Siemens-RDG20KN-Room-Thermostats-FEATURED

Siemens RDG20KN Room Thermostats Operating Instruction

Siemens-LOGO

Siemens RDG20KN Room Thermostats

Siemens-RDG20KN-Room-Thermostats-PRODUCT

RDG2..KN

  • Room thermostat with KNX communications allowing users to set ideal temperature, relative humidity and CO2 level (RDG204KN&RDG264KN). The thermostat offers the operating modes Comfort, Economy, and Protection.
  • In addition, it can operate in Auto mode as per a schedule via KNX bus or local.
  • The fan operates either in Auto mode or at the selected speed in Manual mode.
  • Users can either use the factory settings or adjust settings as desired.

Overview

Siemens-RDG20KN-Room-Thermostats-FIG-1

1: Main display

Siemens-RDG20KN-Room-Thermostats-FIG-2

Operating mode selection *
Scheduler
Fan speed selection
Escape
Delete schedule
Confirm parameters
Number of schedules or slave alarms
Outside temperature
Parameter
Digits for setpoint display
Time bar for schedule

Siemens-RDG20KN-Room-Thermostats-FIG-3

  • Additional user information, such as outside temperature, time of day from KNX bus, relative humidity, or indoor air quality
  • Morning: 12-hour format; Afternoon: 12-hour format
  • Relative humidity
  • Indoor air quality
  • Value with a thermometer: Digits for room temperature display

Siemens-RDG20KN-Room-Thermostats-FIG-4

  • Degrees Celsius or Fahrenheit
  • CO2 values

2: Operating mode

Siemens-RDG20KN-Room-Thermostats-FIG-5

  • Holiday mode
  • Protection mode
  • Economy mode
  • Comfort mode
  • Cooling mode
  • Electric heater active
  • Heating mode
  • Scheduler mode
  • Manual changeover
  • Auto mode
  • Temporary timer
  • Fault
  • Fresh air indication
  • Condensation in the room (dewpoint sensor active) or humidity control active
  • Button lock
  • Automatic fan
  • Fan speed I
  • Fan Speed II
  • Fan Speed III
  1. A. Operating mode button
  2. B. Fan mode button
  3. C. Rotary knob
  4. D. Green leaf
  5. E. Protection hospitality mode or scheduler button

When P002 = 3, the icon is displayed as Siemens-RDG20KN-Room-Thermostats-FIG-6and the button can be used to switch unit between °C and °F. (scan the above QR code for the latest version info).

Operating Instructions

Changing the room temperature

Siemens-RDG20KN-Room-Thermostats-FIG-7

  • Turn the rotary knob clockwise to increase, or counterclockwise to decrease the current room temperature setpoint.

Note: The setting range is 5…40 °C; it can be limited by parameters P013 and P016. (for parameter settings, see Control parameters).

Adjusting the fan speed

Siemens-RDG20KN-Room-Thermostats-FIG-8

  • Press the right button repeatedly until the desired fan mode is reached.
  • In Auto modeSiemens-RDG20KN-Room-Thermostats-FIG-9, the fan speed is automatically selected by the thermostat depending on the setpoint and current room temperature.
  • In Manual mode, the fan operates independently and runs at the speed set by the user: speed I / speed II / speed III.

Changing the operating mode

Siemens-RDG20KN-Room-Thermostats-FIG-10

  1. Comfort mode
    • In Comfort mode, the thermostat maintains the room temperature at the setpoint which can be adjusted with the rotary knob.
  2. Economy mode
    • In Economy mode, the thermostat maintains the room temperature at a lower or higher setpoint, thus saving energy and money.
    • The thermostat can be set to Economy mode either by pressing the operating mode button if enabled (P002 = 2), or via an external signal (switch or KNX bus command) such as keycard or presence detector.
    • The Economy setpoints are factory-set to 15 °C for heating and 30 °C for cooling. They can be adjusted via parameters P019 and P020 (for parameter settings, see Control parameters on page 2).
  3. Protection mode
    • In Protection mode, the thermostat stops operating. However, if the room temperature drops below 8 °C, heating is switched on to protect the room against frost.
    • The thermostat switches to Protection mode when the window contact (local or on KNX) is activated. The setpoints for Protection mode can be changed by your HVAC installer if desired:
    • Changes made by installer:Siemens-RDG20KN-Room-Thermostats-FIG-11 Frost protection: _________ ˚C Heating protection: __________˚C
  4. Auto mode
    • In Auto mode, the thermostat automatically switches over between Comfort and Economy mode as per the KNX bus or local schedule (enabled via P005).
    • If no schedule is available, Comfort replaces Auto.
    • Important: If setpoints are set to Off, there is no protective heating or cooling function. Risk of frost!

Green leaf indication

The green leaf indication is an energy-efficient setting and indicates the end user settings.

Siemens-RDG20KN-Room-Thermostats-FIG-12

  • Green leaf: Settings are within the preset energy-efficient range.Siemens-RDG20KN-Room-Thermostats-FIG-13
  • Red leaf: Settings exceed the preset energy efficiency range.
  • End users can press the red leaf and return to the energy-efficient range.

Reminder to clean filter, display of external faults

  • Siemens-RDG20KN-Room-Thermostats-FIG-14FIL: This message reminds you to clean the filter on your HVAC equipment.
  • Siemens-RDG20KN-Room-Thermostats-FIG-14AL1: It appears afterSiemens-RDG20KN-Room-Thermostats-FIG-11 _______ “fan operating hours” and disappears when the thermostat is manually set to Protection. These fault messages tell you an external fault has occurred **:
  • Siemens-RDG20KN-Room-Thermostats-FIG-14AL2: Siemens-RDG20KN-Room-Thermostats-FIG-14AL1 :Siemens-RDG20KN-Room-Thermostats-FIG-11 _______________________ Siemens-RDG20KN-Room-Thermostats-FIG-14AL2 :Siemens-RDG20KN-Room-Thermostats-FIG-11 __________________________
  • Siemens-RDG20KN-Room-Thermostats-FIG-14AL3: Siemens-RDG20KN-Room-Thermostats-FIG-14AL3 :Siemens-RDG20KN-Room-Thermostats-FIG-11 _______________________

Needs to be configured by the HVAC installer.

Scheduler

Set schedule

Siemens-RDG20KN-Room-Thermostats-FIG-15

  • Press button Siemens-RDG20KN-Room-Thermostats-FIG-22once and then turn the rotary knob or press button Siemens-RDG20KN-Room-Thermostats-FIG-22continuously to select programming mode PROG.
  • Press button Siemens-RDG20KN-Room-Thermostats-FIG-17once to enter scheduler modeSiemens-RDG20KN-Room-Thermostats-FIG-16.
  • Turn the rotary knob to select the weekday to be set, then press button Siemens-RDG20KN-Room-Thermostats-FIG-17once.
  • Turn the rotary knob to view existing schedules, then press button Siemens-RDG20KN-Room-Thermostats-FIG-17once to select the schedule that need to be edited.
  • Comfort mode setting of selected schedule and iconsSiemens-RDG20KN-Room-Thermostats-FIG-18 and Siemens-RDG20KN-Room-Thermostats-FIG-16are displayed, then press button Siemens-RDG20KN-Room-Thermostats-FIG-17once. The start time for Comfort flashes and can be changed by turning the rotary knob.
  • Press button Siemens-RDG20KN-Room-Thermostats-FIG-17once to confirm the adjusted value and enter the Economy mode setting for the schedule. Icons Siemens-RDG20KN-Room-Thermostats-FIG-30and Siemens-RDG20KN-Room-Thermostats-FIG-16are displayed, then press button Siemens-RDG20KN-Room-Thermostats-FIG-17once. The start time for Economy flashes and can be changed by turning the rotary knob.
  • Press button Siemens-RDG20KN-Room-Thermostats-FIG-17once to confirm the adjusted value. Then users can view other schedules by turning the rotary knob and enter other schedule settings (same as edited schedule).

Note: User can press button Siemens-RDG20KN-Room-Thermostats-FIG-19to delete any schedule or Siemens-RDG20KN-Room-Thermostats-FIG-20(Esc) to cancel the change. The maximum number of set schedule is three per day.

Set TIME

Siemens-RDG20KN-Room-Thermostats-FIG-21

  • Press button Siemens-RDG20KN-Room-Thermostats-FIG-22once and then turn the rotary knob or press button Siemens-RDG20KN-Room-Thermostats-FIG-22continuously to select programming mode TIME.
  • Press buttonSiemens-RDG20KN-Room-Thermostats-FIG-17 once and then turn the rotary knob to select time format (12H).
  • Press button Siemens-RDG20KN-Room-Thermostats-FIG-17once and then turn the rotary knob to select AM or PM.
  • Press button Siemens-RDG20KN-Room-Thermostats-FIG-17once and enter the hour setting.
  • The hour value flashes and can be changed by turning the rotary knob.
  • Press button Siemens-RDG20KN-Room-Thermostats-FIG-17once to confirm the adjusted value and enter the minutes setting.

Repeat the steps as for the hour.

Note: When time format is 24 h, AMPM is not displayed.

Set DATE

Siemens-RDG20KN-Room-Thermostats-FIG-23

  • Press button Siemens-RDG20KN-Room-Thermostats-FIG-22once and then turn the rotary knob or press button Siemens-RDG20KN-Room-Thermostats-FIG-22continuously to select programming mode DATE.
  • Press button Siemens-RDG20KN-Room-Thermostats-FIG-17once to enter date setting.
  • Turn the rotary knob to select month/weekday / year, then press button Siemens-RDG20KN-Room-Thermostats-FIG-17once.
  • For example, enter the year setting. The Year value flashes and can be changed by turning the rotary knob.
  • Press button Siemens-RDG20KN-Room-Thermostats-FIG-17to confirm the adjusted value, or Siemens-RDG20KN-Room-Thermostats-FIG-20(Esc) to cancel the change.

Repeat steps for month and weekday settings.

Set AWAY (Holiday mode)

Siemens-RDG20KN-Room-Thermostats-FIG-24

  • Press buttonSiemens-RDG20KN-Room-Thermostats-FIG-22 once and then turn the rotary knob or press button Siemens-RDG20KN-Room-Thermostats-FIG-22continuously to select programming mode AWAY. Holiday mode Siemens-RDG20KN-Room-Thermostats-FIG-31is displayed.
  • Press button Siemens-RDG20KN-Room-Thermostats-FIG-17once to enter scheduler modeSiemens-RDG20KN-Room-Thermostats-FIG-16.
  • Turn the rotary knob to adjust the holidays, then press button Siemens-RDG20KN-Room-Thermostats-FIG-17once.
  • Set the start time (AWAY): Set the month (MON) and then press button Siemens-RDG20KN-Room-Thermostats-FIG-17Siemens-RDG20KN-Room-Thermostats-FIG-32 Set the day (DAY)
  • Press button Siemens-RDG20KN-Room-Thermostats-FIG-17once to confirm the adjusted value; the idle page for Holiday mode is displayed once the start time reaches.

Button lock

  • Siemens-RDG20KN-Room-Thermostats-FIG-25If the button lock function is enabled (parameter P028 = 2), pressing the right button for 3 seconds locks or unlocks the buttons respectively. Locked buttons are indicated by the key symbolSiemens-RDG20KN-Room-Thermostats-FIG-26.
  • If “Auto lock” is configured (P028 = 1), the thermostat automatically locks the buttons 10 seconds after the last adjustment.

Commissioning (by qualified HVAC installer)

To adapt the thermostat to your system and optimize control performance, a number of control parameters can be adjusted. This can be done during operation, either via the buttons on the thermostat or via a commissioning tool.

Control parameters

Siemens-RDG20KN-Room-Thermostats-FIG-27

To change control parameters, proceed as follows:

  1. Press left and right buttons simultaneously for 3 seconds or until device beeps if the buzzer function is enabled (P030).
  2. Service level: Release and within 0.5…4 seconds, press the right button again until “P001” is displayed.
    • Expert level: Release and within 0.5…4 seconds, press the left button again until the temperature disappears.
    • Turn the rotary knob counterclockwise minimum ½ rotation. P050 displays.
  3. Select the required parameter by turning the rotary knob.
  4. Press button Siemens-RDG20KN-Room-Thermostats-FIG-17(OK). The current value of the selected parameter flashes and can be changed by turning the rotary knob.
  5. Press button Siemens-RDG20KN-Room-Thermostats-FIG-17(OK) to confirm the adjusted value, orSiemens-RDG20KN-Room-Thermostats-FIG-20 (Esc) to cancel the change.
    • To adjust additional parameters, repeat steps 3 through 5, or pressSiemens-RDG20KN-Room-Thermostats-FIG-20 (Esc) to quit parameter setting mode.

Note: If password protection (needs to be done by HVAC installer) is enabled, users must enter the password to open parameter setting mode. If the password is mistyped 5 times, the thermostat is locked and the password cannot be entered for 5 minutes.

Symbols Siemens-RDG20KN-Room-Thermostats-FIG-28and Siemens-RDG20KN-Room-Thermostats-FIG-26are displayed.

Parameter list

No. Description Factory setting Setting range Adj.

!

 

 

P001

 

 

Control sequence

2-pipe:
1 = Cooling only
4-pipe:
4 = Heating
and cooling
0 = Heating only 1 = Cooling only
2 = H/C changeover auto
3 = H/C changeover manual 4 = Heating and cooling
 

P002

Operation via room operating mode selector 1 1 = Auto *** – Protection / Auto – Comfort – Protection (when there is local scheduler)
2 = Auto *** – Comfort – Economy – Protection 3 = Auto *** (Comfort) – Protection Hospitality
 

P003

 

Operation via fan operating selector

 

0

0 = Auto – Manual 1 = Manual
2 = Auto – Manual – Protection 3 = Auto – Protection
P004 Unit 0 0 = °C (parameter in °C)
1 = °F (parameter in °F)
P005 Scheduler OFF ON = Enabled; OFF = Disabled
P006 Measured value correction 0 K -5…5 K
P007 Humidity value correction 0 -10…0…10 %
P008 Standard display 0 0 = Room temperature; 1 = Setpoint
 

 

 

P009

 

 

 

Additional display information

 

 

 

0

0 = — (No display) 1 = °C and °F
2 = Outside temperature 3 = Time of day (12 h)
4 = Time of day (24 h) 5 = Humidity
6 = Indoor air quality (numeric) ***** 7 = Indoor air quality (text) *****
8 = Humidity and IAQ (numeric) ***** 9 = Humidity and IAQ (text) *****
P010 Setpoint concept 1 1 = Comfort concept; 2 = Energy saving concept
P011 Comfort basic setpoint 21 °C (70 °F) 5…40 °C (41…104 °F)
P013 Comfort setpoint minimum 5 °C (41 °F) (P010 = 1): 5 °C (41 °F)…P016-1 K
(P010 = 2): 5 °C (41 °F)…P014-1 K
P014 Comfort setpoint maximum heating 21 °C (70 °F) P013+1 K…P015-1 K
P015 Comfort setpoint minimum cooling 25 °C (77 °F) P014+1 K…P016-1 K
P016 Comfort setpoint maximum 35 °C (95 °F) (P010 = 1): P013+1 K…40 °C (104 °F) (P010 = 2): P015+1 K…40 °C (104 °F)
P017 Summer time 1 OFF; 1 = Europe; 2 = Australia; 3 = New Zealand
P019 Economy heating setpoint 15 °C (59 °F) — (0), 5 °C…P020 (41 °F…P020)

P020 = 40 °C max. (P020 = 104 °F max.)

P020 Economy cooling setpoint 30 °C (86 °F) — (0), P019…40 °C (P019…104 °F)
P019 = 5 °C min. (P019 = 41 °F min.)
P023 Indoor air quality setpoint ***** 1000 ppm 10…2000 ppm
P024 Humidity setpoint high 50 — (0), P026 or 20…90 %
P026 Humidity setpoint low OFF — (0), 20…90 % or P024
P027

****

Electric heater when cooling ON ON = Enabled; OFF = Disabled

Siemens-RDG20KN-Room-Thermostats-FIG-33

 

P029

 

Fan: Dead zone Comfort mode

 

0

0 = Fan disable

1 = Low speed (Heat and Cool) 2 = Low speed (Cooling only) 3 = Fan disable Auto & Manual 4 = Low speed Auto & Manual

5 = Low speed Auto & Manual Cooling

P030 Buzzer function ON ON = Enabled; OFF = Disabled
 

 

P031

 

 

Language

 

 

1

1 = English; 2 = Francais (French)

3 = Deutsch (German); 4 = Italiano (Italian)

5 = Espanol (Spanish); 6 = Nederlands (Dutch) 7 = Turkce (Turkish); 8 = Cesky (Czech)

9 = Suomi (Finnish); 10 = Polski (Polish)

11 = Magyar (Hungarian); 12 = Slovenski (Slovak)

13 = (Limba) Romana (Romanian); 14 = Dansk (Danish) 15 = Norsk (Norwegian)

P032 Room operating mode holidays 0 0 = Economy; 1 = Protection
  • When no time schedule via KNX exists, Auto equals Comfort.
  • Parameter P027 is displayed only for application 2-pipe with an electric heater.
  • These parameter values are valid for RDG204KN and RDG264KN.

All temperature settings are in increments of 0.5 °C (except P006 of RDG204KN & RDG264KN is in 0.1 °C).

Siemens-RDG20KN-Room-Thermostats-FIG-11 Remember to record all changes!

Issued by

Siemens-RDG20KN-Room-Thermostats-FIG-34

© Siemens Switzerland Ltd, 2020
Technical specifications and availability are subject to change without notice.

REFERENCE:

DOWNLOAD MANUALS:

Siemens RDG20KN Room Thermostats Operating Instruction

Siemens-LOGO

Siemens RDG20KN Room Thermostats Operating Instruction

Comments

Leave a Reply

Your email address will not be published. Required fields are marked *