verrdant-logo

Verdant VX Series Thermostat 

Verdant-VX-SERIES-Wireless-Thermostat-with-Occupancy-Sensor-PRODUCT

Thermostat Installation

BEFORE YOU BEGIN DETERMINE THE APPROPRIATE INSTALLATION LOCATION FOR THE THERMOSTAT. THE THERMOSTAT SHOULD FACE THE BED AREA OF THE ROOM. After the installation, follow the “Thermostat Configuration” Instructions to correctly configure the thermostat. For installation of a networking thermostat with remote management, refer to the “Network Installation” manual.

BEFORE YOU BEGIN

Consult PTAC manufacturer’s documentation or use a voltmeter to determine if the PTAC unit outputs AC or DC power (24V).
If the PTAC unit outputs AC power, make sure that the jumper on the Wireless Control Card is in the AC position – jumper is connecting “R” and “COM” pins (Default). If the PTAC unit outputs DC power, make sure that the jumper on the Wireless Control Card is in the DC position – jumper is connecting “COM” and “C” pins.

Installing the Wireless Control Card

Make sure that the Wireless Control Card antenna is not touching any metal components of the PTAC unit. Make sure that the contol card is not and cannot fall into the PTAC unit Condensation Pan.

Wiring Table – 24V AC

Wire Color Terminal Letter Terminal Connection
Black C Common
Red R 24V
Yellow Y Compressor
White W Heat
Orange O or B Reverse Valve
Green GH Fan High
Purple GL Fan Low

Wiring Table – 24V DC

Wire Color Terminal Letter Terminal Connection
Black R 24V
Red C Common
Yellow Y Compressor
White W Heat
Orange O or B Reverse Valve
Green GH Fan High
Purple GL Fan Low

Mounting the thermostat to the wall

Thermostat Configuration

Once the thermostat is powered, thermostat configuration settings will appear on the thermostat screen.

In order to properly operate the PTAC unit:

NOTE: You can access Thermostat Configuration settings by pressing the “Configuration” button. Use

NOTE: If the thermostat is connected to a network, the equipment settings configured on the thermostat will be ignored and the thermostat settings configured through the network will be applied.

Setting the thermostat clock

Verdant-VX-SERIES-Wireless-Thermostat-with-Occupancy-Sensor-FIG-2

Set the thermostat clock to current time.

Setting the clock correctly is crucial for proper operation of the thermostat.

Entering the room numberVerdant-VX-SERIES-Wireless-Thermostat-with-Occupancy-Sensor-FIG-3

Enter the room number by changing the digits on the screen. Leading zeros “0” preceding other digits will be ignored, i.e. Room number “123” should be entered as “00123”.

Entering room number correctly is crucial for proper operation of networked thermostats.

Configuring the Equipment Settings – Compressor TypeVerdant-VX-SERIES-Wireless-Thermostat-with-Occupancy-Sensor-FIG-43

Configuring the Equipment Settings – Electric HeatVerdant-VX-SERIES-Wireless-Thermostat-with-Occupancy-Sensor-FIG-44

Configuring the Equipment Settings – Reversing ValveVerdant-VX-SERIES-Wireless-Thermostat-with-Occupancy-Sensor-FIG-45

NOTE: If the thermostat is connected to a network, the equipment settings configured on the thermostat will be ignored and the thermostat settings configured through the network will be applied.

Configuring the Energy Saving SettingsVerdant-VX-SERIES-Wireless-Thermostat-with-Occupancy-Sensor-FIG-46

Refer to the APPENDIX 1 for Energy Saving Preset details.

Testing the thermostat

Following the thermostat configuration, test if the thermostat is controlling the PTAC unit.

Accessing the Thermostat Settings
Thermostat Settings allow customizing the energy savin settings. To access the thermostat settings:

FAN ENERGY SAVINGSVerdant-VX-SERIES-Wireless-Thermostat-with-Occupancy-Sensor-FIG-48

Turn Fan Energy Savings on or off:

1ST STAGE DIFFERENTIAL – HEATVerdant-VX-SERIES-Wireless-Thermostat-with-Occupancy-Sensor-FIG-49

2ND STAGE DIFFERENTIAL – HEATVerdant-VX-SERIES-Wireless-Thermostat-with-Occupancy-Sensor-FIG-50

1ST STAGE DIFFERENTIAL – COOLVerdant-VX-SERIES-Wireless-Thermostat-with-Occupancy-Sensor-FIG-5102-30 (0.2°F – 3.0°F; 0.5°F*) Select the difference between temperature setpoint and room temperature before 1st STAGE cooling is initiated.

INCIDENTAL OCCUPANCY THRESHOLDVerdant-VX-SERIES-Wireless-Thermostat-with-Occupancy-Sensor-FIG-52

00-60 (05*) Select the minimum period of time (in minutes) for which occupancy needs to be detected to enter guest occupancy mode. When occupancy is detected, the thermostat will switch to the occupied mode for a duration of the “Incidental Occupancy Threshold” selected here. If occupancy is detected for a period of time shorter than the “Incidental Occupancy Threshold” selected here, the thermostat will automatically revert to unoccupied mode at the end of the “Incidental Occupancy Threshold” period and continue to observe energy-saving functions that were in effect before the room became occupied. This setting allows ignoring incidental room visits .

NIGHT OCCUPANCY THRESHOLDVerdant-VX-SERIES-Wireless-Thermostat-with-Occupancy-Sensor-FIG-53

00-60 (01*) Select the minimum period of time (in minutes) for which occupancy needs to be detected in order to consider the room occupied during the “Night Occupancy”period. When occupancy is detected while room is considered unoccupied during the “Night Occupancy” period, the thermostat will instantaneously switch to occupied mode for a duration of “Night Occupancy Threshold” selected here. If occupancy is detected for a period of time shorter than the “Night Occupancy Threshold” selected here, the thermostat will automatically revert to unoccupied mode and continue to observe energy saving functions that were in effect before the room became occupied. If occupancy is detected for a period of time longer than the “Night Occupancy Threshold” selected here, the thermostat will disable the occupancy sensor and consider the room occupied until the end of the “Night Occupancy” period. This feature ensures that energy saving functions that may affect guest comfort will not come in effect during the “Night Occupancy” period.

FORCED 2ND STAGE HEATINGVerdant-VX-SERIES-Wireless-Thermostat-with-Occupancy-Sensor-FIG-54

00-60 (30*) Select a number of minutes 1st STAGE heating will run before 2nd STAGE heating is automatically initiated if the temperature setpoint is not reached and the 2nd STAGE heating is not initiated through differential settings. This feature allows automatically turning on 2nd STAGE heating to avoid excessive compressor use. Set to 00 to disable the feature.

NIGHT OCCUPANCY STARTVerdant-VX-SERIES-Wireless-Thermostat-with-Occupancy-Sensor-FIG-55

00-23 (21*) Select the start time (in hours – 24-hour clock) for “Night Occupancy” If occupancy is detected for a period of time longer than the “Night Occupancy Threshold” during “Night Occupancy” period, the thermostat will disable the occupancy sensor and consider the room occupied until the end of the “Night Occupancy” period. This feature ensures that energy saving functions that may affect guest comfort will not come in effect during the “Night Occupancy” period if room was occupied for a period of time longer than “Night Occupancy Threshold”.

NIGHT OCCUPANCY ENDVerdant-VX-SERIES-Wireless-Thermostat-with-Occupancy-Sensor-FIG-56

00-23 (09*) Select the end time (in hours – 24-hour clock) for “Night Occupancy” If occupancy is detected for a period of time longer than the “Night Occupancy Threshold” during “Night Occupancy” period, the thermostat will disable the occupancy sensor and consider the room occupied until the end of the “Night Occupancy” period. This feature ensures that energy saving functions that may affect guest comfort will not come in effect during the “Night Occupancy” period if room was occupied for a period of time longer than “Night Occupancy Threshold”.

TEMPERATURE RECOVERY TIMEVerdant-VX-SERIES-Wireless-Thermostat-with-Occupancy-Sensor-FIG-5700-60 (25*) Select the maximum time allowed for a PTAC unit to attain temperature as defined by Heat and Cool “Recovery Temperature”; “Temperature Recovery Time” selected here and the actual efficiency of the PTAC unit are used to calculate setback temperatures. Calculated setback temperatures maximize energy savings and at the same time ensure that a comfortable room temperature (defined as Heat and Cool “Recovery Temperature”) will be restored within the selected “Temperature Recovery Time”. Setting the “Temperature Recovery Time” to “00”, disables temperature recovery. When temperature recovery is disabled, thermostat will use the Minimum and Maximum Setback Temperatures as setback setpoints.

RECOVERY TEMPERATURE – HEATVerdant-VX-SERIES-Wireless-Thermostat-with-Occupancy-Sensor-FIG-5862-82 (66°F) Select the room temperature in °F that a PTAC unit will have to attain within the selected “Temperature Recovery Time” when there is a need for heating.

TEMPERATURE SETBACK DELAY – HEATVerdant-VX-SERIES-Wireless-Thermostat-with-Occupancy-Sensor-FIG-5900-120 (20*) Select the time delay (in minutes) before the thermostat will initiate the temperature setback and allow the room temperature to drop to the setback temperature after the room becomes unoccupied. This feature prevents initiating temperature setback prematurely while the guest is still in the room but in an area where occupancy cannot be detected by the occupancy sensor. Setting the “Temperature Setback Delay – Heat” to “00”, disables the setback in the heat mode. Set to “00” to disable EMS.

MINIMUM SETBACK TEMPERATUREVerdant-VX-SERIES-Wireless-Thermostat-with-Occupancy-Sensor-FIG-6052-72 (64°F) Select the “Minimum Setback Temperature” in °F. Setback temperature is calculated by measuring PTAC unit’s ability to attain “Recovery Temperature – Heat” within “Temperature Recovery Time”. If recovery is disabled (“Temperature Recovery Time” is set to “0”) or if setback temperatures have not yet been calculated, the “Minimum Setback Temperature” value will be used as the setback temperature for heating. If calculated setback temperature for heating is lower than “Minimum Setback Temperature”, then the “Minimum Setback Temperature” will be used as setback temperature for heating. This feature allows defining the minimum temperature in a room when room is unoccupied and the thermostat is in the setback mode.

TEMPERATURE SETBACK DELAY – COOLVerdant-VX-SERIES-Wireless-Thermostat-with-Occupancy-Sensor-FIG-6100-120 (20*) Select the time delay (in minutes) before the thermostat will initiate the temperature setback and allow the room temperature to raise to the setback temperature after the room becomes unoccupied This feature prevents initiating temperature setback prematurely while the guest is still in the room but in an area where occupancy cannot be detected by the occupancy sensor. Setting the “Temperature Setback Delay – Cool” to “00”, disables the setback in the cool mode. Set to “00” to disable EMS.

MAXIMUM SETBACK TEMPERATUREVerdant-VX-SERIES-Wireless-Thermostat-with-Occupancy-Sensor-FIG-62

72-92 (78°F) Select the “Maximum Setback Temperature” in °F. Setback temperature is calculated by measuring PTAC unit’s ability to attain “Recovery Temperature – Cool” within “Temperature Recovery Time”. If recovery is disabled (“Temperature Recovery Time” is set to “0”) or if setback temperatures have not yet been calculated, the “Maximum Setback Temperature” value will be used as the setback temperature for cooling. If calculated setback temperature for air conditioning is higher than the “Maximum Setback Temperature”, then the “Maximum Setback Temperature” will be used as setback temperature for air conditioning. This feature allows for defining the maximum temperature in a room when the room is unoccupied and the thermostat is in setback mode.

RECOVERY TEMPERATURE – COOLVerdant-VX-SERIES-Wireless-Thermostat-with-Occupancy-Sensor-FIG-63

62-82 (75°F) Select the room temperature in °F that a PTAC unit will have to attain within the selected “Temperature Recovery Time” when there is a need for air conditioning.

MINIMUM SETPOINTVerdant-VX-SERIES-Wireless-Thermostat-with-Occupancy-Sensor-FIG-6464-84 (65°F) Select the minimum setpoint in °F that a guest can select.

MAXIMUM SETPOINT

Verdant-VX-SERIES-Wireless-Thermostat-with-Occupancy-Sensor-FIG-65

60-82 (80°F) Select the maximum setpoint in °F that a guest can select.

AUTO CHANGEOVER SETPOINT OFFSETVerdant-VX-SERIES-Wireless-Thermostat-with-Occupancy-Sensor-FIG-6600-04 (01°F*) Select the difference between the guest-selected setpoint and the heat and cool setpoints. This feature allows to configure the minimum difference between heat and cool setpoints in order to avoid excessive use of the compressor.

SETBACK SETPOINTS / AUTO-RESTOREVerdant-VX-SERIES-Wireless-Thermostat-with-Occupancy-Sensor-FIG-67

Set the “Conditional Control / Auto Restore” to “00”, to disable EMS.

Troubleshooting

The thermostat is not controlling the PTAC unit.

Verify the status of the red light on the Wireless Control Card;

Error Codes

APPENDIX 1

Level 0 Level 1 Level 2 Level 3 Level 4 Level 5
Fan Operation Mode Auto Auto Auto Auto Auto Auto
Minimum Setpoint 64°F 65°F 66°F 67°F 68°F 68°F
Maximum Setpoint 84°F 82°F 80°F 78°F 76°F 74°F
Deadband 2°F 2°F 2°F 2°F 2°F 2°F
1st Stage Heat 0.5°F 0.5°F 0.5°F 0.5°F 0.5°F 0.5°F
2nd Stage Heat 1°F 1°F 1°F 2°F 2°F 2°F
1st Stage Cool 0.5°F 0.5°F 0.5°F 0.5°F 0.5°F 0.5°F
Heat Boost 30’ 30’ 30’ 30’ 30’ 30’
Temp Recovery Time 0’ 15’ 20’ 25’ 30’ 0’
Minimun Setpoint Cool 72°F 73°F 74°F 75°F 76°F 77°F
Minimum Setpoint Heat 69°F 68°F 67°F 66°F 65°F 64°F
Maximum Setpoint Cool 73°F 75°F 77°F 79°F 81°F 92°F
Maximum Setpoint Heat 67°F 66°F 65°F 64°F 63°F 52°F
Setback Delay Heat 0’ 30’ 25’ 20’ 15’ 10’
Setback Delay Cool 0’ 30’ 25’ 20’ 15’ 10’
Occupancy Threshold 0’ 5’ 5’ 5’ 5’ 5’
Night Occupancy Threshold 0’ 1’ 1’ 1’ 1’ 1’
Night Occupancy Start 0h 19h 20h 21h 22h 23h
Night Occupancy End 0h 11h 10h 9h 8h 7h
Autorestore Off On On On On On
Setback Setpoints Off On On On On Off

Warranty

Hardware
Verdant Environmental Technologies Inc. (“Verdant”) warrants the original end user (“Customer”) that new Verdant branded products will be free from defects in workmanship and materials, under normal use, for one (1) year from the original purchase date.

Software
Verdant warrants to Customer that the Verdant thermostat software will perform in substantial conformance to its program specifications for a period of one (1) year from the date of the original purchase.

Exclusions
This warranty excludes (1) physical damp verdant to the surface of the product, including cracks or scratches on the touch-screen or outside casing; (2) damp verdant caused by misuse, neglect, improper installation, unauthorized attempts to open, repair, or modify the product, or any other cause beyond the ranVerdant of intended use; (3) damp verdant caused by accident, fire, power changes, another hazard, or Acts of God; or (4) use of the product with any device if the such device causes the problem.

Exclusive Remedies
Should a covered defect occur during the warranty period and Customer notifies GE, Customer’s sole and exclusive remedy will be, at GE’ sole option and expense, to repair or replace the product. Replacement products or parts may be new or reconditioned or a comparable version of the defective item. Verdant warrants any replaced product or part for a period of ninety (90) days from shipment, or through the end of the original warranty, whichever is longer.

Obtaining Warranty Service
Before returning product, customer must contact Verdant for Return Material Authorization (“RMA”) number. If it is determined that the product may be defective, Customer will be issued an RMA number and instructions for product return. The RMA is valid for 30 days. Customer must return product to Verdant within the applicable warranty period to obtain warranty service. An unauthorized return, i.e. one for which an RMA number has not been issued or one for which an RMA has expired, will not be accepted. Authorized returns are to be shipped prepaid (including all duties, taxes, and shipping charges) and insured to the address on the RMA in an approved shipping container. All product returns will be subject to incoming inspection. Dated proof of original purchase will be required. Verdant will not be responsible for Customer’s memory data contained in, stored on, or integrated with any products returned to Verdant for repair, whether under warranty or not.

Warranty Exclusive
THE FOREGOING WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE, CORRESPONDENCE WITH DESCRIPTION, AND NON-INFRINGEMENT, ALL OF WHICH ARE EXPRESSLY DISCLAIMED BY Verdant AND ITS SUPPLIERS.

Disclaimer
NEITHER Verdant NOR ITS SUPPLIERS SHALL BE LIABLE FOR INCIDENTAL, CONSEQUENTIAL, INDIRECT, SPECIAL, OR PUNITIVE DAMAGES OF ANY KIND, OR FINANCIAL LOSS ARISING OUT OF OR IN CONNECTION WITH THE SALE OR USE OF THIS PRODUCT, WHETHER BASED IN CONTRACT, TORT (INCLUDING NEGLIGENCE) OR ANY OTHER THEORY, EVEN IF Verdant HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. GE’S ENTIRE LIABILITY SHALL BE LIMITED TO THE REPLACEMENT OR REPAIR OF THE PRODUCT.

Technical Specifications

Case Dimensions (Imperial) 5.125 x 4.6875” x 1.25” 3.875” x 2.125” x 0.75”
Case Dimensions (Metric) 130mm x 119mm x 32mm 98mm x 54mm x 19mm
Screen Dimensions (Impe-rial) 3.625″ x 2.125″ N/A
Screen Dimensions (Metric) 92mm x 54mm N/A
Operating Voltage 3V DC – 2 “C” Cell Batteries 24V AC (PTAC Unit)
Control Outputs Fan High (GH)
Fan Low (GL)
Compressor (Y)
Heat Pump (OB)
Electric Heat (W2)
Occupancy Sensor BeamWidth ±85° (170°) N/A
Wireless Frequency 900MHz 900MHz
Temperature Accuracy ±1°F N/A
FCC ID XEYVX XEYV8ACCC
IC 8410A-VX 8410A-V8ACCC

THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES. OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED, INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION. PURSUANT TO PART 15.21 OF THE FCC RULES, ANY CHANGES OR MODIFICATIONS TO THIS EQUIPMENT NOT EXPRESSLY APPROVED BY VERDANT ENVIRONMENTAL TECHNOLOGIES, INC. MAY VOID VOID THE USER’S AUTHORITY TO OPERATE THE EQUIPMENT.

COVERED BY ONE OR MORE OF THE FOLLOWING PATENTS. US PATENTS: RE40,437; 7,232,075; 7,185,825; 7,156,318; 7,152,806; 7,145,110; 7,050,026; 7,028,912; 6,902,117; 6,789,739; 6,786,421; 6,619,555; 6,581,846; 6,578,770; 7,838,803; 7,841,542; CANADIAN PATENTS: 2,633,113; 2,633,200;
OTHER PATENTS ARE PENDING.

Reference

Download manual: 

Verdant VX SERIES Wireless Thermostat with Occupancy Sensor User Manual

verrdant-logo

Verdant VX Series Thermostat User Manual

Leave a Reply

Your email address will not be published. Required fields are marked *

To respond on your own website, enter the URL of your response which should contain a link to this post's permalink URL. Your response will then appear (possibly after moderation) on this page. Want to update or remove your response? Update or delete your post and re-enter your post's URL again. (Find out more about Webmentions.)