Vive -Comfort- TP-S-755- Non-Programmable- Thermostat- fea

Vive Comfort TP-S-855C Non-Programmable Thermostat Installation Manual

Vive-LOGO

Vive Comfort TP-S-855C Non-Programmable Thermostat 

Vive -Comfort- TP-S-755- Non-Programmable- Thermostat- pro

Vive Comfort
P.O. Box 3377
Springfield, MO 65808-3377
Toll Free : 888-776-1427
Web: www.vivecomfort.com
Hours of Operation: M-F 9AM – 6PM Eastern

Description
Gas or Oil Heat Yes
Electric Furnace Yes
Heat Pump (No Aux. or Emergency Heat) Yes
Heat Pump (With Aux. or Emergency Heat) Yes
Multi-Stage Systems Yes
Heat Only Systems Yes
Cool Only Systems Yes
Millivolt Yes
Wired Remote Sensing No
Any HVAC system up to 3H/2C with standard low voltage controlled humidifier. No
Any HVAC system up to 3H/2C with standard low voltage controlled de-humidifier. No

Power Type

  • Battery Power
  • Hardwire (Common Wire)
  • Hardwire (Common Wire) with
  • Battery Backup

A trained, experienced technician must install this product.
Carefully read these instructions. You could damage this product or cause a hazardous condition if you fail to follow these instructions.

Installation Tips

Wall Locations
The thermostat should be installed approximately 4 to 5 feet above the floor. Select an area with average temperature and good air circulation.Vive-Comfort-TP-S-855C-Non-Programmable-Thermostat 

Do not install thermostat in these locations:

  • Close to hot or cold air ducts
  • That are in direct sunlight
  • With an outside wall behind the thermostat
  • In areas that do not require conditioning
  • Where there are dead spots or drafts (in corners or behind doors)
  • Where there might be concealed chimneys or pipes

Installation Tip 
Pick an installation location that is easy for the user to access. The temperature of the location should be representative of the building.

Subbase Installation

Vive-Comfort-TP-S-855C-Non-Programmable-Thermostat-fig-1

  1. Horizontal Mount
    For horizontal mount put one screw on the left and one screw on the right.
  2. Vertical Mount
    For vertical mount put one screw on the top and one screw on the bottom.

Installation Tip: Electrical Hazard
Failure to disconnect the power before beginning to install this product can cause electrical shock or equipment damage.

Mercury Notice 
All of our products are mercury free. However, if the product you are replacing contains mercury, dispose of it properly. Your local waste management authority can give you instructions on recycling and proper disposal.

Mount ThermostatVive-Comfort-TP-S-855C-Non-Programmable-Thermostat-fig-2

Align the 4 tabs on the subbase with corresponding slots on the back of the thermostat, then push gently until the thermostat snaps in place.
Note: To ensure a solid fit between the thermostat and the subbase:

  1. Mount subbase to a flat wall
  2. Use screws provided
  3. Drywall anchors should be flush with the wall
  4. Wires should be pushed into the wall

Thermostat Quick Reference

Battery Installation

Battery installation is recommended even if the thermostat is hardwired (C terminal connected). When the thermostat is hardwired and batteries are installed, the thermostat will activate a compressor delay of 5 minutes when it detects a power outage from the hardwired power supply.Vive-Comfort-TP-S-855C-Non-Programmable-Thermostat-fig-3Important:
High quality alkaline batteries are recommended. Rechargeable batteries or low quality batteries do not guarantee a 1-year life span.

Vive-Comfort-TP-S-855C-Non-Programmable-Thermostat-fig-4

Getting to know your thermostat

Vive-Comfort-TP-S-855C-Non-Programmable-Thermostat-fig-5

  1. Displays the current room temperature
  2. Time and day of the week
  3. Low Battery Indicator: Replace batteries when this indicator is shown.
  4. Energy Efficient Globe:
  5. Keypad Lockout: Lock the thermostat
  6. Program Menu Options: Show different options during programming.
  7. Program Time Periods – Residential: Uses 4 time periods – WAKE, RETURN, LEAVE & SLEEP. Commercial: Uses 2 or 4 time periods that appear in the text field – Occupied & Unoccupied.
  8. Staging Indicators: +1 will appear in the display when second stage of heat or cool is on. +2 will appear for the third stage of heat.
  9. System Operation Indicators:
    If these or the Fan indicator are flashing, it means that the system is in a delay of some type (compressor delay, cooling fan delay, staging delay).
  10. Hold: is displayed when the thermostat program is permanently overridden.
  11. Setpoint: Displays the user selectable setpoint temperature.

Wiring

Caution: Electrical Hazard
Failure to disconnect the power before beginning to install this product can cause electrical shock or equipment damage.

Warning: All components of the control system and the thermostat installation must conform to Class II circuits per the NEC Code.

  1. If you are replacing a thermostat, make note of the terminal connections on the thermostat that is being replaced. In some cases the wiring connections will not be color coded. For example, the green wire may not be connected to the G terminal.
  2. Loosen the terminal block screws. Insert wires then retighten the terminal block screws.
  3. Place nonflammable insulation into the wall opening to prevent drafts.

Installation Tip 
Do not overtighten terminal block screws, as this can damage the terminal block. A damaged terminal block can keep the thermostat from fitting on the subbase correctly or cause system operation issues.
Max Torque = 6in-lbs.

Wiring Tips

C Terminal
The C (common wire) terminal does not have to be connected when the thermostat is powered by batteries.

Wire Specifications
Use shielded or non-shielded 18-22 gauge thermostat wire.

Note:
In many heat pump systems with no emergency heat relay, a jumper can be installed between E and W2 to turn thermostat into a single stage control for Emergency Heat Operation.

Terminal Designations

This thermostat is shipped from the factory to operate a conventional heating and cooling system. This thermostat may also be configured for a heat pump system. See the “heat pump” configuration step on page 17 of this manual to configure the thermostat for heat pump applications.

 

Terminal

2 Heat 2 Cool Conventional System 2 Heat 1 Cool Heat Pump System 3 Heat 2 Cool Heat Pump System
RC Transformer power (cooling) Transformer power (cooling) Transformer power (cooling)
RH Transformer power (heating) Transformer power (heating) Transformer power (heating)
C Transformer common Transformer common Transformer common
B Reversing valve

/ configerable terminal

Reversing valve

/ configerable terminal

Reversing valve

/ configerable terminal

O Reversing valve

/ configerable terminal

Reversing valve

/ configerable terminal

Reversing valve

/ configerable terminal

G Fan relay Fan relay Fan relay
W/E First stage of heat Emergency Heat First stage of auxiliary heat
Y First stage of cool First stage of heat & cool First stage of heat & cool
Y2 Second stage of cool N/A Second stage of heat & cool
W2 Second stage of heat Auxiliary heat Secodn stage of auxiliary heat
S1/S2 Remote Sensor Remote Sensor Remote Sensor
H Humidify Humidify Humidify
D Dehumidify Dehumidify Dehumidify

Getting to know your thermostat

Vive-Comfort-TP-S-855C-Non-Programmable-Thermostat-fig-6

  1. LCD Display
  2. Glow in the dark light button
  3. Setpoint buttons
  4. Program buttons
  5. Menu button
  6. Fan button
  7. System button
  8. Button/battery access door
  9. Battery cover

Important 
The low battery icon is displayed when the AA battery power is low. Whenever the thermostat detects low battery voltage from the AA batteries, the low battery icon will begin flashing on the screen ftor 21 days (if the batteries are not changed). If the batteries are not changed 22 days after the thermostat detects low battery voltage, the thermostat screen will only show the flashing battery icon until buttons are pressed. If the batteries are not changed 43 days after the thermostat detects low battery voltage, the thermostat screen will only show the flashing battery icon until buttons are pressed and the set points will offset to 85°F/29°C in cooling and 55°F/13°C in heating. At this stage, set point changes can be made temporarily but, the set points will change back to defaulted values after a 4-hour period. The thermostat will continue to perform this low battery flashing, temperature offset condition until the internal voltage threshold is reached. When the thermostat internal voltage threshold is reached, all relays will be opened and the thermostat will become inoperable until new batteries are installed.

About The Badge

All of our thermostats use the same universal magnetic badge. Visit the company website to learn more about our free private label program.

Vive-Comfort-TP-S-855C-Non-Programmable-Thermostat-fig-7

Gently slide a screwdriver into the bottom edge of the badge. Gently turn the screwdriver counter clockwise. The badge is held on by a magnet in the well of the battery door. The badge should pry off easily. DO NOT USE FORCE.

Wiring Diagrams

  1. Power supply
  2. Factory-installed jumper. Remove only when installing on 2-transformer systems
  3. Use either O or B terminals for changeover valve
  4. Optional 24 VAC common connection when thermostat is used in battery power mode
  5. If DEHUM relay requires a normally-energized input, set Dehumidify relay to NC in Technician Setup.

Typical 2H/2C System: 1 Transformer

Vive-Comfort-TP-S-855C-Non-Programmable-Thermostat-fig-8

Typical Heat Only System With Fan

Vive-Comfort-TP-S-855C-Non-Programmable-Thermostat-fig-9

Typical 2H/2C System: 2 TransformerVive-Comfort-TP-S-855C-Non-Programmable-Thermostat-fig-10

Typical 2H/1C Heat Pump SystemVive-Comfort-TP-S-855C-Non-Programmable-Thermostat-fig-11

Note: In many systems with no emergency heat relay a jumper can be installed between E and W2.

Technician Setup Menu

This thermostat has a technician setup menu for easy installer configuration. To set up the thermostat for your particular application:

  1. Press the MENU button.
  2. Press and hold the TECH SET button for 3 seconds. This 3 second delay is designed so that homeowners do not accidentally access the installer settings.
  3. Configure the installer options as desired using the table below. Use the Vive-Comfort-TP-S-855C-Non-Programmable-Thermostat-fig-12 keys to change settings and the NEXT or PREV key to move from one step to another.
    Note: Only press the DONE key when you want to exit the Technician Setup options.
  4. Press the DONE key to exit.
Tech Setup Steps LCD Will Show Adjustment Options Default
 

Filter Change Reminder

This feature will flash a reminder after the elapsed run time to remind the user to change the filter. A setting of “OFF” will disable this feature.
Tech Setup Steps LCD Will Show Adjustment Options Default
 

Filter Change Reminder

This feature will flash a reminder after the elapsed run time to remind the user to change the filter. A setting of “OFF” will disable this feature. OF

FILTER

You can adjust the filter change reminder from “OFF” to 2000 hours of runtime in 50 hour increments. OFF
 

Room Temperature Calibration

This feature allows the installer to change the calibration of the room temperature display. For example, if the thermostat reads 70˚ and you would like it to read 72˚ then select +2. 0

CALIBRATE

You can adjust the room temperature display to read up to 4˚above or below the factory calibrated reading. 0˚F
 

 

Cooling Swing

The swing setting often called “cycle rate”, “differential” or “anticipation” is adjustable. A smaller swing setting will cause more frequent cycles and a larger swing setting will cause fewer cycles.
Tech Setup Steps LCD Will Show Adjustment Options Default
 

Filter Change Reminder

This feature will flash a reminder after the elapsed run time to remind the user to change the filter. A setting of “OFF” will disable this feature. OF

FILTER

You can adjust the filter change reminder from “OFF” to 2000 hours of runtime in 50 hour increments. OFF
 

Room Temperature Calibration

This feature allows the installer to change the calibration of the room temperature display. For example, if the thermostat reads 70˚ and you would like it to read 72˚ then select +2. 0

CALIBRATE

You can adjust the room temperature display to read up to 4˚above or below the factory calibrated reading. 0˚F
 

 

Cooling Swing

The swing setting often called “cycle rate”, “differential” or “anticipation” is adjustable. A smaller swing setting will cause more frequent cycles and a larger swing setting will cause fewer cycles. 0.5

COOL SWING

The cooling swing setting is adjustable from 0.2˚ to 2˚. For example: A swing setting of 0.5˚ will turn the

cooling on at approximately 0.5˚ above the setpoint

and turn the cooling off at approximately 0.5˚ below the setpoint.

 

0.5˚

COOL SWING

The cooling swing setting is adjustable from 0.2˚ to 2˚. For example: A swing setting of 0.5˚ will turn the

cooling on at approximately 0.5˚ above the setpoint

and turn the cooling off at approximately 0.5˚ below the setpoint.

 

0.5˚

FILTER

You can adjust the filter change reminder from “OFF” to 2000 hours of runtime in 50 hour increments. OFF
 

Room Temperature Calibration

This feature allows the installer to change the calibration of the room temperature display. For example, if the thermostat reads 70˚ and you would like it to read 72˚ then select +2. 0

CALIBRATE

You can adjust the room temperature display to read up to 4˚above or below the factory calibrated reading. 0˚F
 

 

Cooling Swing

The swing setting often called “cycle rate”, “differential” or “anticipation” is adjustable. A smaller swing setting will cause more frequent cycles and a larger swing setting will cause fewer cycles. 0.5

COOL SWING

The cooling swing setting is adjustable from 0.2˚ to 2˚. For example: A swing setting of 0.5˚ will turn the

cooling on at approximately 0.5˚ above the setpoint

and turn the cooling off at approximately 0.5˚ below the setpoint.

 

0.5˚

Swing Setting Tip
The second stage will turn on at 2x the swing setting. The second stage will turn off when 1x the swing is reached. For example, if the swing setting is .5 degrees for heating and the thermostat is set at 70˚F, the first stage will turn on at approximately 69.5˚F. The second stage will turn on at 69˚F. The second stage will turn off at 69.5˚F and the first will turn off at 70.5˚F. If the third stage is used, it will turn on at 68.5˚F and turn off at approximately 69˚F.

Tech Setup Steps LCD Will Show Adjustment Options Default
Fresh Air Terminal

(Only displayed

if fresh air mode is turned ON. This setting cannot be used with PTAC, three stages of cool, or economizer turned on)

This setting provides the option to select a terminal for Fresh Air damper functions. The selected terminal cannot be used for reversing valve operations when the heat pump setting is turned on.  

0

FRESH AIR TRM

Use the        and       buttons to select O/B.  

O

 

Fresh Air Minutes

This setting selects the minimum number of minutes that the fresh air damper will be energized. 40

FRESH AIR MIN

Use the     and      buttons to select 5, 10, 15, 20, 25,

30, 35, 40, 45, 50, 55 or 60

minutes.

1
 

 

 

 

Program Options

You can configure this thermostat to have a 7 day program, a 5+1+1 program or No program.

Note: If 7d is selected, in set schedule you will program all seven days individually.

If 5d is selected, in set schedule you will program Monday – Friday together and Saturday and Sunday individually.

If 0d is selected the thermostat becomes non-programmable and the Set Schedule button goes away in Menu.

 

5d

 

PROGRAM

Use the and button to select 7d for 7 day, 5d for 5+1+1, or 0d for

non-programmable.

 

 

5d

 

 

Time Periods

(Only displayed if program optioin is set to 5d or 7d)

You can configure this thermostat to have 2 or 4 programmable time periods per day. 4

TIME PERIODS

Use the and buttons to select 4, 2C, or 4C time periods per day.

 

4: Wake, Leave, Return & Sleep.

2C: time periods are Occupied & Unoccupied.

4C: time periods are Occupied 1, Unoccupied 1, Occupied 2, &

Unoccupied 2

 

4

Tech Setup Steps  LCDWill Show  Adjustment Options     Default
 

 

Pro Recovery

This feature will start heating and cooling early to bring the building temperature to its programmed setpoint by the beginning of the WAKE, RETURN and OCCUPIED

time periods.

 

 

 

 

 

 

PRO RECOVERY

Use the         or select on or off. key to  

ON

 

Cycle Minimizer

(Only displayed if program optioin is set to 5d or 7d)

This setting maximizes efficiency and equipment longevity by increasing the heating and cooling swing settings to 2° during the unoccupied and leave time periods. This will result in significantly fewer system cycles. OF

CYCLE MIN

Use the         or select on or off. key to  

OFF

 

 

 

Keypad Lockout

Keypad lockout allows you to configure the thermostat so some or all of the keys don’t function.  

OF

 

KEY LOCKOUT

Use the       and        buttons to select OFF, BASC, PART, FULL

OF – OFF= keypad lock- out has been disabled.

BA – BASIC = basic keypad lockout locks the menu key. PA – PARTIAL= partial keypad lockout, which locks all the keys except the or setpoint keys.

FU – FULL= full keypad lockout, which locks out all the keys.

 

 

OFF

Heat Setpoint Limit This feature allows you to set a maximum heating setpoint limit. The setpoint temperature cannot be raised above this value. HE Use the     or        key to select the maximum heat setpoint and the minimum cooling setpoint. 90˚F
HEAT LIMIT

Keypad Lockout Note:
The selected keypad lockout functionality must be activated after exiting tech setup. If you do not perform this procedure, all keys will function freely. To lock the keypad hold down the Vive-Comfort-TP-S-855C-Non-Programmable-Thermostat-fig-12 keys for 3 seconds. You will see a lock in the display. To unlock the display hold down the Vive-Comfort-TP-S-855C-Non-Programmable-Thermostat-fig-12 keys for 3 seconds.

Tech Setup Steps LCD Will Show Adjustment Options Default
 

Stages of Cool

This setting allows you to select the number of cool stages. 2C

COOL STAGES

Use the     and      buttons to select 1C, 2C, 3C. 2C
 

 

System Set

You can configure the system switch for the particular application. Heat – Off – Cool, Heat – Off, Cool – Off, Heat – Off – Cool – Auto.

Note: If heat pump is selected on then the options will be Heat-off- cool-EM Heat or Heat-off- cool

 

 

 

 

SYSTEM SET

 

AutoOff Em.Heat

Cool

Use the      or         buttons until the desired application is flashing. AUTO = (Auto Changeover)  

OFF

Dual Fuel Auxiliary For Heat Pump This setting allows the system to run Gas, Oil, Propane or any

other types of auxiliary heat. The thermostat will default to electric auxiliary heat in heat pump applications.

OF

DUAL FUEL

Use the     and      buttons to select ON/OFF. OFF
 

 

Electric or Gas Fan Operation

Select GAS to have the system control the fan during a call for heat, select Electric to have the thermostat control the fan during a call for heat.

Note: If heat pump is set to “ON” this step will not show, and will default to ELECTRIC.

GAS

 

 

 

FAN SET

Use      and     buttons to change the setting.  

GAS

Satisfy Setpoint Staging

(Only displayed if there are more than one stage of

heat or cool)

This feature allows the thermostat to keep multiple stages of heat or cool energized until the setpoint is satisfied. OF

SS STAGING

Use the     or        buttons to turn on of off.  

OFF

Staging Delay

(Only displayed if there are more than one stage of

heat or cool)

This feature allows a delay to occur if an additional stage is needed. This allows the previous stage extra time to satisfy the setpoint.

Note: Will not show if using outdoor sensor with balance point temperature.

OF

STAGING DELAY

Use the        or         key to select OFF, 5, 10, 15, 30, 45,

60, or 90 minutes.

 

OFF

Tech Setup Steps LCD Will Show  Adjustment Options   Default
 

Minimum Compressor On Time

This feature allows the installer to select the minimum run time for the compressor. For

example, a setting of 4 will force the compressor to run for at least 4 minutes every time the

compressor turns on, regardless of the room temperature.

OF

MIN COMP ON

You can set the minimum compressor run time to “OFF”, “3”, “4”, or “5” minutes.

If 3, 4 or 5 is selected, the compressor will run for at least the selected time before turning off. Use the

and       buttons to change the setting.

 

OFF

 

Compressor Short Cycle Delay

The compressor short cycle delay protects the compressor from “short cycling”. This feature will not altlow the compressor to be turned on for 5 minutes after it was last turned off.  

 

 

 

 

 

COMP DELAY

Selecting “ON” will not allow the compressor to be turned on for 5 minutes after the last time the compressor was on. Select “OFF” to remove this delay. Use the        and buttons to change the setting.  

ON

 

 

Cooling Fan Delay

The cooling fan delay setting will delay the fan from coming on in cool mode and keep it running after the compressor shuts off for a short time to save energy in some systems. OF

COOL FAN DL

You can set the cooling fan delay to OFF, 15, 30, 60 or 90

seconds. If 15, 30, 60, or 90 is selected the fan will not

turn on for that many seconds when there is a call for cool and will run for that many seconds after satisfying a call for cool.

 

OFF

 

Fresh Air Mode

(This setting cannot be used with PTAC, three stages of cool, or economizer

turned on)

This feature allows fresh air into a unit for a selectable time period. When Fresh Air Mode is

enabled, the fan and the fresh air damper terminal will energize simultaneously.

 

OF

FRESH AIR

Use the       and       buttons to select OFF, OC ON or ON.

OFF: Thermostat does not enable Fresh Air Mode.

OC ON: Fresh Air Mode is enabled during the OCCUPIED, WAKE, RETURN, and SLEEP

time periods (It will not bring in fresh air during Unoccupied and Sleep time periods).

ON: Thermostat will enable Fresh Air Mode for every time periods.

 

OFF

 

Technician Setup Menu                                                           Technician Setup Menu
Tech Setup Steps                                  LCDWill Show  Adjustment Options     Default      Tech Setup Steps                      LCDWill Show  Adjustment Options     Default
Cool Setpoint Limit This feature allows you to set a minimum cooling setpoint limit. The setpoint temperature cannot be lowered below this value. CO

COOL LIMIT

Use the                  or                  key to select the minimum cooling setpoint. 44˚F  

 

 

Contractor Call Number

This feature allows you to put your phone number in the display. You can choose ON or OFF.

Notes:

If contractor call number is selected ON, the phone number entered will show in the display if there has been a continuous call for heating or cooling for 24 hours or if the light button is held down for 3 seconds. To remove the phone number from the display, hold the light button down for 3 seconds.

 

OF

 

PHONE NUMBER

If selected ON, you will see the input screen after pressing NEXT STEP. Use the

or                 button to select the desired number and the FAN or SYSTEM key to move from one character to another. See note below for operation.

 

 

OFF

 

˚F or ˚C

This feature allows you to display temperatures in either Fahrenheit or Celsius. oF

F OR C SET

˚F for Fahrenheit

˚C for Celsius

˚F
 

12 or 24 Hour Clock

You can select either a 12 or 24 hour clock setting. 12

CLOCK SET

Use the            or            key to select 12 or 24 hour clock. 12H
 

 

 

 

IAQ Mode Cycle

This feature will configure the fan to run a selected number of cycles per hour. Note: This mode can be enabled or disabled at anytime during normal operation by selecting IAQ mode with the fan key. Turning this feature on shows IAQ option in fan key.

Notes:

This programmable/selectable mode will operate the fan 1-4 cycles per hour, 1-45 minutes per cycle. Once programmed in tech setup, to enable this mode select “IAQ” with the fan key. Disable this mode by selecting “ON” or “AUTO” with the fan key.

 

OF

 

IAQ MODE CYCL

Select OFF, 1, 2, 3 or 4 with the or          buttons. This sets

the number of cycles per hour that the IAQ fan mode will operate.

 

 

OFF

 

 

Pre Occupancy Fan

The pre-occupancy fan settings will energize the fan before the occupied time to provide ventila- tion prior to scheduled occupancy time periods. This feature only shows if the technician setup step for time periods is set to 2C or 4C.

 

Use the                and                buttons to adjust.

OF

PRE-OCC FAN

You can select the

pre-occupancy fan from OFF, 1, 2, or 3 hours. If 1, 2, or 3 is selected, the fan will turn on that many hours prior to the scheduled occupied time period.

 

OFF

 

 

 

 

Display Light

The display light can be configured to stay on all the time or turn on when any key is pressed. There are LOW and

HIGH selections for continuous ON selection.

NOTE: The thermostat will need to be hardwired in order for the LOW and HIGH display light functions to work properly. “ALWAYS ON LIT” will alter- nate in the text field with “HARDWIRE ONLY” when HIGH is selected. These prompts will alternate every three seconds.

 

If the thermostat is hardwired this feature will default to LOW.

dL

ALWAYS ON LIT

 

 

 

 

 

 

dL

HARDWIRE ONLY

Use the                  and                  buttons to select OFF, LOW, or HIGH.

OFF configures the display light to come on when the light key or any button is pressed.

LOW configures the display light to stay on at a low intensity constantly. When a button is pressed, the display light will transition to high intensity.

HIGH configures the display light to remain on at high intensity all the time.

OFF

If Battery

Powered

 

 

 

 

 

 

LOW

If Hardwired

 

 

 

Contractor Call Number Note

If contractor call number is selected ON, the phone number entered will show in the display if there has been a continuous call for heating or cooling for 24 hours or if the light button is held down for 3 seconds. To remove the phone number from the display, hold the light button down for 3 seconds.

Tech Setup Steps LCD Will Show  Adjustment Options     Default
 

 

 

 

IAQ Minutes Per Cycle

This allows you to select the minimum number of minutes that the fan will run per IAQ mode cycle. The thermostat will keep track of fan runtime from normal heat and cool operation. If additional fan runtime is needed, the thermostat will run the fan to satisfy the IAQ mode minutes.

Notes: This programmable/selectable mode will operate the fan 1-4 cycles per hour, 1-45 minutes per cycle. Once programmed in tech setup, to enable this mode select “IAQ” with the fan key. Disable this mode by selecting “ON” or “AUTO” with the fan key.

 

1

 

IAQ MODE MIN

Select 1, 5, 10, 15, 20, 30 or

45 minutes.

When IAQ fan mode is enabled, it will ensure the fan runs at least the selected number of minutes per IAQ Mode Cycle.

This step will not appear if previous step is set to “OFF”.

 

 

1

 

 

UV Lamp Reminder

Enables a reminder for the user to change the UV light bulb. OFF

 

 

UV LAMP

Use the       or        key to select OFF, 1 YR, 2 YR  

OFF

 

IAQ Cell Reminder

Enables a reminder for the user to change the IAQ Cell after 25,000 hrs. OFF

 

IAQ CELL

Use the       or        buttons to select OFF, or 25 (stands for 25,000 hours).  

OFF

A Note about IAQ Mode
This programmable/selectable mode will operate the fan 1-4 cycles per hour, 1-45 minutes per cycle. Once programmed in tech setup, to enable this mode select “IAQ” with the fan key. Disable this mode by selecting “ON” or “AUTO” with the fan key.

Programming

Set Time Follow the steps below to set the day of the week and current time:

  1. Press the MENU button.
  2. Press SET TIME.
  3. Day of the week is flashing. Use the Vive-Comfort-TP-S-855C-Non-Programmable-Thermostat-fig-12key to select the current day of the week.
  4. Press NEXT.
  5. The current hour is flashing. Use the Vive-Comfort-TP-S-855C-Non-Programmable-Thermostat-fig-12key to select the current hour. When using 12-hour time, make sure the correct a.m. or p.m. choice is selected.
  6. Press NEXT.
  7. Minutes are now flashing. Use theVive-Comfort-TP-S-855C-Non-Programmable-Thermostat-fig-12key to select current minutes.
  8. Press DONE when completed.

All our programmable thermostats are shipped with an energy saving default program. You can customize this default program by following the instructions in the set program schedule section starting on page 24.
Your thermostat can be programmed to have each day of the week programmed uniquely (7 days), all the weekdays the same with a separate program for Saturday and a separate program for Sunday (5+1+1), or
non-programmable. For the 7-day and 5+1+1 programming modes, there are three time period options.

  1. “4” Residential (WAKE, LEAVE, RETURN, SLEEP)
  2. “2C” Commercial (OCCUPIED, UNOCCUPIED)
  3. “4C” Commercial (OCCUPIED 1, UNOCCUPIED 1, OCCUPIED 2, UNOCCUPIED 2)

This thermostat has a programmable fan feature, which allows you to run the fan continually during any time period.

Reminders

Once a reminder has been turned on and set, the elapsed time can be checked by navigating to its tech setup step. The elapsed time will then appear in the text field. It can also be reset at that time by holding down the set time/run sched button for 3 seconds. Resetting an expired reminder can be done without entering tech setup, by holding down the set time/run sched button for 3 seconds from the home screen.

Staging Delay Note: This step will not appear if using an outdoor balance point temperature.

To customize your 7 day 4 time period Program schedule, follow these steps:

Monday:

  1. Select HEAT or COOL with the SYSTEM key.
    Note: You have to program heat and cool each separately.
  2. Press the MENU button (If menu does not appear first, press RUN SCHED).
  3. Press SET SCHED.
    Note: Monday is displayed and the WAKE/OCC1 icon is shown. You are now programming the WAKE/OCC1 time period for that day.
  4. Time is flashing. Use the Vive-Comfort-TP-S-855C-Non-Programmable-Thermostat-fig-12 key to make your time selection for that day’s WAKE/OCC1 time period.
    Note: If you want the fan to run continuously during this time period, select ON with the FAN key. If you want to use IAQ mode during this time period, select IAQ with the FAN key.
  5. Press NEXT.
  6. The setpoint temperature is flashing. Use theVive-Comfort-TP-S-855C-Non-Programmable-Thermostat-fig-12 key to make your setpoint selection for that day’s WAKE/OCC1 period.
  7. Press NEXT.
  8. Repeat steps 4 through 7 for that day’s LEAVE/UNOCC1 time period, for that day’s RETURN/OCC2 time period, and for that day’s SLEEP/UNOCC2 time period.

Repeat steps 4 through 8 for the remaining days of the week.

A Note About Auto Changeover:
In Auto you have the ability to switch between Auto Heat or Auto Cool by pressing the system key. This can be done once the current mode has reached its setpoint. For example: if in Auto Heat, the heat setpoint must be satisfied before the thermostat will allow you to switch to Auto Cool. You can switch out of Auto by holding down the system key. To get back into Auto, you must toggle the system key to Auto.

Set Program Schedule For Two Time Periods (OCCUPIED, UNOCCUPIED)

To customize your 5+1+1 Program schedule, follow these steps:

Weekday:

  1. Select HEAT or COOL with the SYSTEM key.
    Note: You have to program heat and cool each separately.
  2. Press the MENU button (If menu does not appear first, press RUN SCHED).
  3. Press SET SCHED.
    Note: Monday-Friday is displayed and the OCCUPIED text is shown. You are now programming the OCCUPIED time period for that day.
  4. Time is flashing. Use theVive-Comfort-TP-S-855C-Non-Programmable-Thermostat-fig-12key to make your time selection for the weekday OCCUPIED time period.
    Note: If you want the fan to run continuously during this time period, select ON with the FAN key. If you want to use IAQ mode during this time period, select IAQ with the fan key.
  5. Press NEXT.
  6. The setpoint temperature is flashing. Use the or to make your setpoint selection for the weekday OCCUPIED period.
  7. Press NEXT.
  8. Repeat steps 4 through 7 for the weekday UNOCCUPIED time period.

Saturday:
Repeat steps 4 through 7 for the Saturday OCCUPIED time period and for the Saturday UNOCCUPIED time period.

Sunday: 
Repeat steps 4 through 7 for the Sunday OCCUPIED time period, and for the Sunday UNOCCUPIED time period.

Set Program Schedule For Four Time Periods

(WAKE, LEAVE, RETURN, SLEEP or OCCUPIED 1, UNOCCUPIED1, OCCUPIED 2, UNOCCUPIED 2)

To customize your 5+1+1 Program schedule, follow these steps:

Weekday:

  1. Select HEAT or COOL with the system switch.
    Note: You have to program heat and cool each separately.
  2. Press the MENU button (If menu does not appear first press RUN SCHED).
  3. Press SET SCHED.
    Note: Monday-Friday is displayed and the WAKE/OCC1 icon is shown. You are now programming the WAKE/OCC1 time period for the weekday setting.
  4. Time is flashing. Use the Vive-Comfort-TP-S-855C-Non-Programmable-Thermostat-fig-12 key to make your time selection for the weekday WAKE/OCC1 time period.
    Note: If you want the fan to run continuously during this time period, select ON with the FAN key. If you want to use IAQ mode during this time period, select IAQ with the FAN key.
  5. Press NEXT.
  6. The setpoint temperature is flashing. Use theVive-Comfort-TP-S-855C-Non-Programmable-Thermostat-fig-12 key to make your setpoint selection for the weekday WAKE/OCC1 period.
  7. Press NEXT.
  8. Repeat steps 4 through 7 for the weekday LEAVE/UNOCC1 time period, for the weekday RETURN/OCC2 time period, and for the weekday SLEEP/UNOCC2 time period.

Saturday: 
Repeat steps 4 through 7 for the Saturday WAKE/OCC1 time period, for the Saturday LEAVE/UNOCC1 time period, for the Saturday RETURN/OCC2 time period, and for the Saturday SLEEP/UNOCC2 time period.

Sunday: 
Repeat steps 4 through 7 for the Sunday WAKE/OCC1 time period, for the Sunday LEAVE/UNOCC1 time period, for the Sunday RETURN/OCC2 time period, and for the Sunday SLEEP/UNOCC2 time period.

Custom Program

Day of the Week Events Time Setpoint Temperature (HEAT) Setpoint Temperature (COOL)
 

 

 

Weekday

Wake/OCC1
Leave/UNOCC1
Return/OCC2
Sleep/UNOCC2
Occupied
Unoccupied
 

 

 

Saturday

Wake/OCC1
Leave/UNOCC1
Return/OCC2
Sleep/UNOCC2
Occupied
Unoccupied
 

 

 

Sunday

Wake/OCC1
LeaveUNOCC1
Return/OCC2
Sleep/UNOCC2
Occupied
Unoccupied

To customize your 7 day 2 time period program schedule, follow these steps:

Monday:

  1. Select HEAT or COOL with the SYSTEM key.
    Note: You have to program heat and cool each seperately.
  2. Press the MENU button (If menu does not appear first press RUN SCHED).
  3. Press SET SCHED.
    Note: Monday is displayed and the OCCUPIED text is shown. You are now programming the OCCUPIED time period for that day.
  4. Time is flashing. Use the Vive-Comfort-TP-S-855C-Non-Programmable-Thermostat-fig-12 key to make your time selection for that day’s OCCUPIED time period.
    Note: If you want the fan to run continuously during this time period, select ON with the FAN key. If you want to use IAQ mode during this time period, select IAQ with the fan key.
  5. Press NEXT.
  6. The setpoint temperature is flashing. Use the Vive-Comfort-TP-S-855C-Non-Programmable-Thermostat-fig-12 key to make your setpoint selection for that day’s OCCUPIED period.
  7. Press NEXT.
  8. Repeat steps 4 through 7 for that day’s UNOCCUPIED time period.

Repeat steps 4 through 8 for the remaining days of the week.

A Note About Programmable Fan:
The programmable fan feature will run the fan continuously during any time period it is programmed to be on. This is the best way to keep the air circulated and to eliminate hot and cold spots in your building. If using IAQ mode, set fan to IAQ for any time period.

Default Programming

Factory Default Program

Day of the Week Events Time Setpoint Temperature (HEAT) Setpoint Temperature (COOL)
 

 

 

Weekday

Wake/OCC1
Leave/UNOCC1
Return/OCC2
Sleep/UNOCC2
Occupied
Unoccupied
 

 

 

Saturday

Wake/OCC1
Leave/UNOCC1
Return/OCC2
Sleep/UNOCC2
Occupied
Unoccupied
 

 

 

Sunday

Wake/OCC1
LeaveUNOCC1
Return/OCC2
Sleep/UNOCC2
Occupied
Unoccupied

Factory Default Program for 2 Time Periods

Day of the Week Events Time Setpoint Temperature (HEAT) Setpoint Temperature (COOL)
 

Weekday

OCCUPIED 8 AM 70˚F (21˚C) 78˚F (26˚C)
UNOCCUPIED 6 PM 62˚F (17˚C) 83˚F (28˚C)
 

Saturday

OCCUPIED 8 AM 70˚F (21˚C) 78˚F (26˚C)
UNOCCUPIED 6 PM 62˚F (17˚C) 83˚F (28˚C)
 

Sunday

OCCUPIED 8 AM 70˚F (21˚C) 78˚F (26˚C)
UNOCCUPIED 6 PM 62˚F (17˚C) 83˚F (28˚C)

You can use the table on the next page to plan your customized program schedule if using 5+1+1.

Features

Filter Change & Other Reminders 
If the filter change reminder is enabled, you will see a reminder in the display when your air filter needs changed. The reminder will be shown in the display after your system has run long enough to require an air filter change.

Resetting The Filter Change Reminder:
When the reminder is displayed, you should change your air filter and reset the reminder by holding down the 3rd button from the left side of the thermostat for 3 seconds.Vive-Comfort-TP-S-855C-Non-Programmable-Thermostat-fig-13

This thermostat also has other maintenance reminders (Humidity Pad, UV lamp, and IAQ Cell), that are reset with the same procedure.

Temporary & Permanent Hold Feature

Temporary Hold: The thermostat will display HOLD and RUN SCHED on the bottom of the screen when you press the Vive-Comfort-TP-S-855C-Non-Programmable-Thermostat-fig-12key. If you do nothing, the temperature will remain at this setpoint temporarily for 4 hours. The program setpoint will then replace the temporary setpoint.

Permanent Hold: With a temporary hold set, If you press the HOLD key at the bottom of your screen, you will see HOLD appear below the setpoint temperature in the display. The thermostat will now permanently stay at this setpoint and can be adjusted using the Vive-Comfort-TP-S-855C-Non-Programmable-Thermostat-fig-12 keys.

To Return To Program: Press the RUN SCHED key at the bottom of the screen to exit temporary and permanent holds.

Specifications

  • The display range of temperature … 41˚F to 95˚F (5˚C to 35˚C)
  • The control range of temperature…. 44˚F to 90˚F (7˚C to 32˚C)
  • Load Rating……………………………………….. 1 amp per terminal, 1.5 amp maximum all terminals combined
  • Swing (cycle rate or differential) …… The heating is adjustable from 0.2˚ to 2.0˚
  • Cooling is adjustable from 0.2˚ to 2.0˚
  • Power source …………………………………….18 to 30 VAC, NEC Class II, 50/60 Hz for hardwire
  • Battery power from 2 AA Alkaline batteries
  • Operating ambient …………………………. 32˚F to +105˚F (0˚C to +41˚C)
  • Operating humidity ………………………… 90% non-condensing maximum
  • Dimensions of thermostat …………….. 4.7” W x 4.3” H x 0.9” D

Reference

Download Manual:

Vive Comfort TP-S-855C Non-Programmable Thermostat Installation Manual

OTHER MANUALS

Vive Comfort TP-S-855C Non-Programmable Thermostat Operational Manual

Vive-LOGO

Vive Comfort TP-S-855C Non-Programmable Thermostat Installation Manual

Comments

Leave a Reply

Your email address will not be published. Required fields are marked *

To respond on your own website, enter the URL of your response which should contain a link to this post’s permalink URL. Your response will then appear (possibly after moderation) on this page. Want to update or remove your response? Update or delete your post and re-enter your post’s URL again. (Find out more about Webmentions.)