Tekmar 557 Thermostat
Location
Install Thermostat
Switch Settings
Switch | Position | Action |
1 | ON | LOCK Access level adjustment is not available. |
OFF | UNLOCK Access level adjustment is available. | |
2 | Not Used |
Stand Alone Wiring
For tekmarNet®2 or 4 wiring, see Application Brochure 557_A or Installation & Operation Manual 557_D.
User Interface
Critical Settings
The following settings are essential to the successful operation of the system.
- Step 1: Set switch setting #1 and tekmarNet® system control located in the mechanical room to Unlock to change Access level to Installer. Return to Lock setting once installation has been completed.
- Step 2: Press and hold “Home” button for 3 seconds to enter programming menus.
- Step 3: Touch NEXT to locate the Setup Menu and touch ENTER.
Setup Menu Settings |
SENSOR 1
Select the type of sensor connected to auxiliary sensor input 1. |
Range: OFF, ROOM, FLOR (floor), DUCT |
Default: OFF |
SENSOR 2
Select the type of sensor connected to auxiliary sensor input 2. |
Range: OFF, ROOM, FLOR (floor), OUT (outdoor) |
Default: OFF |
SENSOR 3
Select the type of sensor connected to auxiliary sensor input 3. |
Range: OFF, ROOM, FLOR (floor), HUM (humidity) |
Default: OFF |
ROOM SENSOR
Select if the built-in room temperature sensor is on or off. |
Range: OFF or ON |
Default: ON |
W1 TERMINAL UNIT
Select the terminal unit type of the first stage of heat W1. |
Range: NONE, HRF1, HRF2, OTHR (other) |
Default: NONE |
Setup Menu Settings |
BACKUP W2 TERMINAL UNIT
Select the type of backup heating. |
Range: NONE, CONV, COIL, FURN (furnace), OTHR (other) |
Default: NONE |
Y1 RELAY
Select the cooling equipment the Y1 relay operates. |
Range: HP1 (heat pump), AC1 (air conditioner), W2 |
Default: HP1 |
Y2 RELAY
Select the equipment the Y2 relay operates. |
Range: OFF, HP2 (heat pump stage 2), AC2 (air condi- tioner stage 2), HRV, DHUM (dehumidifier), VALV (valve) |
Default: OFF |
ACCESSORY RELAY
Select the equipment the accessory relay operates. |
Range: OFF, HUM (humidifier), DHUM (dehumidifier), VALV (valve) |
Default: OFF |
O/B VALVE
Select the heat pump operation of the O / B relay. |
Range: O or B |
Default: O |
For a full list of settings and operational details, please refer to the thermostat Installation and Operation Manual (557_D) included with compatible tekmarNet® controls or download the brochure from www.tekmarControls.com
tekmar Control Systems Ltd., A Watts Water Technologies Company. Head Offi ce: 5100 Silver Star Road, Vernon, B.C. Canada V1B 3K4, 250-545-7749,