Terneo KT SMART Thermostat Installation Manual

Terneo-logo

Terneo KT SMART Thermostat

Terneo-KT-SMART-Thermostat-product

Terneo kt thermostat is designed for the organization of snow and ice melting systems, which ensure the safety of people and vehicles, as well as reduce damage to buildings in the winter period. When the readings of the air temperature sensor are within the range of +5…–10 ° (adjustable), the thermostat turns on the load.

IN THE BOX

  • Thermostat: 1 piece
  • Temperature sensor with connected sensor: 1 piece
  • Technical data sheet and installation and operation manual: 1 piece
  • The packing box: 1 piece

TECHNICAL DATA

The limits of regulation upper: 0…10 °С

lower: –20…–1 °С

Maximum load current (for category AC-1) 16 А
Rated load capacity (for category AC-1) 3 000 VА
Input voltage 230 V ±10 %
Weight in the complete set 0,18 kg ±10 %
Overall dimensions (w × h × d) 75 × 75 × 39 mm
Temperature sensor NTC thermo-resistor 10 kOhm 25 °C (R10)
The length of the sensor-connected cable 3 m
Number combinations under heat, at least 50 000 cycles
Number of combinations without heating, no less than 20 000 000 cycles
Degree of protection GOST14254 IP20
Measured temperature range –30…+90 °С

IMPORTANT: Before the installation and operation of the device, please read by the end of this ocument. This will help to avoid possible danger, mistakes and misunderstandings.

WIRING

Terneo-KT-SMART-Thermostat-fig-1

Terneo-KT-SMART-Thermostat-fig-2

  • Thermostat supports two types of sensors: analog sensor (R10) or digital sensor (D18).
  • Analog sensor is connected to terminals 1 and 2. Wires colors are of no importance.
  • Digital sensor is connected to terminal 1 using white wire and to terminal 2 using blue wire. In case of incorrect connection, the thermostat will switch to percentage control mode.
  • Power voltage (230 V ± 10 %, 50 Hz) is supplied to terminals 4 and 5, at that phase (L) is determined by indicator and is connected to terminal 5, and neutral (N) — to terminal 4.

RELIABILITY OF THE POWER RELAY provides protection against frequent switching in the thermostat. If there was less than 1 minute between relay switching, the relay activation will be delayed, marking the countdown with a flashing dot.

IN THE CASE OF INCORRECT WIRING, is possible failure of the thermostat. Make sure that external sensor and mains voltage are connected correctly.

INSTALLATION

The thermostat is designed for indoor installation. The ingress risk of moisture or liquid into the place of installation must be minimized. When installed in a bathroom, toilet, kitchen, swimming pool the thermostats should be installed at the place out of reach of casual spraying. The ambient temperature during installation must be between -5 .. + 45 °C. The installation height of the thermostat should be in the range 0,4…1,7 m above the floor level. The thermostat is mounted and connected after the installation and load testing. To protect against short-circuit in the load circuit the circuit breaker (CB) has to be installed before installing the thermostat. The circuit breaker is installed in the gap of phase conductor, as shown in Wiring 1. It should be designed for not more than 16 A.

To protect a people against electric shock leakage is installed the SSD (safety shutdown device). This event is obligatory when installing floor heating in wet areas. For working of SSF the heating cable screen must be grounded (connected to the protective conductor PE) or, if there is a two-wire network, it is necessary to make protective neutral earthing. That is to connect the screen to a zero before SSF. In Wiring 1 protective neutral earthing is shown with a dotted line.

The thermostat is mounted in the standard mounting box 60 mm in diameter, with mounting screws.

For installation, vou must

  • make a hole in the wall for box mounting and wall chase for power wires and the sensor;
  • ake the power wires of the heating system and the sensor to the mounting box;
  • perform the compounds according to the passport data;
  • fix the thermostat in the mounting box. To this a front frame must be removed. Put the thermostat in the mounting box and tighten the mounting screws.

The thermostat terminals are designed for a wire with section not more than 2.5 mm?. To reduce the mechanical loads on the terminals it is desirable to use a soft wire. The ends of the wires must be cleaned and crimped with ferrules with insulation. The wires are tightened in the terminals using a screwdriver with a blade width no more than 3 mm. A screwdriver with a blade width more than 3 mm can cause mechanical damage to the terminals. This may result in the loss of right for warranty. The terminals should be tightened with torque 0,5 N-m.

It is necessary for the temperature controller to switch the current to no more than 2/3 of the maximum current specified in the specification. If the current exceeds this value, the load must be connected through a contactor (magnetic actuator, power relay), which is optimized for this current (Wiring 2). The sections of the wires, which is connected to the thermostat, must be at least: copper 2 × 1,0 mm. The use of aluminum is not desirable.

Mounting the sensor

Terneo-KT-SMART-Thermostat-fig-3

Air temperature sensor should be mounted on the wall or under the edge of the roof in order to ensure its protection from direct sunlight, rain and snow, and ensure the opportunity for easy replacement in the event of a malfunction or damage (Figure 1). If necessary, it is allowed to shorten and expand sensor connecting wires (separate cable not more than 40 m long with a cross-section greater than 0,75 mm ). Power wires should not be placed near connection wire of sensor. otherwise they may cause interference.

WARRANTY TERMS

  • The warranty for devices is valid for terneo 36 months  from the date of sale, provided that the instructions are followed. The warranty period for products without a warranty certificate is counted from the date of production.
  • If your device is not working properly, we recommend that you first read the section «Possible problems». If you cannot find an answer, contact Service Center. In most cases, these actions resolve all issues. If you continue to have issues with the device, please send it to a Service Center or to the store where you purchased the device. If your device is defective due to our fault, we will repair or replace it under warranty within 14 business days.
  • Please see the full text of the warranty and the data you need to send to your Service Center on the website https://www.ds-electronics.com.ua/en/. If you have a warranty case, please, contact the General distributor in your area.

WARRANTY CARD

Terneo-KT-SMART-Thermostat-fig-4

EXPLOITATION

To view the menu items, hold down the « Terneo-KT-SMART-Thermostat-fig-16 » button for a certain number of seconds (see Table 1). Use « Terneo-KT-SMART-Thermostat-fig-10 » and «Terneo-KT-SMART-Thermostat-fig-11 » to change parameters. Upon first press – the parameter flashes, the second press – it is available for modification. 3 seconds after pressing the thermostat returns to the display of the current temperature. In the waiting mode (when the buttons aren’t currently being used the brightness of the indicator and the screen will be reduced to 30 %.

Preset temperature

(factory settings: upper limit 5 °C; lower limit –10 °C)

To view the upper limit, press the button Terneo-KT-SMART-Thermostat-fig-10and to view the lower limit press – Terneo-KT-SMART-Thermostat-fig-11. Use the Terneo-KT-SMART-Thermostat-fig-10orTerneo-KT-SMART-Thermostat-fig-11 buttons to change the flashing value. If the temperature of the sensor is within the set limits, the heater will turn on and the red indicator will light up.

Switching to sleep mode

  • Terneo-KT-SMART-Thermostat-fig-5Hold down the «Terneo-KT-SMART-Thermostat-fig-12» button for 4 seconds (three dashes will appear on the screen one after the other) until «OFF» appears on the screen. To turn it off completely, you need to turn off the automatic switch.
  • Terneo-KT-SMART-Thermostat-fig-6To exit sleep mode, also hold the « Terneo-KT-SMART-Thermostat-fig-12 » button for 4 seconds until «on» appears on the screen.

Button blocking

(child and public protection)

  • Terneo-KT-SMART-Thermostat-fig-7In order to enable /disable button blocking press the «Terneo-KT-SMART-Thermostat-fig-16» and « Terneo-KT-SMART-Thermostat-fig-12 » buttons at the same time for 6 seconds till the «Loc» («oFF») sign appears on the screen.

Table 1: FUNCTION MENU

Terneo-KT-SMART-Thermostat-fig-17

POSSIBLE PROBLEMS, CAUSES AND WAYS TO OVERCOME THEM

While load is running, the screen shows «ЗНЕ»

  • Terneo-KT-SMART-Thermostat-fig-18Possible cause: short circuit in the sensor circuit.
  • It is necessary: remove short circuit in the sensor circuit.
  • Otherwise, heating temperature control is unavailable.

While the load is running, the screen displays «OTerneo-KT-SMART-Thermostat-fig-19»

  • Terneo-KT-SMART-Thermostat-fig-9The thermostat has switched to the percentage load control mode.
  • Possible cause: incorrect connection, damage to the sensor circuit, or the temperature has exceeded the measurement limits (–30…+90 °C).
  • It is necessary: to check the place of connection of the temperature sensor to the thermostat and its circuit, the absence of mechanical damage along the entire length of the connecting wire, as well as the absence of power wires that are laid close.
  • Operation of Interest Management Mode: This mode will ensure the operation of the heated floor in the event of damage to the sensor: in a 30-minute cyclic interval, the load is turned on for set time and it is turned off the rest of the time. The load operating time percentage can be set within a range from 0 to 90% using the «Terneo-KT-SMART-Thermostat-fig-10» or «Terneo-KT-SMART-Thermostat-fig-11» buttons.
  • When the load is turned on for the first time, the percentage of the load’s operating time is equal to 0% «ОTerneo-KT-SMART-Thermostat-fig-19». If you set 50% «50Terneo-KT-SMART-Thermostat-fig-19», the load will be on for 15 minutes in a 30-minute time interval.
  • Heating temperature control is not available in this mode.

Load is off, screen and indicator are off

  • Possible cause: No power supply.
  • It is necessary: make sure that the supply voltage is available. If power supply is available, contact the Service Center.

The load does not work, theTerneo-KT-SMART-Thermostat-fig-20 flashes on the screen

  • Terneo-KT-SMART-Thermostat-fig-13The temperature inside the housing exceeded 8 °C, the protection against internal overheating worked.
  • Possible cause: internal overheating of the thermostat, which can be caused by: poor contact in the terminals of the thermostat, high ambient temperature, exceeding the power of the switching load, or the cross section of the wires for connection is incorrectly selected.
  • It is necessary: to check the tightening of power wires in the terminals of the thermostat, make sure that the switching load power does not exceed the permissible one, the cross section of the wires for connection are selected correctly.
  • Features of the protection against internal overheating: when the temperature inside the housing drops below 80 °C, the thermostat will resume operation. When the protection is triggered more than 5 times in a row, the thermostat will be blocked until the temperature inside the housing drops below 0 °C and one of the buttons is pressed.

Every 5 seconds the screen displays «Ert»

  • Terneo-KT-SMART-Thermostat-fig-14Possible cause: is a break or short circuit of the internal overheating sensor. Internal overheating is not monitored.
  • It is necessary: to send the thermostat to the service center.
  • Otherwise, overheating control will not be carried out.

ADDITIONAL INFORMATION

  • Do not fire and do not throw away the device with the household waste.
  • After the end of its service life, the product must be disposed of in accordance with applicable law.
  • Transportation of goods carried in the package, ensuring the safety of the product.
  • The devi e is transported by any kind of transport (rail, sea, motor, air transportation).
  • Date of manufacture is on the back side of device. Application time is unlimited.
  • The device does not contain harmful substances.
  • If you have any questions or you something will not clear, call the Service centre the telephone number listed below.

Таble 2: RESISTANCE OF EXTERNAL TEMPERATURE SENSOR at different ambient temperatures

Terneo-KT-SMART-Thermostat-fig-21

SAFETY INSTRUCTIONS

  • Carefully read and become aware of yourself these instructions.
  • Connection of the device must be done by a qualified electrician.
  • Do not connect 230 V mains voltage instead of the sensor (it leads to failure of the thermostat).
  • Before the installation (dismantling) and connection (disconnection) of the device, turn off voltage supply and also act according to the «Rules of an arrangement of electric installations».
  • Do not immerse the sensor with a connecting wire in the liquid medium.
  • Do not switch the non assembled device to the network.
  • Turning on and off or and configure the device should be with dry hands.
  • Do not connect the device to the network disassembled.
  • Avoid hitting of water or moisture to the device.
  • Do not expose the device to extreme temperatures (higher than 40 ºС or below –5 °C) and high humidity.
  • Never clean the device with the use of chemicals such as benzene, solvents.
  • Do not store the device and do not use it in areas with the dust.
  • Do not attempt to disassemble and repair the device.
  • Do not exceed the landmarks value adaptor and power.
  • To protect against overvoltage caused by lightning discharges, use a lightning protector.
  • Protect the children from games with the working device, it is dangerous.

vс25_220926

Low Voltage Directive: 2014/35/EU
EMC Directive: 2014/30/EU

Terneo-KT-SMART-Thermostat-fig-15

Contacts

Manufacturer and vendor: DS ELECTRONICS, LTD

SERVICE CENTER CONTACT

Reference

Download Manual:

Terneo KT SMART Thermostat Installation Manual

Terneo-logo

Terneo KT SMART Thermostat Installation Manual


Posted

in

by

Comments

Leave a Reply

Your email address will not be published. Required fields are marked *

To respond on your own website, enter the URL of your response which should contain a link to this post’s permalink URL. Your response will then appear (possibly after moderation) on this page. Want to update or remove your response? Update or delete your post and re-enter your post’s URL again. (Find out more about Webmentions.)