tekmar Q 552 Programmable Thermostat
- Location
- Remove Mounting Base
- Install Mounting Base
- Switch Settings
Switch Position Action
ON LOCK Access level adjustment is not available.
OFF UNLOCK Access level adjustment is available.
Wiring
Install Thermostat
User Interface
Critical Settings
For a full list of settings and operational details, please refer to the thermostat Installation and Operation Manual (D552) included with compatible tekmarNet® controls or download the brochure from www.tekmarcontrols.com
The following settings are essential to the successful operation of the system.
Step 1: Set switch setting #1 and tekmarNet® system control located in the mechanical room to Unlock to change Access level to Installer. Return to Lock setting once installation has been completed.
Step 2: Press and hold “Home” button for 3 seconds to enter programming menus.
Step 3: Touch NEXT to locate the Setup Menu and touch ENTER.
Setup Menu Settings |
SENSOR 1
Select to the type of sensor connected to auxiliary sensor input 1. |
Range: OFF, ROOM, FLOR (floor), OUT (outdoor) |
Default: OFF |
SENSOR 2
Select to the type of sensor connected to auxiliary sensor input 2. |
Range: OFF, ROOM, FLOR (floor) |
Default: OFF |
ROOM SENSOR
Select whether the built-in room temperature sensor is on or off. |
Range: OFF or ON |
Default: ON |
W1 TERMINAL UNIT
Select the terminal unit type of the first stage of heat W1. |
Range: CTRL, HRF1, HRF2, CONV, COIL, OTHR |
Default: CTRL |
Setup Menu Settings |
W1 PUMP
Select whether the boiler system pump or mix system pump on a tekmarNet® system control should operate while the first stage of heat W1 is operating. |
Range: OFF or ON |
Default: ON |
W1 THERMAL MOTOR
Select whether the first stage of heat W1 operates a thermally actuated zone valve (wax actuator). When set to ON, there is a 3 minute delay before operating the pump and any heat sources. |
Range: OFF or ON |
Default: OFF |
W CYCLES PER HOUR
Select the number of heating cycles per hour. Only available when the thermostat is not connected to a tekmarNet® System Control. |
Range: SYNC, AUTO, 2 to 12 |
Default: SYNC |
tekmar Control Systems Ltd., Canada, tekmar Control Systems, Inc., U.S.A. Head Offi ce: 5100 Silver Star Road, Vernon, B.C. Canada V1B 3K4, 250-545-7749, Fax. 250-545-0650 Web Site: www.tekmarcontrols.comProduct design, software and literature are Copyright © 2011 by: tekmar Control Systems Ltd. and tekmar Control Systems, Inc.All specifications are subject to change without notice. Printed in Canada. Q 552 – 11/11.
Reference
Download Manual: