Z-Wave® Commissioning Notes

If the unit needs to be excluded from a network, put the Controller in Exclusion mode and press the button on SES 301 for more than 2 seconds. The Controller indicates when the process is completedSecure- SEC_SES301- Z-Wave- thermostat- 1

The device classes supported are given below.

Z-Wave Device Classes Implemented Device Class
Generic Multilevel sensor
Specific Routing Multilevel sensor
Basic Routing Slave
Command Classes Supported Description
Manufacturer Specific Secure Controls (UK) Manufacturer ID
Version Provides the version number of the software
Multilevel Sensor Supports Multilevel Sensor GET and Multilevel Sensor REPORT. The report carries the measured temperature as a 2-byte signed number (in °C or °F) with a precision of 1 decimal place. The report

can be requested (or sent unsolicited) to the nodes in Group 1.

Battery Level Supports GET and REPORT, for battery level in the range 0-100%. Low Battery Warning is reported (with parameter = 0xFF) to the nodes

in Group 2 if the battery voltage is less than 2.5 volts.

Wake Up(Ver 2) Wake Up Capabilities Report, supports wake up intervals in steps of 10s, with a default setting to 24 hrs, any received out of range wake up

interval will be ignored.

Basic Mapped to the Multilevel Sensor Command Class as follows:

o    Basic SET: Not Supported

o    Basic GET: Multilevel Sensor Get

o    Basic REPORT: Multilevel Sensor Report

Association Two association groups are supported:

Group 1 – Nodes to receive unsolicited multilevel sensor report. Group 2 – Nodes to receive unsolicited low battery warnings report. Each group contains a maximum of 4 nodes

Configuration Two single-byte configurations are supported for the temperature sensor functionality

1.     Configuration Parameter Number 1, temperature scale:

a.     0 to 127 (0x00-0x7F) = Celsius

b.     -128 to -1 (0x80-0xFF) = Fahrenheit

c.       Default value is 0

2.     Configuration Parameter Number 2, delta temperature:

a.     Can set in the range 1 to 100, in 0.1 degree steps

b.     Default value is 10 (1.0 ºC).

Technical Information

Technical Information
Dimensions (WxHxD) 86 x 86 x 30 mm Power supply 2 x AAA alkaline cells
Measurement accuracy ±0.5 °C Transmitter frequency 868 MHz
Pollution control degree 2 Design standard EN 60730-2-9
Enclosure protection IP30 Operating range 0 °C to +40 °C
Enclosure material Flame-retardant thermoplastic

Secure

REFERENCE

DOWNLOAD MANUAL

Secure SEC_SES301 Z-Wave thermostat User Manual

Other Manual:

Secure SEC_SES301 Z-Wave thermostat Installational Instruction

Secure

Secure SEC_SES301 Z-Wave thermostat User Manual

Leave a Reply

Your email address will not be published. Required fields are marked *

Your post must include a link to this post.

How does this work?
Write a response on your own website and include a link to this post. Then submit your response’s URL here. Your response may appear here after moderation. To update or remove it, edit or delete your original post and submit the same URL again. Learn more about Webmentions.