- Programmable- Fan- Coil- Thermostat -16

Using the FAN button for OVERRIDE Operation
Note: Override operation may ony be used when the thermostat is running a time period schedule/program.

Unoccupied Operation
During programmed, unoccupied periods pressing and holding the FAN button for more than 5 seconds will force the thermostat into occupied 1 settings for 1 to 4 hours (Setup Step #16, page 19). The OVERRIDE icon will be illuminated during this time. If you press and hold the FAN button while the thermostat is currently overriding the daily schedule, this will reset the timer, returning the thermostat to the correct time period program for the day.

Occupied Operation
Pressing and holding the FAN button for 5 seconds during a programmed Occupied time period will not function as override but will enter the wifi setup section.

User Setup

Table for button presses that are required for entering various menus

IEC- E055-71520325- Programmable- Fan- Coil- Thermostat -17

How to Change Settings in the Setup Screens
To enter the setup screens, press the MODE button, and simultaneously press FAN button for 5 seconds. Release the buttons when you see “Setup” on the display. Use the UP or DOWN buttons to adjust the value of your selection. Press MODE to advance to the next setup step. Press MODE and FAN together again to leave the setup screens.IEC- E055-71520325- Programmable- Fan- Coil- Thermostat -18

User Setup

Clock

Setting the Clock and Day (setup steps 1 & 2)
Note: When your thermostat is connected to Skyport Cloud Services, the time and day of the week are controlled by Skyport. There is no local adjustment, Skyport also adjusts the time for Daylight Savings Time as well. Setup steps 1 and 2 will not appear on thermostat if connected to Skyport. To set the time and day when not connected to Skyport; enter the setup screens by pressing the MODE button and simultaneously pressing the FAN button for 5 seconds.

Setup step 1 adjusts the clock.
Use the UP and DOWN buttons to adjust the time. Press the MODE button to advance to step 2. Select the day of the week using the UP and DOWN buttons. IEC- E055-71520325- Programmable- Fan- Coil- Thermostat -19 Leave the setup screens by again pressing the MODE button and simultaneously pressing the FAN button for 5 seconds.

IEC- E055-71520325- Programmable- Fan- Coil- Thermostat -20

Show Clock (setup step 3)
This setup step will allow for removal of the clock and day of the week from the display. OFF removes the time and day from the display.

 

IEC- E055-71520325- Programmable- Fan- Coil- Thermostat -21

Backlight Operation

Programmable (setup step 4)
When the very simplest operation is desired, this thermostat may be configured to be nonprogrammable, with or without Auto-Changeover.IEC- E055-71520325- Programmable- Fan- Coil- Thermostat -22
If “OFF” is selected, the thermostat will lockout the Program On screen; only the Off, Heat, Cool and Auto screens may be accessed by pressing the MODE button.IEC- E055-71520325- Programmable- Fan- Coil- Thermostat -23 Select “ON” if you would like your thermostat to be programmable, then the PROGRAM mode will be accessible through the use of the MODE button.

IEC- E055-71520325- Programmable- Fan- Coil- Thermostat -24

 

Backlight (setup steps 5-8)

Installer Setup: Pipe Settings

2 or 4 Pipe System (setup step 9)

Select Fan Coil System type:

2 Pipe System Operation (setup step 10)
Setup Step 10 only appears if Setup Step 9 = 2 pipe

IEC- E055-71520325- Programmable- Fan- Coil- Thermostat -24

Installer Setup: Deadband

Deadband
The Deadband is the number of degrees or minutes that the thermostat waits before it initiates the stages of heating or cooling.

1st Stage Deadband (setup step 11)
Specifies the temperature difference between the room temperature and the desired setpoint before the first stage of heating or cooling is allowed to turn on. (1 – 6 degrees) For example, if the heat setpoint is 68˚ and the 1st Stage deadband is set to 2 degrees, the room temperature will need to reach 66˚ before the heat turns on. For additional information on deadband, go to page 25.IEC- E055-71520325- Programmable- Fan- Coil- Thermostat -23

Minimum Heat/Cool Setpoint Difference (setup step 12)
This feature allows the user to set the minimum gap between Heat and Cool setpoints in AUTO mode. Select from 0 to 6 degreesIEC- E055-71520325- Programmable- Fan- Coil- Thermostat -23

Installer Setup: Setpoint Limits & Lock MODE

Setpoint Limits (setup step 13)
When this feature is set to ON, the Heat and Cool Setpoints may be restricted to preset levels in Setup Steps 14 and 15.IEC- E055-71520325- Programmable- Fan- Coil- Thermostat -24

Maximum Heat Setpoint (setup step 14)
IEC- E055-71520325- Programmable- Fan- Coil- Thermostat -25Minimum Cool Setpoint (setup step 15)IEC- E055-71520325- Programmable- Fan- Coil- Thermostat -26

Lock MODE Buttons
This feature is available when the thermostat is connected to Skyport Cloud Services and may only be accessed through Skyport. This security feature is not accessible locally at the thermostat. When this setting is enabled; pressing the MODE button on the thermostat will have no effect. This feature is often used in conjunction with setpoint limits.

Installer Setup

Dry Contact Operation

Dry Contact Polarity (setup step 25)

Dry Contact Use (setup step 26)

Locking/Unlocking the Keypad

To prevent unauthorized use of the thermostat, the front panel buttons may be disabled. To disable, or ‘lock’ the keypad, press and hold the MODE button. While holding the MODE button, press the UP and DOWN buttons together, for two secondsIEC- E055-71520325- Programmable- Fan- Coil- Thermostat -28

Programming a Daily Schedule

To enter Time Period Programming screens, Press and hold MODE and UP until the scrolling prompt appears. Press MODE to continue to next step.IEC- E055-71520325- Programmable- Fan- Coil- Thermostat -29

Adjust the Unoccupied Heat Setpoint – Press the UP or DOWN button to adjust the Heating setpoint for times when the thermostat is in Unoccupied.

The following steps determine when the Occupied period(s) will be active.

Upon pressing MODE after the above step; you will be prompted to Save and Exit or Copy this Occupied schedule to another day.

About Advanced Features & Operation

Operation: Calibration

Calibration
Under normal circumstances, it will not be necessary to adjust the calibration of the temperature sensor. If calibration is required, please contact a trained HVAC technician to correctly perform the following procedure.

Operation: Factory Defaults

Factory Defaults
If, for any reason, you desire to return all the stored settings back to the factory default settings, follow the instructions below.

WARNING: This will reset all Time Period and Advanced Programming to the default settings. Any information entered prior to this reset will be permanently lost

If, for any reason, you desire to return all the stored settings back to the factory default settings, follow the instructions below.

IEC- E055-71520325- Programmable- Fan- Coil- Thermostat -44

Advanced Setup Table

Step # Description Pg # Range FD
1

2

3

4

5

6

7

8

9

10

 

 

11

12

 

13

14

15

16

17

18

19

20

21

22

23

24

25

26

 

27

28

29

CLOCK WEEKDAY SHOW CLOCK PROG BACKLIGHT NIGHTLT NIGHTLT START NIGHTLT STOP

NUMBER OF WATER PIPES

2 PIPE SUBMODE

(only if prior step=2)

 

 

1ST STAGE DEADBAND MINIMUM HEAT/COOL SPREAD

(unless 2 pipe single mode)

SETPOINT LIMITS MAX HEAT SETPOINT MIN COOL SETPOINT

MAX OVRRIDE TIME IN HOURS DISPLAY F/C

CONTINUOUS FAN, ON (low) or OFF (auto) FAN TYPE, ON (IEC) or OFF

WIRED SENSOR TYPE CONTROL TO TEMP SOURCE PRE-OCC FAN PURGE TIME HOT WATER VALVE TYPE CHILLED WATER VALVE TYPE DRY CONTACT POLARITY DRY CONTACT USE

 

SKYPORT API

TIME API

 14

 14

 14

 15

 15

 15

 15

 15

 16

16

 

 

 17

17

 

 18

 18

 18

 19

 19

 19

 19

 19

 20

 20

 21

 21

 22

22

 

 23

 23

23

12A – 12A

Monday – Sunday On, Off

On, Off On, Off On, Off 12A – 12A

12A – 12A

4 PIPE, 2 PIPE

Heat only, Cool Only Auto Change, Total Elec Auto Change, Aux Heat Auto Change

 

1 – 6 degrees

0 – 6 degrees

 

On, Off

35 – 99 degrees

35 – 99 degrees

0 – 4 hrs F, C

On, Off On, Off

control, monitor thermostat, sensor off – 3 hrs

n.o / n.c.

n.o / n.c.

n.o / n.c.

occupied, condensate, fdd, holiday

On, Off On, Off On, Off

12P

Monday On

On Off Off 8:00P

6:00A

4 PIPE

Auto Change

 

 

2

2

 

Off 82

66

4

F

Off Off control

thermostat off

n.c.

n.c.

n.c. condensate

 

On Off Off

 

Terms and Conditions

International Environmental Corporation

Warranty

This warranty does not cover and does not apply to: (1) Air filters, fuses, fluids; (2) Products relocated after initial installation; (3) Any portion or component of any system that is not supplied by IEC, regardless of the cause of the failure of such portion or component; (4) Products on which the unit identification tags or labels have been removed or defaced; (5) Products on which payment to IEC is or has been in default; (6) Products which have defects or damage which result from improper installation, wiring, electrical imbalance characteristics or maintenance; or are caused by accident, misuse or abuse, fire, flood, alteration or misapplication of the product; (7) Products which have defects or damage which result from a contaminated or corrosive air or liquid supply or operation at abnormal temperatures; (8) Mold, fungus or bacteria damages; (9) Products subjected to corrosion or abrasion; (10) Products manufactured or supplied by others; (11) Products which have been subjected to misuse, negligence or accidents; (12) Products which have been operated in a manner contrary to IEC’s printed instructions; or (13) Products which have defects, damage or insufficient performance as a result of insufficient or incorrect system design or the improper application of IEC’s products. IEC is not responsible for: (1) The cost of any fluids or other system components, or associated labor to repair or replace the same, which is incurred as a result of a defective part covered by IEC’s Limited Express Warranty; (2) The costs of labor, materials or service incurred in removal of the defective part, or in obtaining and replacing the new or repaired part; or, (3) Transportation costs of the defective part from the installation site to IEC or of the return of any part not covered by IEC’s Limited Express.

Limitation

This Limited Express Warranty is given in lieu of all other warranties. If, notwithstanding the disclaimers contained herein, it is determined that other warranties exist, any such warranties, including without limitation any express warranties or any implied warranties of fitness for particular purpose and merchantability, shall be limited to the duration of the Limited Express Warranty.

Limitation of Remedies
In the event of a breach of the Limited Express Warranty, IEC will only be obligated at IEC’s option to repair the failed part or unit or to furnish a new or rebuilt part or unit in exchange for the part or unit which has failed. If after written notice to IEC’s factory in Oklahoma City, Oklahoma of each defect, malfunction or other failure and a reasonable number of attempts by IEC to correct the defect, malfunction or other failure and the remedy fails of its essential purpose, IEC shall refund the purchase price paid to IEC in exchange for the return of the sold good(s). Said refund shall be the maximum liability of IEC. THIS REMEDY IS THE SOLE AND EXCLUSIVE REMEDY OF THE BUYER OR THEIR PURCHASER AGAINST IEC FOR BREACH OF CONTRACT, FOR BREACH OF ANY WARRANTY OR FOR IEC’S NEGLIGENCE OR IN STRICT LIABILITY.

FCC

FCC Compliance Statement
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:

Notice: Only peripherals complying with FCC limits may be attached to this equipment. Operation with noncompliant peripherals or peripherals not recommended by IEC, is likely to result in interference to radio and TV reception. Changes or modifications to the product, not expressly approved by IEC could void the user’s authority to operate the equipment.

FCC – INDOOR Mobile Radio Information: To comply with FCC/IC RF exposure limits for general population / uncontrolled exposure, the antenna(s) used for this transmitter must be installed to provide a separation distance of at least 20 cm from all persons and must not be co-located or operating in conjunction with any other antenna or transmitter.

This Device complies with Industry Canada License-exempt RSS standard(s). Operation is subject to the following two conditions:

IEC

Reference

Download Manual:

IEC E055-71520325 Programmable Fan Coil Thermostat Owners Manual

OTHER MANUALS

IEC E055-71520325 Programmable Fan Coil Thermostat User Manual

IEC E055-71520325 Programmable Fan Coil Thermostat Product Specifications Guide

IEC-LOGO

IEC E055-71520325 Programmable Fan Coil Thermostat Owners Manual

Leave a Reply

Your email address will not be published. Required fields are marked *

To respond on your own website, enter the URL of your response which should contain a link to this post's permalink URL. Your response will then appear (possibly after moderation) on this page. Want to update or remove your response? Update or delete your post and re-enter your post's URL again. (Find out more about Webmentions.)