Viconics VT7200 Room Temperature Control Thermostat
SAFETY INFORMATION
Important Information
Read these instructions carefully and look at the equipment to become familiar with the device before trying to install, operate, service, or maintain it. The following special messages may appear throughout this bulletin or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
The addition of either symbol to a “Danger” or “Warning” safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
DANGER
DANGER indicates a hazardous situation that, if not avoided, will result in death or serious injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
CAUTION indicates a hazardous situation that, if not avoided, could result in minor or moderate injury.
NOTICE
NOTICE is used to address practices not related to physical injury. The safety alert symbol shall not be used with this signal word.
Please Note
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction, installation, and operation of electrical equipment and has received safety training to recognize and avoid the hazards involved.
BEFORE YOU BEGIN
Loss of Control
WARNING
- Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
- The designer of any control scheme must consider the potential failure modes of control paths and, for certain critical control functions, provide a means to achieve a safe state during and after a path failure. Examples of critical control functions are emergency stops and travel stops.
- Separate or redundant control paths must be provided for critical control functions.
- System control paths may include communication links. Consideration must be given to the implications of anticipated transmission delays or failures of the link.1
- Each implementation of equipment utilizing communication links must be individually and thoroughly tested for proper operation before being placed into service.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
California Proposition 65
WARNING
This product can expose you to chemicals including Lead and Bisphenol A (BPA), which are known to the State of California to cause cancer and birth defects or other reproductive harm.
For more information, go to www.P65Warnings.ca.gov.
Failure to follow these instructions can result in birth defects or other reproductive harm.
Electrostatic Discharge
NOTICE
STATIC SENSITIVE COMPONENTS
Circuit boards and option cards can be damaged by static electricity. Observe the electrostatic precautions below when handling controller circuit boards or testing components. Failure to follow these instructions can result in equipment damage.
Observe the following precautions for handling static-sensitive components:
- Keep static-producing materials such as plastic, upholstery, and carpeting out of the immediate work area.
- Store static-sensitive components in protective packaging when they are not installed in the drive.
- When handling a static-sensitive component, wear a conductive wrist strap connected to the component or drive through a minimum of 1 megohm resistance.
- Avoid touching exposed conductors and components lead to skin or clothing.
Installation
NOTICE
- The system must be installed correctly by a qualified technician.
- If replacing an existing Room Controller, label wires before removal of Controller.
- Electronic controls are static-sensitive devices. Discharge yourself correctly before manipulating and installing the Room Controller.
- A short circuit or wrong wiring may permanently damage the Room Controller or equipment.
- All Room Controllers are designed for use as operating controls only and are not safety devices. These instruments have undergone rigorous tests and verification prior to shipping to ensure proper and reliable operation in the field. Whenever a control failure could lead to personal injury and/or loss of property, it becomes the responsibility of the user/installer/electrical system designer to incorporate safety devices (such as relays, flow switch, thermal protections, etc.) and/or an alarm system to protect the entire system against such catastrophic failures. Tampering with the devices or unintended application of the devices will result in a void of warranty.
- This device must be installed to provide a separation distance of at least 8in (20cm) from all persons and must not be located or operating in conjunction with any other antenna or transmitter.
- Refer to the Room Controller User Interface Guide for information on how to configure the Room Controller.
Failure to follow these instructions can result in equipment damage.
Location
NOTICE
- Do not install it on an exterior wall.
- Do not install it behind a door.
- Do not install in areas with direct heat sources.
- Do not install near any air discharge grill.
- Do not install in areas exposed to direct sunlight.
- Ensure the Room Controller has sufficient natural air circulation.
- Ensure the wall surface is flat and clean.
- Ensure external thermal sensor wirings are away from noisy electrical sources.
- Install 1.3 to 1.5 meters (52 to 60 inches) above the floor.
- Perform preventive maintenance on the damper and Variable Air Volume (VAV) box, according to the supplier documentation.
Failure to follow these instructions can result in equipment damage.
Cleaning the Room Controller
NOTICE
- Use a soft, pre-moistened lint-free cloth for cleaning.
- Avoid getting moisture in openings.
- Do not spray anything directly on the Room Controller or use compressed air.
- Do not use caustic/corrosive products, ammonia, solvents or any cleaning product containing alcohol or grit.
- Never use tools directly on the touchscreen.
- Never use paint on the Room Controller.
- do not drop or crush the Room Controller, or allow it to come into contact with liquids.
- Do not use a damaged device (such as one with a cracked screen).
Failure to comply with these recommendations will result in damage to the unit and void the manufacturer’s warranty - Remove the security screw on the bottom of the Fan Coil Terminal Equipment Controller cover.
- Open the unit by pulling on the bottom side of the Fan Coil Terminal Equipment Controller (Fig. 1).
- Remove wiring terminals from the sticker.
- Please read the FCC ID and IC label installed in the cover upon removal of the cover for the wireless products.
Location
- Should not be installed on an outside wall.
- Must be installed away from any direct heat source.
- Should not be installed near an air discharge grill.
- Should not be affected by direct sun radiation.
- Nothing should restrict vertical air circulation to the Fan Coil Terminal Equipment Controller.
Installation
- Swing open the Fan Coil Terminal
- Equipment Controller PCB to the left by pressing the PCB locking tabs (Fig. 2). Pull out cables 6” out from the wall.
- Wall surface must be flat and clean.
- Insert cable in the central hole of the base.
- Align the base and mark the location of the two mounting holes on the wall. Install the proper side of the base.
- Install anchors in the wall.
- Insert screws in mounting holes on each side of the base (Fig. 2).
- Gently swing back the circuit board on the base and push on it until the tabs lock it.
- Strip each wire 1/4 inch from the end.
- Insert each wire according to the wiring diagram.
- Gently push excess wiring back into the hole (Fig. 3).
- Re-install wiring terminals in their correct locations (Fig. 3).
- Re-install the cover (top side first) and gently push the extra wire length back into the hole in the wall.
- Install security screw.
Anti-short cycling can be set to 0 minutes for equipment that possesses its own anti-cycling timer. Do not use that value unless the equipment is equipped with such an internal timer. Failure to do so can damage the equipment.
CONFIGURABLE BI/UI INPUTS OVERVIEW
Binary input #1 can be configured for the following functions:
- (None): No function will be associated with the input
- (Rem NSB): remote NSB timer clock input. The scheduling will now be set as per the binary input. It provides low-cost setback operation via a dry contact
- Contact opened = Occupied
- Contact closed = Unoccupied
- (Motion NO) and (Motion NC): Advanced PIR occupancy functions using a normally open (NO) or normally closed (NC) remote PIR motion sensor. Occupancy mode is now set as per the applied PIR function and configuration. Application information and examples are available on the document: APP-PIRGuide-Exx. This document will provide the installers and system designers with detailed examples of applications, parameter configuration information, sequence of operation, troubleshooting, and diagnostic help required for the proper usage of the PIR accessory covers
- (Window) EMS: Forces the system to disable any current heating or cooling action by the Terminal Equipment Controller. The mode stays the same and the current setpoints are the same occupied setpoints. Only the outputs are disabled. There is a Door/Window alarm displayed on the Terminal Equipment Controller to indicate to the local tenant that the door/window needs to be closed for cooling or heating to resume. Use NC contact.
- Contact opened = System disabled with local Window Alarm
- Contact closed = System enabled
Binary input #2 can be configured for the following functions:
- (None): No function will be associated with the input
- (Door Dry) Door contact and motion detector: This configuration is only functional if binary input #1 is set to Motion NO or Motion NC or a PIR accessory cover is used. With this sequence enabled, the occupancy is now dictated through those 2 inputs. Any motion detected will set the zone to occupied status. The zone will remain permanently in occupied mode until the door contact switch opens momentarily. The Terminal Equipment Controller will then go into stand-by mode. If more movements are detected, the occupied mode will resume. While the door is opened, any movements detected by the remote PIR sensor or the PIR accessory cover will be ignored. Use a Normally Closed-contact switching device.
- Contact opened = Door opened
- Contact closed = Door closed
- (RemOVR): temporary occupancy remote override contact. This function disables the central button override function on the Terminal Equipment Controller. The override function is now controlled by a manual remote momentarily closed contact. When configured in this mode, the input operates in a toggle mode. It is now possible to toggle between unoccupied & occupied setpoints for the amount of time set by the parameter (TOccTime) temporary occupancy time.
- (Filter): a backlit flashing Filter alarm will be displayed on the Terminal Equipment Controller LCD screen when the input is energized. It can be tied to a differential pressure switch that monitors filters
- Contact opened = No alarm
- Contact closed = Alarm displayed
- (Service): a backlit flashing Service alarm will be displayed on the Terminal Equipment Controller LCD screen when the input is energized. It can be tied into the AC unit control card, which provides an alarm in case of malfunction.
- Contact opened = No alarm
- Contact closed = Alarm displayed
Universal input #3 can be configured for the following functions:
- (None): No function will be associated with the input
- (COC/NH) Change over dry contact. Normally Heat: Used for hot/cold air/water change over switching in 2 pipe systems.
Contact closed = Cold air/water present
Contact opened = Hot air/water present
Only used and valid if the system is set up as 2.0. Parameter ( Out1Conf ) set as 2.0. - (COC/NC) Change over dry contact. Normally Cool: Used for hot/cold air/water change over switching in 2 pipe systems.
Contact closed = Hot air/water present
Contact opened = Cold air/water present
Only used and valid if the system is set up as 2.0. Parameter ( Out1Conf ) set as 2.0. - (COS) Change over analog sensor: Used for hot/cold air/water change over switching in 2 pipe systems.
Only used and valid if the system is set up as 2.0. Parameter ( Out1Conf ) set as 2.0.
If temperature is > 77 °F = Hot air / water present
If temperature is < 75 °F = Cold air / water present - (SS) Supply air sensor monitoring: Used for supply air temperature monitoring.
Only used for network reporting of the supply air temperature. Has no internal function in the Terminal Equipment Controller.
MODEL CHART
Network ready
- All Viconics VT7200 series Terminal Equipment Controllers are designed for stand-alone (network-ready) operation.
- They can be fully integrated into your choice of automation systems using the available communication adapter options.
- If required, stand-alone (network-ready) Terminal Equipment Controllers can be field retrofitted with the following communication adapters:
- VCM7000V5000W, Terminal Equipment Controller wireless communication adapter
- VCM7300V5000B, Terminal Equipment Controller BACnet™ MS-TP communication adapter
- VCM7300V5000E, Terminal Equipment Controller Lontalk™ communication adapter
TERMINAL, IDENTIFICATION AND FUNCTION
Terminal identification
Wiring
Power & Fan ( All models )
Auxiliary output ( All models )
Note:
If one or multiple sensor(s) is/are connected to the RS terminal, the internal temperature sensor is automatically disabled. Disconnecting the sensor(s) in RS terminal will reactivate the internal sensor.
Main outputs wiring
Typical applications
Remote sensor accessories
Model No. | Description |
---|---|
S3010W1000 | Wall-mounted temperature sensor |
S3020W1000 | Wall-mounted temperature sensor with override button and occupancy status LED |
S2060A1000 | Averaging temperature sensor |
S2000D1000 | Duct-mounted temperature sensor |
Remote mount temperature sensors use 10K type 2 NTC thermistors.
Features:
- Each sensor can be configured for various averaging combinations
- Optional occupancy led
- Optional override key
If one or multiple sensor(s) is/are connected into the RS terminal, the internal temperature sensor is automatically disabled. Disconnecting the sensor(s) in the RS terminal will reactivate the internal sensor.
Temperature vs. resistance chart for 10 Kohm NTC thermistor (R25°C = 10KΩ±3%, B25/85°C = 3975K±1.5%)
Status display
The VT7200 series wall-mount Terminal Equipment Controller features a two-line, eight-character display. There is a low-level backlight level that is always active and can only be seen at night.
When left unattended, the Terminal Equipment Controller has an auto-scrolling display that shows the actual status of the system. There is an option in the configuration menu to lock out the scrolling display and to only present the room temperature and conditional outdoor temperature to the user. With this option enabled, no local status is given of mode, occupancy, and relative humidity.
Each item is scrolled one by one with the backlighting in low-level mode. Pressing any key will cause the backlight to come on to a high level. When left unattended for 10 seconds after changes are made, the display will resume automatic status display scrolling.
To turn on the backlight to a high level, press any key on the front panel. The backlit display will return to a low level when the Terminal Equipment Controller is left unattended for 45 seconds.
Sequence of auto-scroll status display:
% RH display is conditional to:
(Humidity display is model and configuration dependent)
- A model with an RH sensor built-in
- Display function can be enabled with RH display parameter. Displayed range is
10 to 90 % RH
Outdoor air temperature
- The display is only enabled when the outdoor air temperature network variable is received.
Occupancy status
- Occupied, Stand-By, Unoccupied, and Override statuses are displayed on the scrolling display
Alarms
- If alarms are detected, they will automatically be displayed at the end of the scrolling status display.
- When an alarm message is displayed, the backlit screen will illuminate at the same time as the message and shut off during the rest of the status display.
- A maximum of two alarms can appear at any given time. The priority for the alarms is as follows:
Indication | Description |
---|---|
Service | Indicates that there is a service alarm as per one of the configured binary inputs (BI2). |
Filter | Indicates that the filters are dirty as per one of the configured binary inputs (BI2). |
Window | Indicates that the outside window or door is opened, and the Terminal Equipment Controller has canceled any cooling or heating action (BI1). |
Three status LEDs on the Terminal Equipment Controller cover are used to indicate the status of the fan (any speed), a call for heat, or a call for cooling.
Fan coil models
USER INTERFACE
Unoccupied mode override
An Override can be made on commercial models during an unoccupied period. If the Override option is enabled in the lockout configuration, by pressing the middle override the button will resume occupied setpoints for a time specified by the parameter “ToccTime”.
Local keypad interface
Any setpoint change can be permanent or temporary based on the configuration parameter (Setpoint Type)
- Any setpoint written through the network, will be permanent, and cancel any active temporary setpoints
- Lockouts of access to certain functions are made with configuration parameter (lockout)
Dual occupied setpoints adjustment
(Local occupied setpoint adjustment when “Stp Func” = Dual Stp)
- Heat/Cool setpoint toggle with MODE button to be active only in AUTO mode.
- If cooling, heating or off mode is active, a function is disabled.
Single-occupied setpoints adjustment
(Local occupied setpoint adjustment when “Stp Func” = Attach Stp )
Unoccupied and stand-by setpoint adjustments
The setting of the stand-by and unoccupied setpoints is done through the network or through configuration setup only.
Mode button menu sequence
Modes presented to the user are dependent on the sequence of operations selected.
The default mode is shown in bold when the sequence of operation parameters is changed.
The available mode can only be changed through the network since there is no local mode access
Sequence of operations
Sequence Number | Selected Mode |
---|---|
0 | Cooling Only (Off – Cool) |
1 | Heating Only (Off – Heat) |
2 | Cooling With Electric Reheat (Off – Auto – Heat – Cool) |
3 | Heating With Electric Reheat (Off – Heat) |
4 | Cooling and Heating (2 modulating outputs) (Off – Auto – Heat – Cool) |
5 | Cooling / Heating (2 modulating outputs) with reheat (Off – Auto – Heat – Cool) |
Available fan button menu sequences
Sequence Number | Fan Button Menu Configuration | Default Value When Sequence Toggled |
---|---|---|
0 | Low-Med-High 3 Speed configuration using 3 fan relays (L-M-H) | High |
1 | Low-High 2 Speed configuration using 2 fan relays (L-H) | High |
2 | Low-Med-High-Auto 3 Speed configuration with Auto fan speed mode using 3 fan relays (L-M-H-A) | High |
3 | Low-High-Auto 2 Speed configuration with Auto fan speed mode using 2 fan relays (L-H-A) | High |
4 | On-Auto Single Speed configuration. Auto is for Fan on demand / On is On all the time | Auto |
Auto-speed fan mode is also offered in heating mode applications; it will not have any effect on dehumidification. It will strictly be used for noise comfort issues.
Auto Speed Fan Mode operation for sequences 2 and 3 is dependent on the Auto Fan parameter. When Auto Fan is set to:
- AS (Default) = Auto Speed during occupied periods. The fan is always on during occupied periods. Low, medium, and high speeds operate on temperature offset from the set point.
- AS AD = Auto Speed / Auto Demand during occupied periods.
- Medium and high speeds operate on temperature offset from the set point. Low-speed operates on demand and will shut down when no demand is present.
INSTALLER CONFIGURATION PARAMETER MENU
Configuration can be done through the network or locally at the Terminal Equipment Controller.
- To enter the configuration, press and hold the middle button (°C/°F or Override) for 8 seconds.
- If a password lockout is active, “Password” is prompted. Enter the password value using the “up” and “down” arrows and press the middle button again to gain
access to all configuration properties of the Terminal Equipment Controller.
Entering the wrong password will prevent local access to the configuration menu. - Press the same middle button repetitively to scroll between all the available parameters.
- Use the up and down keys to change the parameter to the desired value.
- To acknowledge and save the new value, press the middle button again.
- The next parameter will now be displayed.
Configuration interface
USER KEY FUNCTIONS
SPECIFICATIONS
- Terminal Equipment Controller power requirements: 19-30 VAC 50 or 60 Hz; 2 VA Class 2
- Operating conditions:
- 0 °C to 50 °C ( 32 °F to 122 °F )
- 0% to 95% R.H. non-condensing
- Storage conditions:
- -30 °C to 50 °C ( -22 °F to 122 °F )
- 0% to 95% R.H. non-condensing
- Temperature sensor: Local 10 K NTC thermistor
- Temperate sensor resolution:± 0.1 °C ( ± 0.2 °F )
- Temperature control accuracy: ± 0.5 ° C ( ± 0.9 °F ) @ 21 °C ( 70 °F ) typical calibrated
- Humidity sensor and calibration: Single-point calibrated bulk polymer type sensor
- Humidity sensor precision: Reading ranges from 10-90% R.H. non-condensing
10 to 20% precision is 10%
20 to 80% precision is 5%
80 to90% precision is 10% - Humidity sensor stability: Less than 1.0% yearly (typical drift)
- Dehumidification setpoint range: 30 to 95% R.H.
- Contact output rating: Triac output: 30 VAC, 1 Amp.
- Maximum, 3 Amp. In-rush.
- Analog: 0 to 10 VDC into 2KΩ resistance min.
- Occ, Stand-By, and Unocc cooling setpoint range: 12.0 to 37.5 °C ( 54 to 100 °F )
- Occ, Stand-By, and Unocc heating setpoint range: 4.5 °C to 32 °C ( 40 °F to 90 °F )
- Room and outdoor air temperature display range: -40 °C to 50 °C ( -40 °F to 122 °F )
- Proportional band for room temperature control: Cooling & Heating: Default: 1.8°C ( 3.2°F )
- Binary inputs: Dry contact across terminal BI1, BI2 & UI3 to Scom
- Wire gauge: 18 gauge maximum, 22 gauge
- Approximate shipping weight: 0.75 lb ( 0.34 kg )
- Agency Approvals of all models: UL: UL 873 (US) and CSA C22.2 No.
- 24 (Canada), File E27734 with CCN
- XAPX (US) and XAPX7 (Canada)
- Industry Canada: ICES-003 (Canada)
- Agency Approvals of all models:
- FCC: Compliant to CFR 47, Part 15, Subpart B, Class A (US)
- CE: EMC Directive 89/336/EEC (Europe Union)
- C-Tick: AS/NZS CISPR 22 Compliant (Australia / New Zealand) Supplier
- Code Number N10696
- Agency Approvals Wireless models: FCC: Compliant to Part 15, Subpart C
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES. OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED, INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION.
Please check with your local government for instructions on the disposal of this product.
Please check with your local government for instructions on the disposal of this product.
Viconics Technologies Inc.
7262 Marconi Street
Montreal I Quebec I Canada I H2R 2Z5
Tel.: (514) 313-8885
Toll-free: 1 (800) 563-5660
[email protected]
www.viconics.com
DRAWING & DIMENSIONS
Reference Link
Download manual:
Viconics VT7200 Room Temperature Control Thermostat Installation Guide
Other manual:
Viconics VT7200 Room Temperature Control Thermostat Data Sheet
Viconics VT7200 Room Temperature Control Thermostat Installation Guide
Leave a Reply