SIEMENS-RDE100.1-DHW-Programmable-Room-Thermostat-FEATURED

SIEMENS RDE100.1 DHW Programmable Room Thermostat Operating Instruction

Siemens-LOGO

SIEMENS RDE100.1 DHW Programmable Room Thermostat 

SIEMENS-RDE100.1-DHW-Programmable-Room-Thermostat-PRODUCT

Operating Instructions

RDE100.1DHW is a room thermostat that allows you to set the ideal room temperature at the time you want.
In addition, it offers independent control of DHW. There are several switching patterns available that can be set to your specific needs.

SIEMENS-RDE100.1-DHW-Programmable-Room-Thermostat-FIG.1

  1. Display
    • SIEMENS-RDE100.1-DHW-Programmable-Room-Thermostat-FIG.2Indicating that batteries need to be replaced
    • SIEMENS-RDE100.1-DHW-Programmable-Room-Thermostat-FIG.3Frost protection (heating) is active
    • SIEMENS-RDE100.1-DHW-Programmable-Room-Thermostat-FIG.4Auto Timer mode View and set Auto Time switch
    • SIEMENS-RDE100.1-DHW-Programmable-Room-Thermostat-FIG.5Comfort mode
    • SIEMENS-RDE100.1-DHW-Programmable-Room-Thermostat-FIG.6Economy mode
    • SIEMENS-RDE100.1-DHW-Programmable-Room-Thermostat-FIG.7Escape
    • SIEMENS-RDE100.1-DHW-Programmable-Room-Thermostat-FIG.8Display of time
    • SIEMENS-RDE100.1-DHW-Programmable-Room-Thermostat-FIG.9Permanent setpoint setting
    • SIEMENS-RDE100.1-DHW-Programmable-Room-Thermostat-FIG.10Day and time setting
    • SIEMENS-RDE100.1-DHW-Programmable-Room-Thermostat-FIG.11Holiday mode setting View and set DHW
    • SIEMENS-RDE100.1-DHW-Programmable-Room-Thermostat-FIG.12Auto Time switch DHW Auto Time switch activated
    • SIEMENS-RDE100.1-DHW-Programmable-Room-Thermostat-FIG.13Morning: 12-hour format
    • SIEMENS-RDE100.1-DHW-Programmable-Room-Thermostat-FIG.14Afternoon: 12-hour format
    • SIEMENS-RDE100.1-DHW-Programmable-Room-Thermostat-FIG.15Confirmation
    • SIEMENS-RDE100.1-DHW-Programmable-Room-Thermostat-FIG.16Room temperature in degrees Fahrenheit
    • SIEMENS-RDE100.1-DHW-Programmable-Room-Thermostat-FIG.17Room temperature in degrees Celsius
    • SIEMENS-RDE100.1-DHW-Programmable-Room-Thermostat-FIG.18Button lock activated
    • SIEMENS-RDE100.1-DHW-Programmable-Room-Thermostat-FIG.19Display of room temperature, setpoint, etc.
    • SIEMENS-RDE100.1-DHW-Programmable-Room-Thermostat-FIG.20Heating ON
    • SIEMENS-RDE100.1-DHW-Programmable-Room-Thermostat-FIG.21Weekday 1 = Monday 7 = Sunday
    • SIEMENS-RDE100.1-DHW-Programmable-Room-Thermostat-FIG.22Timer bar
    • SIEMENS-RDE100.1-DHW-Programmable-Room-Thermostat-FIG.23The actual room temperature
  2. Change operating mode
  3. Set
  4. Ok
  5. Decrease value
  6. Increase value
  7. DHW switch ON/AUTO/OFF button
  8. Battery holder

Do you want to adjust the time and day?

You can set the current time of day.

set ok

+

mode

Proceed as follows:

·        Press set and select

·        Press ok and the time flashes for setting

·        Press + or to adjust the time

·        Press ok to confirm

·        The weekday flashes, press + or to select the desired day

·        Press ok to save the value

·        Press mode to exit or wait for the program to exit automatically

Do you want to lock the buttons?

mode Press and hold mode for at least 7 seconds to activate a button lock. Repeat to unlock.

The unit operates normally when the buttons are locked, but no changes are possible while the buttons are locked.

Are your rooms too warm/too cold?

+

ok set

mode

Press + or to increase or decrease the room temperature setpoint in increments of 0.5 °C / 1 °F. Proceed as follows:

·        Press + or to adjust the setpoint temporarily. This adjustment is reset as soon as the operating mode changes.

·        Press ok, set or mode to save the value or wait for the program to exit automatically

·        To lock the setpoints, use parameters P06 and P08.

 

Do you want to change the operating mode?

mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

!

The thermostat provides Comfort mode, Economy mode, and Auto mode. Changeover between the operating modes can be made manually by pressing mode.

Comfort mode is the permanent (24 h) selection of Comfort. Select this mode to maintain Comfort temperature permanently without any time switch. It is used during occupancy periods, for example.

Economy mode is the permanent (24 h) selection of Economy. Select this mode to maintain the Economy temperature permanently without any time switch.

It is used during non-occupancy periods, for example at night.

AUTO In Auto timer mode, operating modes (Comfort, Economy) are changed automatically according to the time switch set.

 

Note:

Frost protection is a function always active in the background. As soon the room temperature falls below 5 ºC, the unit automatically activates the

heating  .

Do you want to set permanent temperature setpoints?

set ok

+

mode

 

 

 

!

·        Press set and select

·        Press ok to confirm

·        Press mode to select an operating mode, Comfort or Economy

·        Press + or to adjust the setpoint permanently.

·        Press ok to confirm

·        Press mode to exit or wait for the program to exit automatically

Note: This permanent setpoint is used during Auto timer mode.

Energy-saving tips without loss of comfort

  • Select Auto timer mode during the heating period, and set the time switch according to your normal habits at home
  • Select Economy mode or Holiday mode for long periods of non-occupancy and during summer period.

Do you want to set your Holiday mode?

set ok

+

mode

 

 

 

 

 

 

!

Use the Holiday mode to set the thermostat to a constant temperature while absent.

·        Press set and select

·        Press ok to confirm

·        Press + or to adjust the temperature setpoint

·        Press ok to confirm

·        Press + or to adjust the number of days for holidays (Note: 0 = Holiday mode OFF)

·        Press ok to save the value

·        When Holiday mode is activated, the remaining days are displayed on the screen

Note: If you press mode while Holiday mode is active, the function is turned off and the  symbol disappears.

If the Comfort and Economy setpoint values are both locked, the lowest locked setpoint value is the Holiday mode setpoint value. You can adjust the setpoint temperature from 5 ºC up to the lowest locked setpoint value.

Do you want to enter your own time switch?

Option 1: Time switch with individual day selection (P11=0)

set
ok
+

mode
You can select Comfort or Economy at 15 minute intervals throughout the day. The 0:00 to 24:00 hour time bar allows you to set the operating mode for the selected day(s).
Example:

SIEMENS-RDE100.1-DHW-Programmable-Room-Thermostat-FIG.24

  1. Visible bars: Control to Comfort temperature
  2. Invisible bars: Control to Economy temperature

When Auto timer mode is enabled, changeover between the operating modes is automatic after the settings are saved.
Proceed as follows:

  1. Press set and select AUTO.
  2. Press ok to confirm.
  3. Time switch for day Mon(1) is displayed.
  4. Press + or – to select the day, from Mon(1) to Sun(7).
  5. Press ok to confirm the selection and initiate time programming.
    During programming step:
  6. Press mode to select an operating mode, (Comfort or Economy) or
  7. Press + or – to adjust the time setpoint by 15 minutes for the selected mode.
  8. Press ok to save the time switch.
  9. Repeat steps 4-8 for all remaining days (if required);
    or
  10. Press mode or wait for the program to exit automatically.

Option 2: Time switch with the same 7 day selection (P11=1)

set ok

+

mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

You can set all the 7 day time switches at the same time.

Example:SIEMENS-RDE100.1-DHW-Programmable-Room-Thermostat-FIG.24

 Visible bars: Control to Comfort temperature

‚ Invisible bars: Control to Economy temperature

 Proceed as follows:

1) Set the parameter (P11=1). Please refer to the section “Do you want to change parameters“.

2) Press set and select AUTO.

3) Press ok to confirm.

4) Time switch for period Mon (1) – Sun (7) is displayed.

5) Press ok to initiate time programming.

 During programming step:

6) Press mode to select an operating mode, (Comfort or Economy) or

7) Press + or to adjust time setpoint by 15 minutes for the selected mode.

 8) Press ok to save the time switch.

9) Press mode or wait for the program to exit automatically.

Option 3: Time switch with 5-2 day selection (P11=2)

set ok

+

mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

You can set Monday – Friday time switch at once and Saturday – Sunday time switch at once.

Example:SIEMENS-RDE100.1-DHW-Programmable-Room-Thermostat-FIG.24

 Visible bars: Control to Comfort temperature

‚ Invisible bars: Control to Economy temperature

 

Proceed as follows:

1) Set the parameter (P11=2). Please refer to the section “Do you want to change parameters“.

2)  Press set and select AUTO.

3)  Press ok to confirm.

4)  Time switch for period Mon(1) – Fri(5) is displayed.

5)  Press + or to select the period, Mon (1) – Fri( 5) or Sat (6) – Sun (7).

6) Press ok to confirm the selected period and initiate time programming.

During programming step:

7) Press mode to select an operating mode, (Comfort or Economy) or

8) Press + or to adjust the time setpoint by 15 minutes for the selected mode.

9)  Press ok to save the time switch.

10) Repeat the steps 5-9 for the other period if necessary; or

11) Press mode or wait for the program to exit automatically.

Factory default for 7-day Time switch

Default value Day/s Comfort mode Economy mode
Mo (1) – Fr (5) 6:00 – 8:00 hr

17:00 – 22:00 hr

22:00 – 6:00 hr

8:00 – 17:00 hr

Sa (6) – Su (7) 7:00 – 22:00 hr 22:00 – 7:00 hr

Do you want to activate DHW control?

  • PressSIEMENS-RDE100.1-DHW-Programmable-Room-Thermostat-FIG.26 to switch on DHW heating
  • While DHW heating is switched on, theSIEMENS-RDE100.1-DHW-Programmable-Room-Thermostat-FIG.26symbol is displayed
  • PressSIEMENS-RDE100.1-DHW-Programmable-Room-Thermostat-FIG.26again
  • DHW is in the auto status, the AUTO symbol is displayed. DHW switches according to the DHW time switch.
    If you want to see the DHW time bar, press and holdSIEMENS-RDE100.1-DHW-Programmable-Room-Thermostat-FIG.26for 5 seconds. The time bar flashes to show the programmed DHW times. The timeout of the DHW timer bar is set with parameter P13
  • Press SIEMENS-RDE100.1-DHW-Programmable-Room-Thermostat-FIG.26again
  • DHW heating is switched off and the symbol disappears
    DHW can also be switched on/off while frost protection is active.

Do you want to enter your own time switch for DHW control?

SIEMENS-RDE100.1-DHW-Programmable-Room-Thermostat-FIG.26

set

ok

You can enter the DHW Auto Time switch as follows:

·       Press set and select AUTO , then press ok You can select DHW on or off for every 15 minutes interval of the day. The 0:00 to 24:00 hour time bar

allows you to set DHW on or off for the selected day(s).

Example:

SIEMENS-RDE100.1-DHW-Programmable-Room-Thermostat-FIG.24

 Visible bars: DHW control is switched on

‚ Invisible bars: DHW control is switched off

There are 3 options for DHW Time switch setting: Individual day, 7 day and 5/2 day.

To set the DHW Time switch, please follow the same steps as in the section “Do you want to enter your

own time switch“.

Factory default of 7-day time switch for DHW

Default value Day/s DHW control ON DHW control OFF
Mo (1) – Fr (5) 6:00 – 8:00 hr

17:00 – 22:00 hr

22:00 – 6:00 hr

8:00 – 17:00 hr

Sa (6) – Su (7) 7:00 – 22:00 hr 22:00 – 7:00 hr

Does symbol SIEMENS-RDE100.1-DHW-Programmable-Room-Thermostat-FIG.2appear on the display?

SymbolSIEMENS-RDE100.1-DHW-Programmable-Room-Thermostat-FIG.2is displayed when the batteries are low. Replace them with 2 new alkaline batteries type AAA. Proceed as follows:

  • Get 2 new alkaline batteries type AAA
  • Remove the battery holder, then the batteries, insert the new batteries and, within 1.5 minutes, replace the battery holder
  • Ensure the exhausted batteries are disposed of correctly, in compliance with environmental requirements

Do you want to change the parameters?

+

ok mode

If you want to change control parameters, proceed as follows:

·        Press + and simultaneously for 5 seconds

·        Release them and parameter “P01” is displayed on the bottom segment

·        Press + or to scroll to the parameter that needs to be adjusted

·        Press ok to select this parameter

·        Press + or to adjust the value

·        Press ok to confirm the adjusted value

·        Press mode to exit the parameters without saving or wait for the program to exit automatically

Parameter list

Parameter no. Description Setting range (default)
P01 Time format 1 = 24:00 hours (default)

2 = 12:00 AM/PM

P02 Selection of °C or °F 1 = °C (default)

2 = °F

P03 Standard temperature display 1 = room temperature (default)

2 = setpoint

P04 Temperature sensor calibration -3…3 °C

Step 0.5 °C

(-6…6 °F, step 1 °F) Default: 0 °C

P06 Comfort setpoint lock 0 = OFF (default)

1 = ON à locked according to setting in permanent temperature setpoint

P08 Economy setpoint lock 0 = OFF (default)

1 = ON à locked according to setting in permanent temperature setpoint

P09 Buzzer 0 = OFF

1 = ON (default)

P10 Show frost protection icon 0 = OFF (default)

1 = ON

P11 Time switch type for autotimer and DHW 0 = individual Days (default) 1= all 7 days

2= 5/2 days

P12 Periodic pump run 0 = OFF (default)

1 = ON

P13 DHW timer bar timeout 0 = no DHW bar

1 = 1 minute (default)

2 = 2 minutes

Adjustable range 0 to 15 minutes

P21 Button scanning rate for the capacitive buttons

Note: a higher scanning rate means shorter battery life.

0.2 = 0.25 s

0.5 = 0.5 s

1.0 = 1.0 s (default) 1.5 = 1.5 s

P22 Reload factory settings 0 = OFF (default)

1 = reload

P23 Software version information No adjustment possible
P78 Control behavior 0 = On/Off, 1.0K

1 = On/Off, 0.3K 2 = TPI fast

3 = TPI medium

4 = TPI slow (default)

P89 Forward shift on max 0, 0.5,…24 h

Default: 0 h

P90 Early shutdown max 0, 0.5,…6 h

Default: 0 h