Danfoss Icon2 RT Room Thermostat
Installation
Follow the illustrations in fig. 1 to 6 (dismantling, see fig. 7).
Note, fig. 3: Thermostats can be wired in either BUS or Star configuration, see Master Controller Installation Guide for more information.
Note, fig. 8: Optional floor sensor requires use of electrical conduit!
Touch and holdto access the Settings Menu. In the Settings Menu, touch and hold
to access the Installer Menu.
: Range limitation of setpoint for room temperature.
: Info/version number, can be used to identify the product.
: Perform Link Test of connection with Master Controller. Returns result as 0-100% (80% or higher is a very strong connection).
: Floor sensor mode:
= Comfort mode. Both air- and floor sensor is used.
= Floor sensor mode. The end user sets desired floor temperature.
= Dual mode. The thermostat controls a radiator and floor heating circuit(s). Floor heating circuits assure min. floor temperature and the radiator is used for peak load.
: Min. and max. temperature for the floor, used in and mode.
: Reference Room. Set to ON, if you want this thermostat to be the reference thermostat for switching between cooling and heating.
: Cooling ON/OFF. Use to turn of the ability to cool, e.g. bathrooms.