Viconics VT7600 Programmable Thermostats
Product Overview
The VT7600 PI thermostat family is specifically designed for single-stage and multi-stage control of heating/cooling equipment such as rooftops and self-contained units. The product features an intuitive, menu-driven, back-lit LCD display, which walks users through the programming steps, making the process extremely simple. Accurate temperature control is achieved due to the product’s PI time proportional control algorithm, which virtually eliminates temperature offset associated with traditional, differential-based thermostats.
All models contain two digital inputs, which can be set by the user to monitor filter status, activate a remote temporary occupancy switch, and/or used as a general-purpose service indicator. In addition, depending on the model, up to three remote sensor inputs are available. All models contain an SPST auxiliary switch, which can be used to control lighting or disable the economizer function, and a discharge air sensor input. For more advanced applications, an economizer control logic has been integrated into the thermostat for use with proportional damper economizer actuators.
The thermostats are also compatible with the new Viconics PIR cover accessories. Thermostats equipped with a PIR cover provide advanced active occupancy logic, which will automatically switch occupancy levels from Occupied to Unoccupied as required by local activity being present or not. This advanced occupancy functionality provides advantageous energy savings during occupied hours without sacrificing occupant comfort.
All thermostats can be ordered with or without a factory-installed PIR cover ( see ordering notes below ).
- The additional following documentation is available on www.viconics.com – PIR application information and examples, are available on the document: APP-VT76-PIR-Guide-Exx
- PIR cover installation information is available in the document: PIR Cover Installation-Exx
- Information on the BACnet models (VT76xxX5x00B), is available on document ITG-VT76xx-PIR-BAC-Exx
- Information on the Wireless models (VT76xx0X5x00W), is available on documents: ITG-VWG-40-BAC-Exx and LIT-VWG-40-SETUP-Exx
Models available
Application | 1 Heat / 1 Cool | 2 Heat / 2 Cool | 2 Heat / 2 Cool with an economizer | 3 Heat / 2 Cool heat pump |
Model (programmable) | VT7652A5x00(X) | VT7652B5x00(X) | VT7656B5x00(X) | VT7652H5x00(X) |
Model (non-programmable) | VT7600A5x00(X) | VT7600B5x00(X) | VT7605B5x00(X) | VT7600H5x00(X) |
Ordering Information Notes:
- (X) model number represents available communication options: X=none for Stand-alone, X=B for BACnet MS-TP, X=E for Echelon and X=W for Wireless
- Thermostats can be ordered with a factory-installed PIR cover. Please use the (5500) extension instead of the (5000) only extension.: Ex. VT7600B5500E.
- Thermostats ordered without a PIR cover can be retrofitted with a separate PIR accessory cover afterward when required.
Features and Benefits
Features | Benefits |
Advanced occupancy functions | Through the network or smart local occupancy sensing |
Ready for PIR accessory cover | Fully integrated advanced occupancy functionality with a PIR accessory cover |
Ready for PIR accessory cover | Fully integrated advanced occupancy functionality with a PIR accessory cover |
2 digital inputs | Adds functionality |
Smart fan operation | saves energy during night mode |
Unique configuration key with password protection | Minimizes parameter tampering |
Lockable keypad | Tamper proof, no need for thermostat guards |
6 hour reserve time for the clock | No need to reprogram the day/time after the power shortage |
Auxiliary output | Can be used for lighting and/or economizer override |
Discharge air sensor | Can be used to monitor unit efficiency |
Intuitive, menu-driven programming (7-day, 2/4 events – on programmable models only) | Can be used for all types of establishments |
Economizer output 0-10 Vdc economizer models only | Excellent retrofit opportunities |
3 Heat/2 Cool (on heat pump models only) | Support single and two-stage heat pumps with one auxiliary heat stage |
Specifications
- Thermostat power requirements: 19-30 Vac 50 or 60 Hz; 2 VA ( RC & C ) Class 2
- RC to RH jumper 2.0 Amps 48 VA maximum
- Operating conditions: 0 °C to 50 °C ( 32 °F to 122 °F ) 0% to 95% R.H. non-condensing
- Storage conditions: -30 °C to 50 °C ( -22 °F to 122 °F ) 0% to 95% R.H. non-condensing
- Sensor: Local 10 K NTC thermistor
- Resolution: ± 0.1 °C ( ± 0.2 °F )
- Control accuracy: ± 0.5 ° C ( ± 0.9 °F ) @ 21 °C ( 70 °F ) typical calibrated
- Occupied and unoccupied setpoint range cooling: 12.0 to 37.5 °C ( 54 to 100 °F )
- Occupied and unoccupied setpoint range heating: 4.5 °C to 32 °C ( 40 °F to 90 °F )
- Room and outdoor air temperature range -40 °C to 50 °C ( -40 °F to 122 °F )
- Proportional band for room temperature control: Factory set, heating and cooling at: 1.1°C ( 2.0°F )
- Digital inputs: Relay dry contact only across C terminal to DI1 or DI2
- Contact output rating: Each relay output: ( Y1, Y2, G, W1, W2 & AU )
30 Vac, 1 Amp. maximum
30 Vac, 3 Amp. in-rush - Economizer analog output rating: 0 to 10 Vdc into 2KΩ resistance min.
- Economizer analog output accuracy: ± 3% typical
- Wire gauge 18 gauge maximum, 22 gauge recommended
- Dimensions: 4.94” x 3.38” x 1.13”
- Approximate shipping weight: 0.75 lb ( 0.34 kg )
- Agency Approvals all models: UL: UL 873 (US) and CSA C22.2 No. 24 (Canada), File E27734 with CCN XAPX (US) and XAPX7 (Canada)
- Industry Canada: ICES-003 (Canada)
- Agency Approvals all models FCC: Compliant to CFR 47, Part 15, Subpart B, Class A (US)
- CE: EMC Directive 89/336/EEC (Europe Union)
- C-Tick: AS/NZS CISPR 22 Compliant (Australia / New Zealand) Supplier Code Number N10696
- Agency Approvals Wireless models FCC: Compliant to Part 15, Subpart C
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES. OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS:
- THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE, AND
- THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED, INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION.
Drawing & Dimensions
Important notice
All VT7600 series controls are for use as operating controls only and are not safety devices. These instruments have undergone rigorous tests and verifications prior to shipment to ensure proper and reliable operation in the field. Whenever a control failure could lead to personal injury and/or loss of property, it becomes the responsibility of the user/installer / electrical system designer to incorporate safety devices ( such as relays, flow switch, thermal protections, etc…) and/or alarm system to protect the entire system against such catastrophic failures. Tampering of the devices or missing application of the device will void the warranty.