SIEMENS RDD310/EH Flush-mount Room Thermostat

SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Product-Specifications-PRODUCT

Key features

Key features of both types of thermostats:

Additional feature of RDE410/EH:

Use

RDD310/EH and RDE410/EH room thermostats are used to control the room temperature in…

Functions

Temperature control

The thermostat acquires the room temperature with its built-in sensor and maintains the setpoint by delivering control commands. The switching differential is 1 K.
Function diagram

SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Product-Specifications- (1)

Floor heating application

Operating modes

The operating mode is selected via the operating mode button SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Product-Specifications- (4). The respective setpoint maintains the room temperature at the desired level. The following operating modes are available:

Setpoints

Type summary

Product no. (ASN) Stock no. Features
RDD310/EH S55770-T296 Mains-powered AC 230 V
RDE410/EH S55770-T333 Mains-powered AC 230 V with Auto Timer
QAP1030/UFH S55770-S289 Cable temperature sensor NTC 3 k, cable length 4 m

Ordering
When ordering, please indicate the product no., stock no. and description. Example:

Product no. (ASN) Stock no. Description
RDD310/EH S55770-T296 Room thermostat

The cable temperature sensors, electric floor mat, valves and actuators must be ordered separately.

Equipment combinations

Description Product no. Data Sheet
Cable temperature sensor, cable length 4 m SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Product-Specifications- (8) QAP1030/UFH 1854
Electromotor actuators with On/Off valve (only available in AP, UAE, SA and IN) SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Product-Specifications- (9) MVI../MXI.. A6V11251892
Electromotor On/Off actuators SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Product-Specifications- (10) SFA21.. 4863
Thermal actuators (for radiator valves) SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Product-Specifications- (11) STA23.. 4884
Thermal actuators (for small valves 2.5 mm) SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Product-Specifications- (12) STP23.. 4884
Zone valve actuators (only available in AP, UAE, SA and IN) SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Product-Specifications- (13) SUA21.. 4830

Mechanical design

The room thermostat consists of 2 parts:

The base fits on the conduit box. The front panel slides in the mounting base and snaps on.

RDD310/EHSIEMENS-RDD310-EH-Flush-mount-room-thermostat-Product-Specifications- (14)

  1. Operating mode button/Frost Protection
  2. Button for adjustment of setpoint and control parameters

RDE410/EHSIEMENS-RDD310-EH-Flush-mount-room-thermostat-Product-Specifications- (15)

  1. Operating mode button
  2. Button for adjustment of setpoints, control parameters, and time of day
  3. Button for Auto Timer program
  4. Button for Frost Protection
  5. Button for setting the time of day and the weekday
  6. Button for confirmation

Display

The digital display shows the acquired room temperature or the setpoint for the current operating mode, selectable via parameter P06. The factory setting displays the current room temperature.

SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Product-Specifications- (16)

  1. Operating mode:
    • SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Product-Specifications- (5)Frost Protection
    • SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Product-Specifications- (6)AUTO Auto Timer
    • SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Product-Specifications- (2)Comfort
    • SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Product-Specifications- (3)Economy
  2. Room temperature, setpoints, and control parameters
    • SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Product-Specifications- (17)The symbol for display of the current room temperature
  3. SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Product-Specifications- (18)Heating On
  4. The current time of day *)
  5. Weekday 1…7 *)
    1 = Monday / 7 = Sunday
  6. Button lock active

Mounting and installation notes

Mount the room thermostat on a recessed rectangular conduit box. Do not mount it in niches or bookshelves, not behind curtains, not above or near heat sources, and not exposed to direct solar radiation. Mount it about 1.5 m above the floor.SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Product-Specifications- (19)

Wiring

See Mounting Instructions CB1M1440xx enclosed with the thermostat.

Commissioning notes

After power is applied, the thermostat carries out a reset during which all LCD segments flash, indicating that the reset was correctly made. After the reset, which takes about 3 seconds, the thermostat is ready for commissioning by qualified HVAC personnel. The control parameters of the thermostat can be set to ensure the optimum performance of the entire system (see below).

Control parameters

# Parameter Factory setting Setting range
Service level
P02 Selection of operating mode via the operating mode button 1 = Comfort – Frost Protection RDD310/EH: 1 = Comfort – Frost Protection
2 = Comfort – Economy – Frost Protection

RDE410/EH: 1 = Auto-Comfort – Frost Protection
2 = Auto – Comfort – Economy – Frost
Protection

P05 Temperature sensor calibration 0.0 °C –3…3 °C
P06 Standard temperature display 0 = Room temperature 0 = Room temperature 1 =Setpoint
P08 Comfort basic setpoint 20 °C 5…40 °C
P09 Min. setpoint limitation in Comfort mode (WminComf) 5 °C 5…40 °C
P10 Max. setpoint limitation in Comfort mode (WmaxComf) 35 °C 5…40 °C
P11 Heating setpoint in Economy mode 16 °C Off, 5…18 °C
P14 Button lock (press the operating mode button  for 3 seconds to lock or unlock) 0 = Disabled 0 = Disabled 1 =
Auto-lock
2 = Manual lock
Expert level
P30 Switching differential in heating mode 1 K 0.5…6 K
P38 External input 0 0 = No input

1 = External sensor input

P45 Heating system load in kW 2.8 kW 0…3.6 kW
P51 Floor heating temperature limit Off Off, 10…60 °C
P65 The setpoint of heating in Frost Protection modeSIEMENS-RDD310-EH-Flush-mount-room-thermostat-Product-Specifications- (5) (WheatStb) 8 °C Off, 5…18 °C
P69 Temporary setpoint in Comfort mode Off Off =       Disabled
On =       Enabled
P71 Reloading factory settings Set the value to “On” and confirm by pressing buttons + and – Off Off =       Idle
On =       Reset
Diagnostics and test
d02 Status X1 Diagnostics 0…xx °C = Measured temperature
d07 Software version information No adjustment Ux.x

Parameter settings

Parameter settings at service and expert levels:
The parameters are divided into “Service level” and “Expert level”. The parameter setting mode can be entered as follows: Set the thermostat to “Off/Frost Protection”SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Product-Specifications- (5).

Service level only (P02…P14)
Press buttons + and – simultaneously for 3 seconds. Release them and, within 2 seconds, press button + for 7 seconds. Parameters P02…P14 can now be adjusted (service level)

Expert level plus service level (all parameters P02…P71)
Press buttons + and – simultaneously for 3 seconds. Release them and, within 2 seconds, press the button – for 7 seconds. Parameters P02…P71 can now be adjusted (expert level)

In parameter setting mode, the parameters can be readjusted as follows:

  1. Select the required parameter by repeatedly pressing the button + or –.
  2. When pressing buttons + and – simultaneously, the current value of the selected parameter starts to flash; change it by repeatedly pressing button + or –.
  3. When you again press buttons + and – simultaneously, the next parameter is displayed.
  4. Repeat steps 1 to 3 to display and change additional parameters.
  5. At the service or expert level: 10 seconds after the last display or setting, all changes are stored and the thermostat will leave parameter setting mode. At the expert level: Press + or – until “End” is displayed. Then, press + and – simultaneously to save the change and exit parameter setting mode.

Disposal
The device is considered an electronic device for disposal in accordance with European Guidelines and may not be disposed of as domestic garbage.

Technical data

 Power  supply Operating voltage AC 230 V +10/-15%
Frequency 50/60 Hz
Power consumption Max. 4 VA
Outputs Control output Y1-N1 (NO)
Rating
AC 230 V

Max. 16 (8) A

External protection for incoming cable Circuit breaker

Circuit breaker tripping characteristic

 Max. 16 A

Type B, C, or D to EN 60898 and EN 60947

Inputs External sensor input (X1-M) Type
Temperature range
Cable length
 NTC 3 k

0…70 °C

Max. 80 m

Operating data Switching differential (adjustable)

Heating mode                                           (P30)

 

1 K (0.5…6 K)

Setpoint setting and range

SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Product-Specifications- (2)Comfort mode                                 (P08)

SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Product-Specifications- (3)Economy mode                               (P11)

SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Product-Specifications- (5)Frost Protection                               (P65)

 

20 °C (5…40 °C)

16 °C (Off, 5…18 °C)

8 °C (Off, 5…18 °C)

Floor temperature limitation setting range        (P51) Factory setting                                         (P38) Off and 10…60 °C

Off (limitation function not active)

Built-in room temperature sensor Measuring range

Accuracy at 25 °C

Temperature calibration range

0…49 °C

<±0.5 K

±3.0 K

Settings and display resolution Setpoints

Current temperature value displayed

0.5 °C

0.5 °C

Environmental conditions Operation

Climatic conditions Temperature

Humidity

As per IEC 60721-3-3

Class 3K5 0 …50 °C

< 95% r.h.

Transport

Climatic conditions Temperature Humidity

Mechanical conditions

As per IEC 60721-3-2

Class 2K3

– 25…60 °C

< 95% r.h.

Class 2M2

Storage
Climatic conditions
Temperature Humidity
As per IEC 60721-3-1
Class 1K3
– 25…60 °C < 95% r.h.
Standards and directives EU Conformity (CE) CE1T1440xx*)
RCM conformity CE1T1440en_C1*)
Protection class II as per EN 60730-1
Pollution class II as per EN 60730-1
Degree of protection of housing IP31 as per EN 60529
Environmental compatibility The product environmental declaration CE1E1440en*) contains data on environmentally compatible product design and assessments (RoHS compliance, materials composition, packaging, environmental benefit, disposal).
Eco-design and labeling directives Based on EU Regulation 813/2013 (Eco design directive) and 811/2013 (Labelling directive) concerning space heaters, and combination heaters, the following classes apply:
Application with On/Off operation of a heater Class, I           value 1%
General Connection terminals Solid wires 1 x 2.5 mm2
Weight 0.149 kg
Color of housing front RAL 9003 white

The documents can be downloaded from http://siemens.com/bt/download.
The documents can be downloaded from http://siemens.com/bt/download.

Connection diagrams

SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Product-Specifications- (20)

Application examples

SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Product-Specifications- (21)

Dimensions (mm)

SIEMENS-RDD310-EH-Flush-mount-room-thermostat-Product-Specifications- (22)

Remarks

Issued by:
Siemens Switzerland Ltd
Smart Infrastructure
Global Headquarters
Theilerstrasse 1a
CH-6300 Zug
Tel. +41 58 724 2424
www.siemens.com/buildingtechnologies
© Siemens Switzerland Ltd, 2013 – 2021 Technical specifications and availability are subject to change without notice.

Reference:

Download manuals:

SIEMENS RDD310EH Flush-mount room thermostat Product Specifications Guide

Other manuals:

SIEMENS RDD310/EH Flush-mount room thermostat Operating Instruction

SIEMENS-LOGO

SIEMENS RDD310/EH Flush-mount Room Thermostat Product Specifications Guide

Leave a Reply

Your email address will not be published. Required fields are marked *

To respond on your own website, enter the URL of your response which should contain a link to this post's permalink URL. Your response will then appear (possibly after moderation) on this page. Want to update or remove your response? Update or delete your post and re-enter your post's URL again. (Find out more about Webmentions.)