Venstar T1900 Programmable Thermostat Thermostat

Venstar-T1900-Programmable-Thermostat-product

Preparation

Remove & Replace the Old Thermostat

Configuring the MISC Outputs

Configuring the Jumpers

For additional flexibility, your thermostat has three configurable outputs. These outputs are designed to have different functions depending on how the jumpers are set (below). Each output, labeled MISC1, MISC2, and MISC3 may be set for one of the five choices available. In the diagram below, the MISC3 jumper has been set for HUM (humidification) operation, the MISC2 jumper has been set for DEHUM (dehumidification) operation, and the MISC1 jumper has been set for PROG (programmable) operation.

Venstar-T1900-Programmable-Thermostat-fig.2

Explanation of Jumper Settings

W3 JUMPER SETTING
If the jumper for MISC1, MISC2, or MISC3 is set to W3, the corresponding MISC screw terminal on the backplate will control a third stage of heat.

W3 MULTI-STAGE OPERATION EXPLAINED

The 3rd Stage of Heat is turned on when

  1. The 1st and 2nd stages have been on for the time required (steps 27 and 28, page 14.6). It is adjustable from 0-60 minutes and the default is two minutes.
  2. The temperature from the setpoint is equal to or greater than the setpoint plus the 1st stage deadband (step #24, 14.5), plus the 2nd stage deadband (step #25, 14.5) plus the 3rd stage deadband (step #26, 14.5). This 3rd stage deadband is adjustable from 0-10 degrees and the default is two degrees.Venstar-T1900-Programmable-Thermostat-fig.3

PROG JUMPER SETTING
If the jumper for MISC1, MISC2, or MISC3 is set to PROG, the terminal on the backplate will control a pilot relay or other accessory. the corresponding MISC screw

PROGRAMMABLE OUTPUT – SECTION 15 of the Owner’s Manual

This jumper setting allows the MISC outputs to control a pilot relay by time, temperature, or a signal from the Internet/Phone. The following are three possible scenarios:

HUM JUMPER SETTING
If the jumper for MISC1, MISC2, or MISC3 is set to HUM, the corresponding MISC screw terminal on the backplate will control a humidification system.

HUMIDIFICATION OPERATION – SECTION 9 of the Owner’s Manual If your HVAC unit is equipped with a humidification system the thermostat will provide power to the MISC1, MISC2, or MISC3 terminal of the thermostat whenthe humidity in the home falls below the humidity setpoint you have chosen. The value for this setpoint ranges from 0% to 60%. If no humidity is desired or if a humidification system has not been installed, set the value to OFF.

DEHUM JUMPER SETTING

If the jumper for MISC1, MISC2, or MISC3 is set to DEHUM,the corresponding MISC screw terminal on the backplate will be connected to the dehumidification terminal of a furnace board.
NOTE: Not all furnaces have a dehumidification terminal.

DEHUMIDIFICATION OPERATION – SECTION 10 of the Owner’s Manual If your HVAC unit is equipped with a dehumidification system the thermostat will operate in one of two ways.

  1. Normally Closed (NC): The thermostat will de-energize the MISC1, MISC2, or MISC3 terminal of the thermostat (this MISC terminal is connected to theDEHUM terminal on your furnace) to allow the fan to run in low speed when the humidity in the home is above the dehumidify setpoint you have chosen and there is a call for 1st stage cooling.
  2. Normally Open (NO): The thermostat will energize the MISC1, MISC2, or MISC3 terminal of the thermostat (this MISC terminal is connected to the DEHUM terminal on your furnace) to allow the fan to run in low speed when the humidity in the home is above the dehumidify setpoint you have chosen and there is a call for 1st stage cooling.

Y2 JUMPER SETTING

If the jumper for MISC1 is set to Y2 the MISC1 screw terminal on the backplate will control a second stage of cooling.
Y2 OPERATION – SECTION 14 of the Owner’s Manual
Control up to two Cool stages.
The 2nd Stage of heat or cool is turned on when:

  1.  The 1st Stage has been on for the time required (step #27, page 14.6). It is adjustable from 0-60 minutes and the default is two minutes.
  2. The temperature spread from the setpoint is equal to or greater than: the setpoint plus the deadband (step #24, page 14.5), plus the 2nd deadband (step #25, page 14.5). This 2nd deadband is adjustable from 0-10 degrees and the default is two degrees.

Venstar-T1900-Programmable-Thermostat-fig.4

Wire Connections

If the terminal designations on your old thermostat do not match those on the new thermostat, refer to the chart below, or the wiring diagrams that follow.

Venstar-T1900-Programmable-Thermostat-fig.5

Sample Wiring Diagrams

6 Wire, 1 Stage Cooling, 1 Stage Heat

Residential & Commercial 1 Stage Cooling, with 1st stage Gas Heat
Commercial Heat Pump 1 Stage Cooling with 2 Stage HeatVenstar-T1900-Programmable-Thermostat-fig.66 Wire, 1 Stage Cooling, 1 Stage Heat

Residential & Commercial 1 Stage Cooling, with 1st stage Electric Heat Venstar-T1900-Programmable-Thermostat-fig.76 Wire, 1 Stage Cooling, 2 Stage Heat

Residential Heat Pump with O Reversing Valve 1 Stage Cooling, with 2 stage Heat Venstar-T1900-Programmable-Thermostat-fig.86 Wire, 1 Stage Cooling, 2 Stage Heat

Residential Heat Pump with b Reversing Valve 1 Stage Cooling, with 2 stage Heat Venstar-T1900-Programmable-Thermostat-fig.9

Adding a 2nd Stage of Cooling (MISC1), Sprinkler System (MISC2),and 3rd Stage of Heating or Dual Fuel Applications (MISC3)

Venstar-T1900-Programmable-Thermostat-fig.10

Adding a Humidification System (MISC1) and Dehumidification System (MISC2)

Venstar-T1900-Programmable-Thermostat-fig.11

CK1 and CK2 terminals wired to a Time Clock

For instructions on wiring the optional Remote and Outdoor Sensors, please see page 16.2 of the Owner’s Manual Venstar-T1900-Programmable-Thermostat-fig.12

DRY CONTACT SWITCH – The terminals are ‘normally open’ (or may be programmed for normally closed operation, see page 17.2 of the Owner’s Manual). Closing or completing the circuit will cause the thermostat to do one of the following:

  1. If Vacation is selected in step #41 of the Advanced Setup (see page 17.3 of the Owner’s Manual), when the dry contact is energized the thermostat will be forced into Vacation mode (see Section 20 of the Owner’s Manual).
  2. If Service Pan is selected, when the dry contact is energized the thermostat will lockout Y1 (compressor) and write Service Pan on the display.

Test Operation

Calibrating the Thermostat Sensors

Under normal circumstances it will not be necessary to adjust the calibration of the temperature and humidity sensors. If calibration is required, please contact a trained HVAC technician to correctly perform the following procedure.

Venstar-T1900-Programmable-Thermostat-fig.13

After calibration is complete, press the MODE button once to return to normal operation.

Troubleshooting

References:

Download Manual

Venstar T1900 Programmable Thermostat Thermostat Installation Instructions

OTHER MANUAL

Venstar T1900 Programmable Thermostat Owner Manual

Venstar-logo

Venstar T1900 Programmable Thermostat Installation Instruction

Leave a Reply

Your email address will not be published. Required fields are marked *

To respond on your own website, enter the URL of your response which should contain a link to this post's permalink URL. Your response will then appear (possibly after moderation) on this page. Want to update or remove your response? Update or delete your post and re-enter your post's URL again. (Find out more about Webmentions.)