Emerson logo

EMERSON White-Rodgers 1F95-0671 Non-Programmable

EMERSON-White-Rodgers-1F95-0671-Non-Programmable 

APPLICATIONS

Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE.

Model Programming Choices
1F95-0671  

7 Day

 

5/1/1 Day

 

Non-Programmable

THERMOSTAT APPLICATION GUIDE

Description
Heat Pump (No Aux. or Emergency Heat) Yes
Heat Pump (with Aux. or Emergency Heat) Yes
Systems with up to 4 Stages Heat, 2 Stages Cool Yes
Heat Only Systems Yes
Millivolt Heat Only Systems – Floor or Wall Furnaces Yes
Cool Only Systems Yes
Gas or Oil Heat Yes
Electric Furnace Yes
Hydronic (Hot Water) Zone Heat – 2 Wires Yes
Hydronic (Hot Water) Zone Heat – 3 Wires Yes
Wired Remote Temperature Sensor (Indoor or Outdoor) Yes
Dual Fuel Feature (Heat Pump Mode, Outdoor Remote Required) Yes

SPECIFICATIONS

Electrical Rating:

CAUTION To prevent electrical shock and/or equipment damage, disconnect electric power to system at main fuse or circuit breaker box until installation is complete.
ATTENTION: MERCURY NOTICE
This product does not contain mercury. However, this product may replace a product that contains mercury.
Mercury and products containing mercury must not be discarded in household trash. Do not touch any spilled mercury. Wearing non-absorbent gloves, clean up any spilled mercury and place in a sealed container. For proper disposal of a product containing mercury or a sealed container of spilled mercury, place it in a suitable shipping container. Refer to www.thermostat-recycle.org for location to send product containing mercury.

INSTALLATION

WARNING Thermostat installation and all components of the control system shall conform to Class II circuits per the NEC code.

Remove Old Thermostat
Before removing wires from old thermostat, mark wires for terminal identification so the proper connections will be made to the new thermostat.

Installing New Thermostat

  1. Pull the thermostat body off the thermostat base. Forcing or prying on the thermostat will cause damage to the unit.
  2. Place base over hole in wall and mark mounting hole locations on wall using base as a template.
  3. Move base out of the way. Drill mounting holes. If you are using existing mounting holes and the holes drilled are too large and do not allow you to tighten base snugly, use plastic screw anchors to secure the base.
  4. Fasten base snugly to wall using mounting holes shown in Figure 1 and two mounting screws. Leveling is for appearance only and will not affect thermostat operation.
  5. Connect wires to terminal block on base using appropriate wiring schematic.
  6. Push excess wire into wall and plug hole with a fire resistant material (such as fiberglass insulation) to prevent drafts from affecting thermostat operation.
  7. Carefully line the thermostat up with the base and snap into place.

Battery Location

2 “AA” alkaline batteries are included in the thermostat at the factory with a battery tag to prevent power drainage. Remove the battery tag to engage the batteries.
To replace batteries, set system to OFF, remove thermostat from wall and install the batteries in the rear along the top of the thermostat (see Figure 1). For best results, use a premium brand “AA” alkaline battery such as Duracell® or Energizer®. If the home is going to be unoccupied for an extended period (over 3 months) and EMERSON-White-Rodgers-1F95-0671-Non-Programmable-1is displayed, the batteries should be replaced before leaving.

Power Stealing Switch
The Power Stealing Switches (Figure 1, rear view) should be left in the “On” position for most systems. The information in the following table details the thermostat power method and switch options.

Thermostat Power Method Switch Position/Description
Battery Powered, no 24 Volt system power available. Switches “On”, thermostat runs on batteries.
Hardwired with Battery Back-up, for 24 Volt systems with common connection from transformer to “C” terminal on thermostat. Switches “On”, thermostat runs on power directly from

transformer with battery back-up.

*Battery Powered with Power Stealing Assist, for 24 Volt systems with no common connection from transformer to “C” terminal on thermostat. Switches “On”, thermostat runs on batteries and supplemental power drawn through the heat or cool circuit.

Note: Power Stealing Assist is very reliable to increase battery life, but on a small number of heating or cooling systems with high-impedance electronic modules you may observe one of the following conditions:

  1. The furnace draft inducer motor may run with no call for heat.
  2. The furnace fan may turn on with no call for heat or may not turn off.
  3. The furnace may not turn off when the call for heat ends.
  4. The air conditioner may not turn off when the call for cool ends.

If the Power Stealing Assist method is not compatible with your system, place the Power Stealing Switches to “Off”. This cancels Power Stealing Assist, operates the thermostat on batteries and corrects the condition.EMERSON-White-Rodgers-1F95-0671-Non-Programmable-2

WIRING DIAGRAMS

Refer to equipment manufacturers’ instructions for specific system wiring information. After wiring, see the CONFIGURATION section for proper thermostat configuration. Wiring diagrams shown are for typical systems and describe the thermostat terminal functions.

TERMINAL DESIGNATION DESCRIPTIONS 

Single Stage and Multi-Stage Connections

Refer to equipment manufacturers’ instructions for specific system wiring information. This thermostat is designed to operate a single-transformer or two-transformer system.

You can configure the thermostat for use with the following systems:

Heat Pump Connections

Refer to equipment manufacturers’ instructions for specific system wiring information. This thermostat is designed to operate a single-transformer or two-transformer system. You can configure the thermostat for use with the following systems:

Home Screen DescriptionEMERSON-White-Rodgers-1F95-0671-Non-Programmable-7EMERSON-White-Rodgers-1F95-0671-Non-Programmable-8

Programming and Configuration Items

  1. “System On” indicates when heating or cooling stage is energized. “System On +2” indicates when additional stages are on.
  2. The word “Hold” is displayed when the thermostat is in the HOLD mode. “Temp” is displayed when the thermostat is in a Temporary HOLD mode.
  3. Displays “Change Filter” when the system has run for the programmed filter time period as a reminder to change or clean your filter.
  4. Displays “Set” for setpoint when in Run Program mode.
  5. Displays System Mode (Heat, Em, Auto, Cool, Off) or Time in menu mode.
  6. Displays Fan mode (On, Auto) “Prog FAN On” or “Run Sched” in Menu mode.
  7. Displays “Run Schedule”, “Schedule”, or “Menu”.
  8. Displays “Save” when Cool SavingsTM is working.
  9. Displays “Heat Pump” when system is configured as Heat Pump thermostat.
  10. Displays “Hold” in programmable mode when not in Hold mode. Displays Light Bulb in non-programmable mode.
  11. Initially displays “Auto Sched”. If Auto Schedule had been used or disabled, then it displays “Cool Savings” when in the Cool Mode. Displays “Copy” in Schedule mode and “Fan” in Fan Schedule mode.
  12. “Call For Service” indicates a diagnostic fault in the heating/cooling system, it does not indicate a fault in the thermostat.
  13. “Keypad Lockout” in Menu mode when selecting keypad Lockout or in RUN when a keypad Lockout is active.

INSTALLER/CONFIGURATION MENU

Thermostat must be in Heat, Cool or Auto. Press and hold the Menu button for at least 5 seconds. The display will show item #1 in the table below. Press EMERSON-White-Rodgers-1F95-0671-Non-Programmable-9Menu to advance to the next menu item. Press or to change a menu item options.

INSTALLER/CONFIGURATION MENU
Menu Ref. HP SS Press Button Displayed (Factory Default) Press  EMERSON-White-Rodgers-1F95-0671-Non-Programmable-9 to select from listed options Comments
1 1 1 MENU (MS 2) HP 1, HP 2, SS 1 Selects Multi-Stage (MS 2 No Heat Pump), Heat Pump 1 (HP 1, 1 compressor),

Heat Pump 2 (HP 2, 2 compressor or 2 speed compressor), or Single Stage (SS 1)

2 2 2 MENU (GAS) for SS or MS (ELE) for HP ELE GAS setting: furnace controls the blower ELE setting: thermostat controls the blower
3 3 3 MENU CS (3) 0, 1, 2, 4, 5, 6 Selects Cool Savings Value 1 (low) to 6 (high), Value 0 disables feature
4 4 4 MENU E (On) OFF Selects Energy Management Recovery (EMR) On or OFF.
5 5 MENU CR Heat (ME) SL, FA Selects Adjustable Anticipation, cycle rate, Heat (This item only appears when MS 2 or SS 1 is selected above)
6 5 MENU CR Heat Pump (ME) SL, FA Selects Adjustable Compressor Anticipation (Heat Pump) This item only appears when HP 1, HP 2 is selected above
7 6 6 MENU CR Cool (ME) or

CR AU (FA)

SL, FA SL Selects Adjustable Anticipation, cycle rate, cool (when MS 2 or SS 1 is selected above.) or Selects the cycle rate for Auxiliary stage (when HP 1 or HP 2 is selected above)
8 7 7 MENU CL (OFF) CL On Compressor Lockout Time
9 8 8 MENU Em Heat, Auto Cool Off

or

Heat, Auto,Cool Off

Heat Cool Off, Heat Off with Fan icon, Heat Off without Fan icon

Cool Off, Auto Off

System Mode Configuration

with Automatic Changeover capability

10 9 9 MENU dL (On) dL OFF Selects Display Light On or OFF
11 10 10 MENU 0

(current temperature)

1 HI, 2 HI, 3HI, 4 HI,

1 LO, 2 LO, 3 LO, 4 LO

Adjustable Ambient Temperature Display
12 11 11 MENU °F °C Selects Fahrenheit/Celsius Temperature Display
13 12 12 MENU (On) b OFF Select Beeper OFF to stop audible

key feedback (not applicable on all models)

14 13 13 MENU P (7) 3, 0 Defaults 7-day programming (P7) but non- programmable (0) or 5/1/1 programming (P3) is available on most models.
15 14 14 MENU PS (4) 2 Selects Program periods per day: 4 = Morn, Day, Eve, Night

2 = Day, Night

16 15 15 MENU Heat AS (On) OFF Automatic Schedule for heat mode
17 16 16 MENU Cool AS (On) OFF Automatic Schedule for cool mode
18 17 MENU Heat FA (On) OFF Fast Heat option may be disabled by selecting OFF. NA to SS or HP1 config.
19 18 MENU Cool FA (On) OFF Fast Cool option may be disabled by selecting OFF. NA to SS or HP1 config.
20 19 17 MENU Remote (OFF) On Selects Remote Sensor On/OFF
MENU Remote (In) Outdoor Selects Remote Sensor to outdoor NA is Remote Sensor OFF
MENU Indoor Loc (On) OFF Selects Local Sensor (in thermostat) to OFF. N/A if Remote is selected to Outdoor
21 20 18 MENU dS (On) Off Selects Automatic Daylight Saving Time option
22 21 19 MENU (OFF)

Keypad Lockout

L, P, Limit Selects one of 3 Keypad Lockout configurations L – Total Keypad Lockout

P – Partial Keypad Lockout (Up and Keys still work)

Limit – Limited Temperature Range

MENU (000)

Keypad Lockout

1-999 Selects personal lockout code. 000 is NOT A VALID CODE.
23 22 20 MENU L Heat (99) L 62 to L 98 Select Limited HEAT Range Temperature
24 23 21 MENU L Cool (45) L 46 to L 82 Select Limited COOL Range Temperature
25 24 MENU CO (05) 06-50 Selects outdoor Compressor OFF temperature (Balance Point temperature). 05 disables feature. Outdoor Remote required
MENU (dF) EA Selects between dF (dual Fuel) or EA (Electric Aux) only available if CO is greater than 05
MENU Cd (60) Selects Compressor delay OFF time in seconds (only if dF is selected)
26 25 MENU AO (80) Selects AO (Auxiliary OFF) temperature. Fea- ture disabled if 80 is selected. Outdoor Remote required
27 26 22 MENU Change Filter (OFF) On Selects Filter Change-out Indicator On or OFF.
MENU Change Filter (200 h) 25-1975 h Change Filter time in 25 hour increments. This menu only appears if On is selected in above.
28 27 23 MENU (OFF)

Change UV Lamp

On Selects UV Lamp Timer: On/OFF
MENU (350)

Change UV Lamp

25-1975 Selects number of Days between changing UV Lamp
29 28 24 MENU Cool On (o) Heat On (b) Selects operation of the reversing valve terminal (O/B) output as an O or B terminal
30 29 27 MENU RUN SCHED Returns to Normal Operation

OPERATING YOUR THERMOSTAT

Check Thermostat Operation

NOTE To prevent static discharge problems, touch side of thermostat to release static build-up before touching any keys.
If at any time during testing your system does not operate properly, contact a qualified service person.

Fan Operation
If your system does not have a G terminal connection, skip to Heating System.

  1. Turn on power to system.
  2. Press FAN button to select ON. The blower should begin to operate.
  3. Press FAN button to select AUTO. The blower should stop immediately.

CAUTION Do not allow the compressor to run unless the com-pressor oil heaters have been operational for 6 hours and the system has not been operational for at least 5 minutes.

Heating System

  1. Press SYSTEM button to select Heat. If the auxiliary heating system has a standing pilot, be sure to light it.
  2. PressEMERSON-White-Rodgers-1F95-0671-Non-Programmable-10to adjust thermostat setting to 1° above room temperature. The heat pump system should begin to oper-ate. The display should show “System On”. However, if the system configuration is set to HP1 or HP2 and setpoint temperature display is flashing, the 5 minute compressor lockout feature is operating (see Configuration menu, item 11).
  3. Adjust temperature setting to 3° above room temperature. If your system configuration is set at MS2, HP2 or HP1, the auxiliary heat system should begin to operate and the display will show “System On +2”.
  4. Press EMERSON-White-Rodgers-1F95-0671-Non-Programmable-11to adjust the thermostat below room temperature. The heating system should stop operating.

Emergency System

EM bypasses the Heat Pump to use the heat source wired to terminal W/E on the thermostat. EM is typically used when compressor operation is not desired, or you prefer backup heat only.

  1. Press SYSTEM button to select EM. “EM” will flash on the display.
  2. Press EMERSON-White-Rodgers-1F95-0671-Non-Programmable-10to adjust the thermostat setting above room temperature. The Emergency heating system will begin to operate. The display will show “System On” and flash “EM” to indicate that the Emergency system is operating.
  3. Press EMERSON-White-Rodgers-1F95-0671-Non-Programmable-11to adjust the thermostat below room temperature. The Emergency heating system should stop operating.

CAUTION To prevent compressor and/or property damage, if the outdoor temperature is below 50°F, DO NOT operate the cooling system.

Cooling System

  1. Press SYSTEM button to select Cool.
  2. PressEMERSON-White-Rodgers-1F95-0671-Non-Programmable-11to adjust thermostat setting below room temperature. The blower should come on immediately on high speed, followed by cold air circulation. The display should show “System On”. If the setpoint temperature display is flashing, the compressor lockout feature is operating (see Configuration menu, item 5).
  3. Adjust temperature setting to 3° below room temperature. The second stage cooling should begin to operate and the display should show “System On +2”.
  4. PressEMERSON-White-Rodgers-1F95-0671-Non-Programmable-10 to adjust the temperature setting above room temperature. The cooling system should stop operating.

Choose the Fan Setting (Auto or On)
Fan Auto is the most commonly selected setting and runs the fan only when the heating or cooling system is on.
Fan On selection runs the fan continuously for increased air circulation or to allow additional air cleaning.
Fan Prog On indicates that the fan is programmed to be on for the entire period. The Prog Fan On can be overridden
to have the fan cycle with the system. Press the FAN button to change the fan to Auto. The fan programming will be overridden until the next program period begins or until Run Schedule is pressed.

PROGRAMMING

Set Current Time and Day

  1. Press Menu button to enter installer menu. Then press Time button once to indicate hour & AM or PM designation in clock display.
  2. Press and hold either the EMERSON-White-Rodgers-1F95-0671-Non-Programmable-9button until you reach the correct hour and AM or PM designation.
  3. Press Time again to display minutes only in clock display.
  4. Press and hold either theEMERSON-White-Rodgers-1F95-0671-Non-Programmable-9 button until you reach the correct minutes.
  5. Press Time once again to display year.
  6. Press and hold either theEMERSON-White-Rodgers-1F95-0671-Non-Programmable-9button until you reach the correct year.
  7. Press Time once again to display month.
  8. Press and hold either theEMERSON-White-Rodgers-1F95-0671-Non-Programmable-9button until you reach the correct month.
  9. Press Time once again to display date of the month along with day of the week at top row (which is automatic).
  10. Press and hold either theEMERSON-White-Rodgers-1F95-0671-Non-Programmable-9button until you reach the correct day of the month and day of the week is automatically calculated and displayed at the top row.
  11. Press RunSched button once; now the display will show the correct time and room temperature.

PROGRAMMING

Energy Saving Factory Pre-Program
The 1F95-0671 thermostats are programmed with the energy saving settings shown in the table below for all days of the week. If this program suits your needs, simply set the thermostat clock and press the RunSched button. The table below shows the factory set heating and cooling schedule for all days of the week.

* Wake Up (Morn) Leave For Work (Day) * Return Home (Eve) Go To Bed (Night)
Heating Program 6:00 AM 70°F 8:00 AM 62°F 5:00 PM 70°F 10:00 PM 62°F
Cooling Program 6:00 AM 75°F 8:00 AM 83°F 5:00 PM 75°F 10:00 PM 78°F

Note: You can eliminate these two program periods in the configuration menu (reference #15) if the building is occupied all day. Day period will change to 6:00 AM and 70° and can be programmed as required.

Planning Your Program – Important
The Heating and Cooling Program schedules below allow you to pencil in your own program times and temperatures.
The 1F95-0671 comes configured for 7 day programming and can also be configured for 5+1+1 programming (see configura-tion section).
Factory settings are listed on Monday, Saturday and Sunday. If you are re-programming a 5+1+1 day schedule, pencil in your own times and temperatures directly below the factory times and temperatures.
If you are re-programming a 7 day schedule, fill in all lines with the times and temperatures you want. Keep the following guidelines in mind when planning your program.

Worksheet for Re-Programming 5+1+1 and 7 Day Program

Heating Program Wake Up (Morn)  

Fan

Leave For Work (Day)  

Fan

Return Home (Eve)  

Fan

Go To Bed (Night)  

Fan

 

MON

6:00 AM 70°F Auto 8:00 AM 62°F Auto 5:00 PM 70°F Auto 10:00 PM 62°F Auto
TUE
WED
THU
FRI
 

SAT

6:00 AM 70°F Auto 8:00 AM 62°F Auto 5:00 PM 70°F Auto 10:00 PM 62°F Auto
 

SUN

6:00 AM 70°F Auto 8:00 AM 62°F Auto 5:00 PM 70°F Auto 10:00 PM 62°F Auto
Cooling Program Wake Up (Morn)  

Fan

Leave For Work (Day)  

Fan

Return Home (Eve)  

Fan

Go To Bed (Night)  

Fan

 

MON

6:00 AM 75°F Auto 8:00 AM 83°F Auto 5:00 PM 75°F Auto 10:00 PM 78°F Auto
TUE
WED
THU
FRI
 

SAT

6:00 AM 75°F Auto 8:00 AM 83°F Auto 5:00 PM 75°F Auto 10:00 PM 78°F Auto
 

SUN

6:00 AM 75°F Auto 8:00 AM 83°F Auto 5:00 PM 75°F Auto 10:00 PM 78°F Auto

Automatic Daylight Saving Calculation

The Real Time Clock will adjust automatically for daylight savings time, in the following manner:
Increment one hour at 2 AM on the second Sunday of March and decrement one hour at 2 AM on the first Sunday of November. (New DST effective 2007).
The daylight saving feature can be enabled or disabled in installer configuration menu. Default is DS ON (enabled). After entering installer configuration mode, momentarily press MENU button until the display indicates dS (in actual temperature digits) and on (default – in clock digits). EMERSON-White-Rodgers-1F95-0671-Non-Programmable-9buttons will toggle display and operation from on to OFF.

Programming Tip: Copy Program
When programming your thermostat, you may copy the program from one day to another day or group of days using the Copy key. In 7 day programming mode, a day can be copied to another day or all six other days. In 5/1/1 day programming mode the weekday (Mon – Fri) program can be copied into Sat and Sun or either Sat or Sun.

To copy a program from one day to another:

  1. In Set Schedule mode, enter the program for the day or select the day you wish to copy by pressing Advance Day.
  2. Press Copy. On the display, “Copy” will begin to flash. The day of the week being copied will show.
  3. Press Advance Day. The day being copied will be indicated and the other days will be flashing.
  4. If you wish to copy to all days skip to next step or press Advance Day until the day you wish to copy to is flashing.
  5. Press Copy. “Copy” will be on, the day you copied from will disappear and the day(s) you copied to will be on.
  6. If you wish to copy this same program into other days, press Copy and repeat steps 2 through 5.
  7. Press RunSched to return to normal operation.

Fill in the blank schedule on the next page then:

Enter the Heating Program

  1. Press SYSTEM button to select Heat in the system switch area indicating the active mode being programmed.
  2. Press the Menu button and then press Schedule.
  3. The top of the display will show the day(s) being programmed. The first period to be programmed will appear. The set temperature will also be displayed and the time will be flashing to indicate that the time can be changed.
  4. Press EMERSON-White-Rodgers-1F95-0671-Non-Programmable-9 buttons to adjust the start time for the period. The time will change in 15 minute increments.
  5. Press the System Time button to change to the temperature flashing.
  6. PressEMERSON-White-Rodgers-1F95-0671-Non-Programmable-9buttons to change the temperature to your selected temperature for the first heating period.
  7. After you have set the time and temperature for the first period, press Schedule to advance to the next program period.
  8. Repeat steps 4 through 7 until all of the program times and temperatures are entered for all program periods for that day.
  9. Press Schedule button to change to the next day and repeat steps 4 through 8 until all program days and periods are entered.
  10. When programming is complete and all of the times and temperatures match your desired heating schedule, press RunSched. The thermostat will now run your program.

Enter the Cooling Program

  1. Press the SYSTEM button until the Cool icon appears.
  2. Follow Enter Heating Program instructions for entering cooling times and temperatures.

Automatic Schedule
This feature provides a method to program every day with the most popular time and temperature settings using one key. For this feature to be available, the Auto Schedule options (Installer/Configuration menu item 16, AS Heat, or item 17, AS Cool) must be selected On.
To use Auto Schedule, press RunSched to be sure you are in normal operating mode. In SYSTEM Heat mode, use the keys to select your “Comfort Temperature”. When your “Comfort
Temperature” is selected, press Auto Sched button. The Auto Schedule key will disappear to indicate that the Auto Schedule command has been accepted.
In Heat mode the thermostat will maintain your “Comfort Temperature” during the Morning, Day and Evening periods and setback 6° for the Night. Morning period will begin at 6:30 AM and Night period will begin at 10:30 PM.
To set the Auto Schedule temperature for Cool mode, press SYSTEM to change the mode to Cool and repeat setting the temperature. In Cool mode, the thermostat will maintain your selected “Comfort Temperature” continuously.
The “Comfort Temperature” can be temporarily overridden by changing the setpoint temperature using theEMERSON-White-Rodgers-1F95-0671-Non-Programmable-9 buttons. Once Auto Schedule has been set and the key has disappeared, it can be reset in the Installer/ Configuration menu.

Entering Fan Program
The fan can be programmed to turn on at the beginning of a period and remain on through the whole period. In RunSched mode when the FAN switch indicates Prog Fan On the fan is programmed to be on for the period.

  1. Press System button to select either Heat or Cool.
  2. Press Menu button and then press Fan button to the right of the display.
  3. The top of the display will show the day(s) being programmed. The first period to be programmed will appear.
  4. Press the Fan button to change from Auto to Prog.
  5. Press the Fan button to the right of the display to change to the next period.
  6. Repeat steps 4 and 5 to program the fan for all periods of the day.
  7. Press Fan to advance to the next day of the week and repeat steps 4 through 7 to program the fan for all days of the week.

Wired Remote Temperature Sensing

One remote temperature sensor can be installed indoor or outdoor and connected to the thermostat by a maximum cable length of 100 meters (300 feet). Terminals +, S and – on the terminal block allow connection of the remote sensor. The thermostat must have 24 VAC Common connection to terminal C for the remote sensor to operate. The remote sen-sor can be enabled or disabled in the Installer/Configuration menu, item 20.
When remote sensor, Remote, is selected Off (factory de-fault), no remote sensor is enabled. When remote sensor is selected On, the next step is to select the remote as indoor, Remote In, or outdoor, Remote Outdoor. If the remote is se-lected as Remote In, an additional step will be to select if the temperature shown on the display will be from the thermostat, Loc On, or the remote sensor Loc Off.
In normal operation, when a remote sensor is enabled the time digits of the display will alternate between the time and the remote temperature for three seconds each. Above the remote temperature will be “Remote”, for indoor sensor or “Outdoor Remote”, for outdoor sensor. If the remote sensor is an indoor sensor and the local display has been disabled, the temperature displayed as the room temperature will be the remote sensor temperature.

Sensing Range:

Weighing of Remote Reading:
The thermostat will weight or average the temperature of the indoor remote sensor with the local sensor in the thermostat for each program period. The averaging will be active only when the local sensor and the indoor remote sensor are both functional and enabled in the Installer/Configuration menu.
When the thermostat is in the Set Schedule mode, the weight of the indoor sensor will be shown in the current temperature digits of the display. The weight will show as A2 (average and default), H4 (high) or L1 (low). Pressing the EMERSON-White-Rodgers-1F95-0671-Non-Programmable-9 but-tons at the same time will change the weight for the program period. The weight of the thermostat sensor is fixed. In normal operation of the thermostat, the current tempera-ture displayed will be the weighted average of the local sensor and the remote sensor using the formula (local sensor weight x local sensor temperature) + (remote sensor weight x remote sensor temperature) / (local sensor weight + remote sensor weight).
Example: Local sensor temperature is 80° and the remote sensor is 70°.

The example shows that the weight selected would prioritize the overall averaged temperature between the two sensors. The high weight selection caused the remote sensor to have a higher influence in the calculated temperature average than the local sensor and the low weight selection caused the remote sensor to have less influence.

Dual Fuel Temperature Setpoint
When the thermostat is configured for Heat Pump mode and an outside remote sensor is installed and enabled, the thermostat can monitor the outside temperature to determine when to switch to auxiliary heat and shut down the compressor. This eliminates the need for a fossil fuel kit.
The Compressor Off temperature (CO) set in the configuration menu, item 25, will determine when the auxiliary heat will start and the compressor will shut off. The default setting is 05°F. -15°C (feature disabled) and can be set for 06 to 50°. When the outside temperature falls to the selected temperature, the auxiliary heat system will begin.
The auxiliary heat system can be fossil fuel (dF) or electric heat (EA). This is selected after CO is set greater than 05°. If the auxiliary heat is fossil fuel, (df), a delay time for the compressor shut down (Cd) can be selected. The default for this delay is 60 seconds but can be set from 0 to 99 seconds. If EA is selected, there is no selection for Cd because the compressor will shut down immediately.

TROUBLESHOOTING

Reset Operation
Note: When thermostat is reset, installer configuration menu settings and programming will reset to factory settings.
If a voltage spike or static discharge blanks out the display or causes erratic thermostat operation, you can reset the thermostat by removing the wires from terminals R and C (do not short them together) and removing batteries for 2 minutes. After resetting the thermostat, replace the wires and batteries. If the thermostat has been reset and still does not function correctly contact your heating/cooling service person or place of purchase.
Note: Be sure to review the installer configuration menu settings.
To reset the programming, clock and configuration settings, press the EMERSON-White-Rodgers-1F95-0671-Non-Programmable-9 and SYSTEM button simultaneously. The thermostat should go blank and then all segments will be displayed momentarily.

Symptom Possible Cause Corrective Action
No Heat/No Cool/No Fan (common problems) 1.  Blown fuse or tripped circuit breaker.

2.  Furnace power switch to OFF.

3.  Furnace blower compartment door or panel loose or not properly installed.

4.  Loose connection to thermostat or system.

Replace fuse or reset breaker. Turn switch to ON.

Replace door panel in proper position to engage safety interlock or door switch.

Tighten connections.

No Heat 1.  Pilot light not lit.

2.  Furnace Lock-Out Condition. Heat may also be intermittent.

 

 

3.  Heating system requires service or thermostat requires replacement.

Re-light pilot.

Many furnaces have safety devices that shut down when a lock-out condition occurs. If the heat works intermittently contact the furnace manufacturer or local HVAC service person for assistance.

Diagnostic: Set SYSTEM Switch to HEAT and raise the setpoint above room temperature. Within a few seconds the thermostat should make a soft click sound. This sound usually indicates the thermostat is operating properly. If the thermostat does not click, try the reset operation listed above. If the thermostat does not click after being reset contact your heating and cooling service person or place of purchase for a replacement. If the thermostat clicks, contact the furnace manufacturer or a HVAC service person to verify the heating is operating correctly.

No Cool 1. Cooling system requires service or thermostat requires replacement. Same as diagnostic for No Heat condition except set the thermostat to COOL and lower the setpoint below the room temperature. There may be up to a five minute delay before the thermostat clicks in Cooling.
Heat, Cool or Fan Runs Constantly 1.  Possible short in wiring.

2.  Possible short in thermostat.

3.  Possible short in heat/cool/fan system.

4.  FAN Switch set to Fan ON.

Check each wire connection to verify they are not shorted or touching together. No bare wire should stick out from under terminal block. Try resetting the thermostat as de- scribed above. If the condition persists the manufacturer of your system or service person can instruct you on how to test the Heat/Cool system for correct operation. If the system operates correctly, replace the thermostat.
Thermostat Setting & Thermostat Thermometer Disagree 1. Thermostat thermometer setting requires adjustment. The thermometer can be adjusted +/- 4 degrees. See Temperature Display Adjustment in the Configuration Menu section.
Furnace (Air Conditioner) Cycles Too Fast or Too Slow (narrow or wide temperature swing) 1. The location of the thermostat and/or the size of the Heating System may be influencing the cycle rate. Digital thermostats provide precise control and cycle faster than older mechanical models. The system turns on and off more frequently but runs for a shorter time so there is no increase in energy use. If you would like an increased cycle time, choose SL for slow cycle in the Configuration menu, step 7 (heat) or 8 (cool). If an ac-

ceptable cycle rate is not achieved, contact a local HVAC service person for additional suggestions.

Forgot Keypad Lockout Code Press the menu button (button will disappear) and hold in for 20 seconds. This unlocks the thermostat.

White-Rodgers is a business of Emerson Electric Co.
The Emerson logo is a trademark and service mark of Emerson Electric Co.
HELP LINE: 1-800-284-2925
www.white-rodgers.com
www.emersonclimate.com

Other manuals

EMERSON White-Rodgers 1F95-0671 Non-Programmable specification sheet

Download Manuals

EMERSON White-Rodgers 1F95-0671 Non-Programmable Installation and Operating Instructions

Emerson logo

EMERSON White-Rodgers 1F95-0671 Non-Programmable Installation and Operating Instructions

Leave a Reply

Your email address will not be published. Required fields are marked *

To respond on your own website, enter the URL of your response which should contain a link to this post's permalink URL. Your response will then appear (possibly after moderation) on this page. Want to update or remove your response? Update or delete your post and re-enter your post's URL again. (Find out more about Webmentions.)