Trane XR724 Smart Control Thermostat User Guide
XR724 Features
- WiFi comfort control
- Remote access via smartphone, tablet, or P.C.
(requires a Trane® Home account) - Interactive 4.3” black & white touchscreen
- 7 Day programmable, 4 schedules/day
- Built in humidity sensor with RH display
- Filter, maintenance, and humidifier service reminders
- Remote temperature sensing option (1 indoor/1 outdoor)
- Auxiliary & compressor heat lockouts
- Dehumidification (over cooling)
- Enhanced dehumidification (cooling)
- Adjustable variable speed fan settings (pwm)
- Energy Savings Mode (ESM)
- Screen lock
- Upgradable firmware (requires a Trane Home account)
- Service test modes
- Humidifier control
XR724 Product Specifications
Specification | Description |
Product Model: | TCONT724AS42DA |
Product: | XR724 HVAC System comfort control. WiFi communications enabled. |
Size: | 5.75” wide x 3.5” height x 1” depth |
Display: | Fixed Segment LCD, 4” x 2.25”, with 17 character alpha numeric display |
Touchscreen: | Yes |
Backlight: | Yes, White, Controllable, on, off, timeout |
Power: | 24VAC from HVAC System |
HVAC System Type: | Standard (gas/electric), Heat Pump, or Dual Fuel |
Heat/Cool Stages: | Up to four stages of heat/two stages cool |
PWM Output (BK) | Variable speed motor control |
Heat Pump Switchover valve: | Selectable change over with cool or with heat |
Auxiliary Contact | Humidifier, Ventilation or Dehumidifier control |
Communications: | WiFi |
Memory: | Non-volatile |
Date/Time: | 12 hour super capacitor backup
Time is automatically updated if the control is connected to Trane Home |
Operation
The XR724 Comfort Control provides typical operation of a forced air heating and cooling HVAC system. It also features WiFi capability for remote control and Trane Home connectivity.
Normally, the Comfort Control displays the Home Screen as shown above.
Item | Description | Notes |
Clock Display | The current time is displayed in the upper left corner of the main screen. The time will blink when the clock has not been set. | See TIME/DATE for more information. If the control is connected to Trane Home, the clock will be updated by the Trane Home portal. |
Dynamic Labels and Func- tion Control Buttons | The buttons are defined by the dynamic labels in each button. As you navigate through menus, the labels for the buttons will change. | |
Setpoint Display and Set- point Up/Down Buttons | The current heat or cool setpoint is displayed. These setpoints may be set using Trane Home, the Control’s internal schedule, or by pressing the Setpoint Up/ Down buttons. Pressing the setpoint button changes the setpoint screen. The current mode is displayed at the top of the screen. Adjust the setpoint by pressing the up or down arrows. To change setpoint mode press the MODE button. | The setpoints will push each other if they are adjusted to within the minimum heat/cool separation setting.
This is normally 3 degrees. |
Temperature Display | The Comfort Control displays the current temperature as sensed by the internal temperature sensor. | The internal temperature sensor can be adjusted as necessary. |
Menu Button | Button used to access other Comfort Control menus | |
System Mode Button | Button used to change the system mode. | Off: System off Heating: Heating only Cooling: Cooling only
Auto: Heating/Cooling as necessary EM Heat: Heat Pump Emergency Heat, Compressor Disabled, Indoor Heat only. |
Fan Mode Button | Button used to change the fan mode | Auto: Fan on when cooling/heating is necessary On: Fan constantly on
Circ: Fan on for a user-selected number of minutes per hour |
Schedule Mode Button | Button used to change the schedule mode
The default mode is HOLD which disables scheduling. |
Hold: System maintains the current temperature setpoints. Schedules are disregarded.
Run: Run the system schedule Energy Saving Mode (ESM): Run schedule using the ESM Setpoints. Manual setpoint changes while in Run Schedule mode will only last until the next schedule period. |
The following is a guide of the menu options available by pressing the Menu button. Certain menu selections, which are marked by an asterisk ( * ), may or may not be present depending on other menu settings.
HUMIDITY
* Only appears as a menu item if Dehumidify is set to Yes, Aux Relay is set to Dehumidifier or Aux Relay is set to Humidity.
HUMIDITY | ||
Setting | Range | Description |
Cooling RH Target* | 30% to 60% [50%] | Select the desired indoor relative humidity during cooling mode. Dehu- midification must be enabled in the Installer Settings for this option to be available. |
Heating RH Target* | 10% to 45% [40%] | Select the desired indoor relative humidity during heating mode. Humidification must be enabled in the Installer Settings for this option to be available. |
Once all selections have been made, press the Done button to exit and return to menu. Press Next to navigate to the next setting. |
USER SETTINGS
User Settings allow the user to customize various settings on the XR724 control. To access User Settings simply press the Menu button once and “User Settings” will be displayed. To enter the User Settings menu, press the Select button, then use the Next button to navigate through the options below. The default setting will be shown in brackets. After each selection press the Done button to save changes. Certain menu selections, which are marked by an asterisk ( * ), may or may not be present depending on other menu settings.
THERMOSTAT | ||
Setting | Range / Sub Setting | Description / Range of Sub Settings |
Temperature Scale | [Fahrenheit], Celsius | Select the temperature display scale |
Max Heat Setpoint | 55 – [90] Degrees | Select the highest heating setpoint allowed |
Min Cooling Setpoint | [60] – 99 Degrees | Select the lowest cooling setpoint allowed |
Time/Date* | Set Hour | 1 – 12 AM, 1 – 12 PM [12PM] |
If connected with Trane Home, then time and date are provided by the network |
Set Minutes | 0 – 59 [0] |
Day of Week | [Sun], Mon, Tue, Wed, Thr, Fri, Sat | |
Year | [2013] – 2113 | |
Month | [Jan], Feb, Mar, Apr, May, Jun, Jul, Aug, Sep, Oct, Nov, Dec | |
Date | [1] – 31 | |
DST Enable | [Yes], No | |
Continuous Fan Airflow* | 35% – 100% [50%] | Select the desired fan speed when the Fan Mode selected is Continuous (variable speed blower required). Only available if ID Fan Type = Variable. |
Fan Circulate On Time | [10] – 55 minutes | Select the desired amount of time the fan will cycle per hour when the Fan Mode selected is Circ |
Once all selections have been made, press the Done button to exit and return to menu. Press Next to navigate to the next setting. |
The following is a guide of the menu options available by pressing the Menu button. Certain menu selections, which are marked by an asterisk ( * ), may or may not be present depending on other menu settings.
SCHEDULES | ||
Setting | Range / Sub Settings | Description / Range of Sub Settings |
ESM Heat Setpoint* | 55 – 90 degrees [62] | Select the desired Heating Setpoint when ESM (Energy Savings Mode) is selected |
ESM Cooling Setpoint* | 60 – 99 degrees [85] | Select the desired Cooling Setpoint when ESM is selected |
Edit Schedule* | Select Day (use Back/Next) Wake Period | This section is done for each day Set Time [6:00 am]
Heat Setpoint 60˚- 90˚ [70] Cool Setpoint 60˚- 90˚ [78] |
Day Period | Set Time [8:00 am]
Heat Setpoint 60˚- 90˚ [62] Cool Setpoint 60˚- 90˚ [85] |
|
Eve Period | Set Time [6:00 pm]
Heat Setpoint 60˚- 90˚ [70] Cool Setpoint 60˚- 90˚ [78] |
|
Night Period | Set Time [10:00 pm]
Heat Setpoint 60˚- 90˚ [62] Cool Setpoint 60˚- 90˚ [78] |
|
Copy Schedule* | Copy from (use Back/Next) Select day to copy
Copy (day selected) To |
Copy selected day to current schedule period. |
Smart Recovery* | Yes, [No] | |
Once all selections have been made, press the Done button to exit and return to menu. Press Next to navigate to the next setting. |
DISPLAY | ||
Setting | Range | Description |
Backlight On | 0 – [100] percent | Select the screen brightness level when the backlight is lit |
Backlight Off | [0] – 100 percent | Select the screen brightness level when the backlight timeout expires |
Display Lock | [Unlocked], Display lock | Select security level
• Unlocked – Enables selection of all menus and settings • Display Lock – Disables selection of all menus and settings Note: When Display Lock is selected a lock icon will appear next to the up arrow. Note: To disable Display Lock, press and hold the Menu button 5 seconds until the lock icon disappears. |
Once all selections have been made, press the Done button to exit and return to menu. Press Next to navigate to the next setting. |
CALIBRATE SENSORS | ||
Setting | Range | Description |
Sensor Cal | +/- 7 degrees (F or C) [0 deg] | Calibrate the internal temperature sensor (1˚ in F = 2˚ in C) |
Remote Sensor Cal* | +/- 7 degrees (F or C) [0 deg] | Calibrate an attached remote sensor |
ODT Sensor Cal* | +/- 7 degrees (F or C) [0 deg] | Calibrate an attached outdoor sensor |
RH Cal | +/- 7 % [0 %] | Calibrate the internal humidity sensor |
Once all selections have been made, press the Done button to exit and return to menu. Press Next to navigate to the next setting. |
WIFI
Even though open networks (no password) and WEP WiFi encryption are supported, it is recommended to use a more secure network encryption such as WPA2 or later.
WIFI | ||
Setting | Range | Description |
Network | Join a Network OR leave network | Network connection action required: Yes, No |
Status | WiFi not configured
OR Trane Home enrolled |
Status of Network connection |
Connection Result | WiFi not configured OR Success | Status of WiFi connection |
Info | SPWF FW | Firmware version displayed |
SSID | Not Available OR Network Name displayed | |
IP | Not Available OR IP Address displayed | |
Mask | Not Available OR Mask displayed | |
GW | Not Available OR Gateway IP address displayed | |
DNS | Not Available OR DNS IP address displayed | |
MAC | Not Available OR MAC address displayed | |
Retries | Retries (X) | Number of connection retries |
Connection Time | Disconnected OR X hours | Connection hours |
RSSI | RSSI – xx DBM | Connection signal strength |
Once all selections have been made, press the Done button to exit and return to menu. Press Next to navigate to the next setting. |
TRANE HOME
HOME APP | ||
Setting | Range | Description |
Status | WiFi Not Configured Enrolled | WiFi connection status |
Info | Port (XXXXX)
HOME APP Pin (XXXX) |
Trane Home connection info |
Enroll OR Unenroll | Enroll, Unenroll | Join OR leave a Trane Home Connection |
Once all selections have been made, press the Done button to exit and return to menu. Press Next to navigate to the next setting. |
The following is a guide of the menu options available on the screen accessed by pressing the Menu button. Certain menu selections, which are marked by an asterisk ( * ), may or may not be present depending on other menu settings.
SERVICE
Press and hold Service button for 5 seconds until the service menu is displayed
INSTALLER SETTINGS | ||
Setting | Sub Settings | Range |
Equipment Type | ODU Type (Outdoor Unit) | None, [AC], HP |
ODU Stages | [1 Stage], 2 Stages | |
Compressor Type* | [1 Comp – 2 Stage], 2 Comp – 2 Stage | |
IDU Type | [Gas / Oil], Electric, Hydronic | |
Hydronic Type* | [Hydro Air], Wet Heat | |
ID Heat Stages | [1 Stage], 2 Stages | |
ID Fan Type | [Non-Variable], Variable | |
SOV Operation* | [with Cool], With Heat | |
Sensor Settings | Remote Sensor | [None], Replace Indoor, Average |
ODT Sensor | [None], Outdoor | |
Accessories | Aux Relay | [None], Humidity, Ventilation, Dehumidifier |
Control Option* | [With Active Heat], Without Active Heat | |
Vent Run Time* | [Off], 5 – 60 min in 5 min increments | |
Comfort Settings | Control Response | [Normal], Less Aggressive, More Aggressive (see page 9 for definitions) |
Dehumidify* | [Yes], No | |
Overcooling Limit* | [Off], 1 deg, 2 deg, 3 deg | |
Smart Cont Fan* | [No], Yes | |
Airflow Settings | One of the following groups will be di | splayed |
Fan type = Non Variable | On Delay Cooling | [0], 5-90 Sec in 5 sec increments |
Off Delay Cooling | [0], 5-90 Sec in 5 sec increments | |
On Delay Heating* | [0], 5-90 Sec in 5 sec increments | |
Off Delay Heating* | [0], 5-90 Sec in 5 sec increments | |
Fan type = Variable | On Delay Cooling | Disabled, [Enhanced Mode], 30-sec delay |
Off Delay Cooling | Disabled, [1.5 Min at 100%], 45 sec delay | |
On Delay Heating* | Disabled, [Enhanced Mode], 30 sec delay | |
Off Delay Heating* | Disabled, [1.5 Min at 100%], 45 sec delay | |
Hydronic Type = Hydro Air | On Delay Heat | [0], 5-90 Sec in 5 sec increments |
Off Delay Heat | [0], 5-90 Sec in 5 Sec increments | |
Lockouts* | Aux Heat | [No], Yes |
Aux Lockout ODT* | 30 – 70 Deg [50 Deg] | |
Comp Heat | [No], Yes | |
Comp Lockout ODT* | 5 – 70 Deg, [40 Deg] | |
Once all selections have been made, press the Done button to exit and return to menu. Press Next to navigate to the next setting. |
The following is a guide of the menu options available on screen accessed by pressing the Menu button. Certain menu selections, which are marked by an asterisk ( * ), may or may not be present depending on other menu settings.
TEST MODE (stays on for 30 minutes) | ||
Test Mode | Settings | Description |
Blower (Non-VS) | Blower On | Energize “G” circuit |
Blower (VS) | 50%, 100% | Energize “G” and “BK” circuit |
Cooling | Single Stage, 1st Stage, 2nd Stage | Energize selected “Y1” or “Y2”, “O” and “G” circuit (BK also for VS indoor unit) |
Comp Heating* | Single Stage, 1st Stage, 2nd Stage | Energize selected “Y1” or “Y2” and “G” circuit (“BK” also for VS indoor unit) |
Indoor Heating | Single Stage, 1st Stage, 2nd Stage | Energize selected “W1” or “W2” (“G” circuit also for electric heat) |
Aux Relay | Relay On | Close normally open dry contacts |
Once testing is complete, press the Done button to exit and return to menu. |
REMINDERS | ||
Setting | Range | Description |
Filtration Enable | [No], Yes | Filter change reminder |
Filter Period* | [Monthly], Quarterly, Bi-Annually, Annually | Filter change reminder period |
Start Month* | [Jan], Feb, Mar, Apr, May, Jun, Jul, Aug, Sep, Oct, Nov, Dec | Period start month |
System Maint Enable | [No], Yes | System Maintenance reminder |
Maint Period* | [Bi-Annually], Annually | Maintenance reminder period |
First Maint Month* | Jan, Feb, [Mar], Apr, May, Jun, Jul, Aug, Sep, Oct, Nov, Dec | Period start month |
Second Maint Month* | Jan, Feb, Mar, Apr, May, Jun, Jul, Aug, [Sep], Oct, Nov, Dec | 2nd period start month |
Humidifier Enable | [Yes], No | |
Start Month | [Jan], Feb, Mar, Apr, May, Jun, Jul, Aug, Sep, Oct, Nov, Dec | |
Once all selections have been made, press the Done button to exit and return to menu. Press Next to navigate to the next setting. |
RESTORE DEFAULTS | ||
Setting | Action | Description |
Restore HVAC Defaults | Yes, No | Resets all HVAC settings to Default Settings |
Restore Factory Defaults | Press and Hold “Yes” | Press and hold “Yes” button until “Factory” is displayed Resets HVAC and WiFi defaults |
ABOUT
Setting | Range | Description |
Version | XXXXXX | Firmware version number |
Device ID (SIN) | XXXXXX | Unit serial number |
ODU Type | None, AC, HP | Outdoor unit type setting |
IDU Type | Electric, Gas/Oil, Hydronic | Indoor unit type setting |
SOV | W/Cool, W/Heat | Switchover value type setting (HP only) |
Once all selections have been made, press the Done button to exit and return to menu. Press Next to navigate to the next setting. |
CLEAN SCREEN
Setting | Range | Description |
Clean Screen | Yes, No | 30 sec countdown |
Once all selections have been made, press the Done button to exit and return to menu. Press Next to navigate to the next setting. |
XR724 Control Response Profiles
From Installer Settings / Comfort Settings (numbers are in degrees, F or C)
Cooling | Normal | Less Aggressive | More Aggressive |
Cooling Delta Stage 1 ON | 0.5 | 1 | 0.5 |
Cooling Delta Stage 2 ON | 1.5 | 2 | 1 |
Cooling Delta Stage 1 OFF | -0.5 | 0 | -1.0 |
Cooling Delta Stage 2 OFF | -0.5 | 0 | -1.0 |
Heating – HP | Normal | Less Aggressive | More Aggressive |
Comp Heat Delta Stage 1 ON | 0.5 | 1 | 0.5 |
Comp Heat Delta Stage 2 ON | 1.5 | 2 | 1.0 |
Indoor Heat Delta Stage 1 ON | 2.5 | 3 | 1.5 |
Indoor Heat Delta Stage 2 ON | 3.5 | 4 | 2.0 |
Comp Heat Delta Stage 1 OFF | 0 | 0 | 0 |
Comp Heat Delta Stage 2 OFF | 0 | 0 | 0 |
Indoor Heat Delta Stage 1 OFF | 0 | 0 | 0 |
Indoor Heat Delta Stage 2 OFF | 0 | 0 | 0 |
Heating – Gas | Normal | Less Aggressive | More Aggressive |
Indoor Heat Delta Stage 1 ON | 0.5 | 1 | 0.5 |
Indoor Heat Delta Stage 2 ON | 1.5 | 2 | 1.0 |
Indoor Heat Delta Stage 1 OFF | 0 | 0 | 0 |
Indoor Heat Delta Stage 2 OFF | 0 | 0 | 0 |
Timers | Normal | Less Aggressive | More Aggressive |
Heat Stage UP Timer | 15 min | 20 min | 10 min |
Cool Stage UP Timer | 15 min | 20 min | 10 min |
XR724 TRANE HOME Enrollment
The XR724 uses the Trane Home mobile app to enroll into Trane Home. To enroll download the Trane Home app from the Google Play™ Store or App Store®, then launch the app. Once in the app, click Connect New Device, select smart thermostat 724 model then follow the installation wizard prompts. All trademarks referenced are the trademarks of their respective owners. Google is a trademark of Google LLC.
Even though open networks (no password) and WEP WiFi encryption are supported, it is recommended to use a more secure network encryption such as WPA2 or later.
XR724 TRANE HOME WiFi Reconfiguration
XR724 INSTALLER’S GUIDE
INSTALLATION AND WIRING
MERCURY NOTICE
PHYSICAL LOCATION
Temperature Sensing Considerations
The XR724 Control is designed for installation in climate-controlled living spaces. It is recommended to place the unit in central locations with good circulation. Avoid exterior walls and areas near windows, doors, vents or concealed pipes or chimneys.
- CAUTION: ELECTRICAL HAZARD
CAUTION: Before proceeding with installation, verify system power has been removed. Separate the face of the new Comfort Control from the wall plate.
NOTE: It is not recommended that this WiFi Comfort Control be mounted onto metal structures. Metal may adversely affect the radio frequency (RF) communication between the Comfort Control and the WiFi network. - Mark two mounting holes using a new wall plate.
- Pull wires through hole in the center of wall plate.
- Locate the new wall plate over the existing opening.
- Mark two holes with a pencil.
- Use a level to verify that the two hole locations are level.
- Correct hole locations as needed.
- Install new wall plate.
- Pull wires through hole in the center of wall plate.
- Locate the naew wall plate over the existing opening.
- Attach wall plate to the wall using two screws provided. Do not over-tighten.
- Attach all wires securely to the new Comfort Control.
(See the Field Wiring Diagrams on the following pages.)
Note: A wire must be connected to “C” to power the Comfort Control.- Use the information from the Field Wiring Diagrams to match the wires to the correct terminals.
- Use 1/8” blade screwdriver to secure wires in terminals.
CAUTION: EQUIPMENT DAMAGE HAZARD
Improper wiring can lead to equipment damage. Use the field wiring diagrams to ensure the Comfort Control is wired properly. After wires are secure, bare wires MUST NOT touch each other. See the Field
Connection Wiring Diagrams on the following pages for specific system applications.
- Attach the Comfort Control face to the wall plate.
- Carefully align the face plate to the wall plate while aligning pins into wire terminals.
- Once Comfort Control face is properly aligned, apply pressure at top and bottom of
Comfort Control face until it is secure.
- Turn power to the heating and cooling system back on.
The Comfort Control display should turn on and begin displaying information. Proceed to Installer’s Setup to configure system settings.
Field Wiring Diagrams
Heat/Cool Wiring Diagrams
Heat/Cool Diagram 1: 1 or 2 Stage Cooling w/TAM7 Model Variable Speed Air Handler or TAM9 24V mode
Notes:
- Cut/remove the factory-installed “BK” jumper at the indoor unit
- “Y2” & “R” connections at outdoors are only required for two-stage units
- Jumper “W2” to “W3” if three stages of indoor heat are available
- “YI” and “YO” connections must be made as shown for freeze protection and internally mounted condensate overflow circuits to work properly
If third-party condensate overflow switches are installed, they should be wired between “Y1” of the thermostat and “YI” of the airflow control board
Remote Temperature Sensor Connections and Operation:
Sensor Options in the Installer Settings/Sensor Settings menu Remote Sensor (connect to the RS terminals)
- None
- Replaces internal sensor
- Average with internal sensor
Outdoor Temp Sensor (connect to the ODT terminals) - None
- Outdoor
Caution: Do not run sensor wires in the same bundle with HVAC wires. Keep away from high-voltage wiring to avoid interference.
Heat/Cool Diagram 2: 1 Stage Cooling w/GAM5A & TAM4 Model Air Handler
Notes:
- Jumper “W2” to “W3” if three stages of indoor heat are available
- “YI” and “YO” connections must be made as shown for freeze protection and internally mounted condensate overflow circuits to work properly
- If third-party condensate overflow switches are installed, they should be wired between “Y” of the thermostat and “YI” of the airflow control board
Remote Temperature Sensor Connections and Operation:
Sensor Options in the Installer Settings/Sensor Settings menu Remote Sensor (connect to the RS terminals)
- None
- Replaces internal sensor
- Average with internal sensor
Outdoor Temp Sensor (connect to the ODT terminals) - None
- Outdoor
Caution: Do not run sensor wires in the same bundle with HVAC wires. Keep away from high-voltage wiring to avoid interference.
Heat/Cool Wiring Diagrams
Heat/Cool Diagram 3: 1 Stage Cooling w/“GAM5B” Model Air Handler
Notes:
- Jumper “W2” to “W3” if three stages of indoor heat is available
- “Y” terminal must be connected at indoor unit for high-stage airflow.
Remote Temperature Sensor Connections and Operation:
Sensor Options in the Installer Settings/Sensor Settings menu Remote Sensor (connect to the RS terminals)
- None
- Replaces internal sensor
- Average with an internal sensor
Outdoor Temp Sensor (connect to the ODT terminals) - None
- Outdoor
Caution: Do not run sensor wires in the same bundle with HVAC wires. Keep away from high-voltage wiring to avoid interference.
Heat/Cool Diagram 4: 2 Stage Cooling w/GAM5B Model Air Handler
Notes:
- Jumper “W2” to “W3” if three stages of indoor heat are available
- “Y” must be connected at indoor unit for cooling airflow
Remote Temperature Sensor Connections and Operation:
Sensor Options in the Installer Settings/Sensor Settings menu Remote Sensor (connect to the RS terminals)
- None
- Replaces internal sensor
- Average with an internal sensor
Outdoor Temp Sensor (connect to the ODT terminals) - None
- Outdoor
Caution: Do not run sensor wires in the same bundle with HVAC wires. Keep away from high-voltage wiring to avoid interference.
Heat/Cool Wiring Diagrams
Heat/Cool Diagram 5: 1 Stage Cooling w/GAF2-S Model Air Handler
Remote Temperature Sensor Connections and Operation:
Sensor Options in the Installer Settings/Sensor Settings menu Remote Sensor (connect to the RS terminals)
- None
- Replaces internal sensor
- Average with internal sensor
Outdoor Temp Sensor (connect to the ODT terminals) - None
- Outdoor
Caution: Do not run sensor wires in the same bundle with HVAC wires. Keep away from high-voltage wiring to avoid interference.
Heat/Cool Diagram 6: 1 Stage cooling w/GAF2-36M Model Air Handler
Notes:
- “YI” and “YO” connections must be made as shown for freeze protection and internally mounted condensate overflow circuits to work properly
- If third party condensate overflow switches are installed, they should be wired between “Y1” of the thermostat and “YI” of the airflow control board
Remote Temperature Sensor Connections and Operation:
Sensor Options in the Installer Settings/Sensor Settings menu Remote Sensor (connect to the RS terminals)
- None
- Replaces internal sensor
- Average with internal sensor
Outdoor Temp Sensor (connect to the ODT terminals) - None
- Outdoor
Caution: Do not run sensor wires in the same bundle with HVAC wires. Keep away from high voltage wiring to avoid interference.
Heat/Cool Wiring Diagrams
Heat/Cool Diagram 7: 1 Stage Cooling w/GAT2 & GAM2 Model Air Handlers
Notes:
- Jumper “W2” to “W3” if three stages of indoor heat are available
Remote Temperature Sensor Connections and Operation:
Sensor Options in the Installer Settings/Sensor Settings menu Remote Sensor (connect to the RS terminals)
- None
- Replaces internal sensor
- Average with internal sensor
Outdoor Temp Sensor (connect to the ODT terminals) - None
- Outdoor
Caution: Do not run sensor wires in the same bundle with HVAC wires. Keep away from high-voltage wiring to avoid interference.
Heat/Cool Diagram 8: 1 Stage Cooling w/TEM3 Model Air Handler
Notes:
- Jumper “W2” to “W3” if three stages of indoor heat are available
Remote Temperature Sensor Connections and Operation:
Sensor Options in the Installer Settings/Sensor Settings menu Remote Sensor (connect to the RS terminals)
- None
- Replaces internal sensor
- Average with internal sensor
Outdoor Temp Sensor (connect to the ODT terminals) - None
- Outdoor
Caution: Do not run sensor wires in the same bundle with HVAC wires. Keep away from high-voltage wiring to avoid interference.
Heat/Cool Diagram 9: 1 or 2 Stage Cooling w/TEM8, TEM6 Variable Speed Air Handler
Notes:
- Cut/remove the factory-installed “BK” jumper at the indoor unit
- “Y2” & “R” connections at outdoors are only required for two-stage units
- Jumper “W2” to “W3” if three stages of indoor heat are available
- For non-Trane/American Standard Indoor units “BK” is not connected and “Y1”/”Y2” must be connected at the indoor unit.
Remote Temperature Sensor Connections and Operation:
Sensor Options in the Installer Settings/Sensor Settings menu Remote Sensor (connect to the RS terminals)
- None
- Replaces internal sensor
- Average with internal sensor
Outdoor Temp Sensor (connect to the ODT terminals) - None
- Outdoor
Caution: Do not run sensor wires in the same bundle with HVAC wires. Keep away from high-voltage wiring to avoid interference.
Heat/Cool Diagram 10: 1 Stage Cooling w/non-Variable Speed Air Handler (Excludes Hyperion/Forefront/TEM3 Air Handlers)
Notes:
- Jumper “W2” to “W3” if three stages of indoor heat are available
Remote Temperature Sensor Connections and Operation:
Sensor Options in the Installer Settings/Sensor Settings menu Remote Sensor (connect to the RS terminals)
- None
- Replaces internal sensor
- Average with internal sensor
Outdoor Temp Sensor (connect to the ODT terminals) - None
- Outdoor
Caution: Do not run sensor wires in the same bundle with HVAC wires. Keep away from high-voltage wiring to avoid interference.
Heat/Cool Diagram 11: 1 Stage Cooling w/non-Variable Speed Gas Furnace
Remote Temperature Sensor Connections and Operation:
Sensor Options in the Installer Settings/Sensor Settings menu Remote Sensor (connect to the RS terminals)
- None
- Replaces internal sensor
- Average with internal sensor
Outdoor Temp Sensor (connect to the ODT terminals) - None
- Outdoor
Caution: Do not run sensor wires in the same bundle with HVAC wires. Keep away from high voltage wiring to avoid interference.
Heat/Cool Diagram 12: 1 or 2 Stage Cooling w/Variable Speed Gas Furnace
Notes:
- Cut/remove the factory-installed “BK” jumper at the indoor unit
- “Y2” & “R” connections at outdoor are only required for two-stage units
- For non-Trane/American Standard Indoor units “BK” is not connected and “Y1”/”Y2” must be connected at indoor unit.
Remote Temperature Sensor Connections and Operation:
Sensor Options in the Installer Settings/Sensor Settings menu Remote Sensor (connect to the RS terminals)
- None
- Replaces internal sensor
- Average with internal sensor
Outdoor Temp Sensor (connect to the ODT terminals) - None
- Outdoor
Caution: Do not run sensor wires in the same bundle with HVAC wires. Keep away from high voltage wiring to avoid interference.
Heat/Cool Diagram 13: 1 Stage Cooling w/non-Variable Speed Oil Furnace
Notes:
- BT (Bonnet Thermostat) model THT1248 is required for dual fuel, oil furnace applications.
- Field-supplied relay (R1) required for oil burner primary
Remote Temperature Sensor Connections and Operation:
Sensor Options in the Installer Settings/Sensor Settings menu Remote Sensor (connect to the RS terminals)
- None
- Replaces internal sensor
Average with internal sensor
Outdoor Sensor (connect to the ODT terminals) - None
- Outdoor
Caution: Do not run sensor wires in the same bundle with HVAC wires. Keep away from high voltage wiring to avoid interference.
Heat/Cool Diagram 14: 1 or 2 Stage Cooling w/Variable Speed Oil Furnace
Notes:
- Cut/remove the factory-installed “BK” jumper at the indoor unit
- “Y2” & “R” connections at outdoor unit are only required for 2 stage systems
- For non-Trane/American Standard Indoor units “BK” is not connected and “Y1”/”Y2” must be connected at indoor unit.
- BT (Bonnet Thermostat) model THT1248)
required for dual fuel, oil furnace applications - Field supplied relay (R1) required for oil burner primary
Remote Temperature Sensor Connections and Operation:
Sensor Options in the Installer Settings/Sensor Settings menu Remote Sensor (connect to the RS terminals)
- None
- Replaces internal sensor
- Average with internal sensor
Outdoor Temp Sensor (connect to the ODT terminals) - None
- Outdoor
Caution: Do not run sensor wires in the same bundle with HVAC wires. Keep away from high voltage wiring to avoid interference.
Heat/Cool Diagram 15: Package Single or Multi-Stage Gas/Electric with Variable Speed Blower
Notes:
- Cut/remove the factory-installed “BK” jumper on the ECM fan control board
- For non-Trane/American Standard Indoor units “BK” is not connected
Remote Temperature Sensor Connections and Operation:
Sensor Options in the Installer Settings/Sensor Settings menu Remote Sensor (connect to the RS terminals)
- None
- Replaces internal sensor
- Average with internal sensor
Outdoor Temp Sensor (connect to the ODT terminals) - None
- Outdoor
Caution: Do not run sensor wires in the same bundle with HVAC wires. Keep away from high voltage wiring to avoid interference.
Heat/Cool Diagram 16: Package Single Stage Gas/Electric with non-Variable Speed Blower
Remote Temperature Sensor Connections and Operation:
Sensor Options in the Installer Settings/Sensor Settings menu Remote Sensor (connect to the RS terminals)
- None
- Replaces internal sensor
- Average with internal sensor
Outdoor Temp Sensor (connect to the ODT terminals) - None
- Outdoor
Caution: Do not run sensor wires in the same bundle with HVAC wires. Keep away from high voltage wiring to avoid interference.
Heat Pump Wiring Diagrams
Heat Pump Diagram 1: 1 or 2 Stage Heat Pump w/TAM7 Model Variable Speed Air Handler
Notes:
- Outdoor Sensor required for dual fuel restricted mode.
Remote Temperature Sensor Connections and Operation:
Sensor Options in the Installer Settings/Sensor Settings menu Remote Sensor (connect to the RS terminals)
- None
- Replaces internal sensor
- Average with internal sensor
Outdoor Temp Sensor (connect to the ODT terminals) - None
- Outdoor
Caution: Do not run sensor wires in the same bundle with HVAC wires. Keep away from high voltage wiring to avoid interference.
Optional Remote Temperature Sensor Installation
Wire specification for remote sensors: 2 conductors, 18 gauge wire. Make sure that the sensor wires are installed in a separate cable from the wiring to the HVAC system. Best results for distances of 100 feet or less. Accuracy may be affected for distances up to a maximum of 200 feet. Shielded cable is recommended for distances over 100 feet and less than 200 feet.
CAUTION: Keep this wiring at least one foot away from large inductive loads such as electronic air cleaners, motors, line starters, lighting ballasts, and large distribution panels. Failure to follow these wiring practices may introduce electrical interference (noise) which can cause erratic system operation. Shielded cable is required if the above wiring guidelines cannot be met.
Be sure to ground only one end of the shield to the Comfort Control common terminal. Tape back the other end of the shield.
Remote Sensor Part Numbers
Remote Indoor Sensor: Use ZZSENSAL0400AA for indoor applications.
Remote Outdoor Sensor: Use BAYSEN01ATEMPA for outdoor applications.
- IMPORTANT: Make sure that the sensor wires are installed in a separate cable from the Comfort Control cable.
- IMPORTANT: Follow directions below for averaging. These instructions replace the averaging information found in the Installer’s Guide for the ZZSENSAL0400AA.
Remote Temperature Sensor Connections and Operation:
- A) Indoor sensor connected to RS.
The Remote Sensor (RS) function can be configured in the Service/Installer Settings/Sensor Settings menu. Options are:- None
- Replaces onboard temp sensor of the Comfort Control
- Averages with onboard temp sensor
Replace – RS Sensor replaces the internal temperature sensor of the Comfort Control. This allows the Comfort Control to be installed in a location different than the area where the temperature will be measured. Use ZZSENSAL0400AA.
Average – RS Sensor averages its temperatures with the internal sensor. Use ZZSENSAL0400AA.
- B) Outdoor sensor connected to ODT. Reports outdoor temperature to the Comfort Control.
The Outdoor Sensor (ODT) function can be configured in the Service/Installer Settings/Sensor Settings menu. Options are:- None
- Outside
Outside – ODT (outdoor temperature sensor). If ODT sensor is selected and connected, the outdoor temp is displayed on the main screen. ODT model is BAYSEN01ATEMPA.
Troubleshooting
Troubleshooting | ||
Symptom | Possible Cause | Action |
Display will not come on | Loss of 24VAC between R & C at the Control | 1) Check wiring between R & C
2) Check transformer for 24VAC output 3) Check for broken or shorted thermostat wire |
Indoor Temperature display is incorrect | 1) Indoor temperature display needs calibrating (always allow 1 hour before calibrating after any power cycle)
2) Heat from the touchscreen is being trapped within the body of the control |
1) Calibrate indoor temperature sensor
2) Relocate the control away from any competing air sources or redirect the air sources away from the control |
Indoor humidity display is incorrect | Indoor humidity sensor needs calibrating | Calibrate humidity sensor |
Room temperature overshoots the desired setpoint in cooling mode | 1) The delta “Off” in cooling mode is set to a negative number
2) Cooling overshoot is enabled and the indoor RH is higher than the target cooling RH 3) Minimum compressor on time has not been met |
1) Intended operation; if objectionable, change the delta “Off” to 0 degrees
2) Intended operation: if objectionable, disable cooling over- shoot or raise cooling target RH 3) Intended operation; if objectionable, change Control Response settings in the Installers Settings, Comfort Settings Menu |
Room temperature overshoots the desired setpoint in heating mode | Minimum compressor/indoor heat on time has not been met | Intended operation; if objectionable, change control response settings in the Installers Settings, Comfort Settings Menu |
Cooling will not come on | 1) System mode is not set to Cool/Auto or setpoint is set too high
2) Delta “On” for cooling is set too high 3) Minimum off time delay is being enforced 4) Cooling system may need service |
1) Select the correct system mode and/or lower the setpoint
2) Change the delta “On” setting for cooling mode 3) Intended operation; if objectionable, change Control Response settings in the Installers Settings, Comfort Settings Menu 4) Check/repair system |
Heating will not come on | 1) System mode is not set to Heat/Auto or setpoint is set too low
2) Delta “On” for heating is set too high 3) Minimum off time delay is being enforced 4) Heating system may need service |
1) Select the correct system mode and/or raise the setpoint
2) Change the delta “On” setting for heating mode 3) Intended operation; if objectionable, change Control Response settings in the Installers Settings, Comfort Settings Menu 4) Check/repair system |
Heating or Cooling is being displayed, but no air coming from registers/ vents | 1) Fan delay time has not expired
2) System is not operating properly |
1) Wait one minute for blower delay to end, then recheck register/grills
2) Check/repair system |
Fan runs all the time | 1) Fan mode is set to “On” or “Circ”
2) System is not operating properly |
1) Intended operation; if objectionable, change fan mode to “Auto”
2) Check/repair system |
Fan is set to “On” but not running | 1) Smart continuous fan (SCF) is enabled and the indoor humidity is higher than the cooling target RH (SCF will be displayed on fan mode button)
2) System is not operating properly |
1) Intended operation; if objectionable, disable SCF or raise cooling target humidity
2) Check/repair system |
FCC NOTICE
INFORMATION TO USER
TCONT724A542DAB
Contains Transmitter Module FCC ID: TLZ-CU300
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
This equipment has been tested and found to comply with the limits for Class B Digital Device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures.
- Reorient or relocate the receiving antenna
- Increase the separation between the equipment and receiver
- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected
- Consult the dealer or an experienced radio/TV technician for help
Any changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.
IC Notice
Contains Transmitter Module IC ID: 6100A-CU300
This device complies with Industry Canada license-exempt RSS standard(s). Operation is subject to the following two conditions: (1) this device may not cause interference, and (2) this device must accept any interference, including interference that may cause undesired operation of the device.
Trane – by Trane Technologies (NYSE: TT), a global climate innovator – creates comfortable, energy efficient indoor environments for commercial and residential applications. For more information, please visit trane.com or tranetechnologies.com.
Trane has a policy of continuous data improvement and it reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.
Representative-only illustrations included in this document.
Doc Number: 18-HD82D1-1E-EN 16 September 2021
Supersedes: 18-HD82D1-1D-EN 06 August 2020
REFERENCE:
Download Manual:
Trane XR724 Smart Control Thermostat User Guide
Leave a Reply