INSTALLATION

WARNING!

The device is designed to be installed in a standard recess (or wall) mounted junction box with two modules or else directly on the wall using the screw anchors provided.

To install the device perform the following steps

  1. Push, with the help of a screwdriver, the plastic tooth located in the slot on the bottom side, then slightly lift up the plastic cover
  2. Lift up the cover, while pressing it slightly, until it is fully extracted
  3. Fix the base directly on a wall or on 2-modules wiring boxes through the two screws seats with 60 mm wheelbase paying attention to push the cables through the hole
  4. Make the electrical wirings following the connection diagrams
  5. The power supply must be connected to the ‘E’ terminal while the load must be connected to the ‘F’ terminal
  6. Connect the optional remote sensor to the ‘G’ connector
    WARNING
    1. The outputs, terminals 3, 4 and 5, are tension-free and insulated with double insulation from the other parts of the thermostat.
    2. So, it is possible to power the thermostat with a low tension SELV (24V~) and, at the same time, control a load at a high tension (230V~).
    3. In this case, it is necessary to keep a separation between the remote sensor cables, power cables and the load wires, according to the current standards. In particular, it is necessary to fix the group of cables with cable ties separating the SELV wires from the others to avoid that if a wire gets disconnected accidentally, this won’t reduce the insulation towards SELV
  7. Close the thermostat as follows:
    1. Match the two teeth located in the upper side of the plastic base with the two slots located on the plastic cover.
    2. Close the upper side of the cover while, at the same time, slightly press with a finger, the plastic tooth located on the bottom side of the base making it lean towards the inner side of the thermostat
      Complete the insertion of the cover until the plastic tooth on the base snaps into position
  8. Turn on the thermostat and configure it (see ‘SETTING USER PARAMETERS’) section.

DESCRIPTION OF CONTROLS

KEY:

DISPLAY INDICATIONS

The meaning of the symbols appearing on the display is given below:

seitron- TAD022- Taddy- Digital- Room- Thermostat-5

OVERVIEW

STARTING UP

When starting up for the first time:

Regulation mode set-up

Comfort and Economy temperatures regulation

Temperature display

Switching off – Antifrost function

Backlighting

The display backlight turns on whenever any button is pressed. It turns off automatically 20 seconds after the last press of a button.

TECHNICAL CHARACTERISTICS

Internal sensor

Remote probe (optional)

CLASSIFICATION UNDER REG. 2013.811.EC

DIMENSIONS
seitron- TAD022- Taddy- Digital- Room- Thermostat-16

SETTING USER PARAMETERS

To enter the setting mode of the thermostat parameters, proceed as follows:

  1. Keep pressed for more than 10 seconds the key ‘ seitron- TAD022- Taddy- Digital- Room- Thermostat-3  ‘; the display shows the icon ‘ seitron- TAD022- Taddy- Digital- Room- Thermostat-(6) ’ and the first user parameter ‘ AFr ‘.
  2. Press the keys ‘ seitron- TAD022- Taddy- Digital- Room- Thermostat- 2  ‘ and ’ seitron- TAD022- Taddy- Digital- Room- Thermostat-3 ’ to scroll among the user parameters:
    1. Antifrost Setting ‘ AFr ’
    2. Internal sensor Offset setting ‘ OFS1 ’
    3. Remote sensor Offset setting ‘ OFS2 ’
    4. Regulation sensor setting ‘ rEG ’
    5. Hysteresis setting ‘ HYS ’
    6. Heating / Cooling setting ‘ H_C ’
    7. Minimum relay activation time setup ‘ t_SA ’
    8. Reset to default data ‘ diet ’
  3. Push the key ‘ seitron- TAD022- Taddy- Digital- Room- Thermostat-3 ‘ to enter the settings of the selected parameter; the display shows the blinking icon ‘ seitron- TAD022- Taddy- Digital- Room- Thermostat-(6) ’.
  4. Configure the data associated with each individual parameter as illustrated below.
  5. Push the key ‘  seitron- TAD022- Taddy- Digital- Room- Thermostat-3‘ to exit from the settings of the selected parameter; every change is automatically stored in memory.
  6. To exit the user parameter programming mode, press the ‘seitron- TAD022- Taddy- Digital- Room- Thermostat-17 ’ button to confirm the changes made, or else wait 10 seconds without pressing any button

‘AFr’ ANTIFROST SETTING

The Antifrost function allows you to select a minimum temperature to be maintained when the thermostat is off, so as to protect both the room and the equipment when the room temperature falls below the set value. The device comes with a factory default with the Antifrost function set to 6°C.

IMPORTANT: This function is active only when the device has been set to heating mode.

To set the Antifrost temperature, carry out the following steps:

  1. Select the parameter ‘ AFr ’ and press the ‘ seitron- TAD022- Taddy- Digital- Room- Thermostat-3‘ button.
  2. The display will show the previously set Antifrost temperature.
  3. Press buttons ‘ seitron- TAD022- Taddy- Digital- Room- Thermostat- 2  ‘ and ’ seitron- TAD022- Taddy- Digital- Room- Thermostat-(1) ’ to change the setting (between OFF, 0.5°C..25°C); every change will be automatically stored in memory.
  4. Push the key ‘ seitron- TAD022- Taddy- Digital- Room- Thermostat-3 ‘ to exit from the settings of the selected parameter. To exit from the programmation of the user parameters, push the key ‘ seitron- TAD022- Taddy- Digital- Room- Thermostat-17 ’ or wait 10 seconds without pushing any key

‘OFS1’ INTERNAL SENSOR OFFSET SETTING
With this parameter, it is possible to correct the temperature reading of the internal sensor by ±9.9°C in order to correct any systematic reading errors due to the placement of the thermostat in areas unsuitable for measuring the room temperature. The device leaves the factory with the Offset set at 0.0°C. To set the Offset value for the internal sensor, perform the following steps:

  1. Select the ‘ OFS1 ’ parameter and press the ‘ ‘ button.
  2. The display will show the previously set Offset temperature.
  3. Press buttons ‘ ‘ and ’ ’ to modify the setting (range: -9.9°C .. +9.9°C); every change will be automatically stored in memory.
  4. Push the key ‘ ‘ to exit from the settings of the selected parameter. To exit from the programmation of the user parameters, push the key ‘ ’ or wait 10 seconds without pushing any key.

‘OFS2’ REMOTE SENSOR OFFSET SETTING
With this parameter, it is possible to correct the temperature reading of the remote sensor by ±9.9°C in order to correct any systematic reading errors due to the positioning of the remote sensor in areas unsuitable for measuring the room temperature. The device comes with a factory default Offset at 0.0°C. To regulate the Offset value for the remote sensor, perform the following steps:

  1. Select the ‘ OFS2 ’ parameter and press the ‘ seitron- TAD022- Taddy- Digital- Room- Thermostat-3 ‘ button.
  2. The display will show the previously set Offset temperature.
  3. Press buttons ‘  seitron- TAD022- Taddy- Digital- Room- Thermostat- 2 ‘ and ’ seitron- TAD022- Taddy- Digital- Room- Thermostat-(1) ’ to modify the setting (range: -9.9°C .. +9.9°C); every change will be automatically stored in memory.
  4. Push the key ‘  seitron- TAD022- Taddy- Digital- Room- Thermostat-3‘ to exit from the settings of the selected parameter. To exit from the programmation of the user parameters, push the key ‘ seitron- TAD022- Taddy- Digital- Room- Thermostat-17 ’ or wait 10 seconds without pushing any key.

WARNING: The function is active only if the parameter ‘ rEG ’ is set on ‘ EHt ‘.

REGULATION SENSOR CHOICE SETTING
This parameter sets whether the room temperature regulation is made based on the thermostat’s internal sensor or the remote sensor wired to the connector of Fig. 8. The device comes with a factory default settings on the internal sensor (Int).

To switch back and forth between these two parameters, perform these operations:

  1. Select parameter ‘ rEG ’ then press key ‘ seitron- TAD022- Taddy- Digital- Room- Thermostat-3  ‘.
  2. The display shows ‘ Int ‘ or ‘ EHt ‘
  3. Press keys ‘ seitron- TAD022- Taddy- Digital- Room- Thermostat- 2  ‘ and ’ seitron- TAD022- Taddy- Digital- Room- Thermostat-(1) ’ to change the value (Int: internal sensor – EHt: remote sensor); each selection is automatically stored in memory.
  4. Push the key ‘ seitron- TAD022- Taddy- Digital- Room- Thermostat-3‘ to exit from the settings of the selected parameter. To exit from the programmation of the user parameters, push the key ‘ seitron- TAD022- Taddy- Digital- Room- Thermostat-17 ’ or wait 10 seconds without pushing any key.

WARNING: When the regulation is set according to the remote sensor ‘ EHt ‘ and in case this sensor is missing or broken, the temperature regulation will be performed according to the internal sensor, even if the parameter remains set on ‘ EHt

HYSTERESIS SETTING
This parameter sets the hysteresis, in °C, used in the temperature regulation. The device comes with factory default with the differential set at 0,2°C.

WARNING: The regulation of this parameter must be absolutely made by qualified personnel because setting an inappropriate value might result in a wrong operation of the whole regulation system

To set the hysteresis follow these steps:

  1. Select the parameter ‘ HYS ’ and press the ‘ seitron- TAD022- Taddy- Digital- Room- Thermostat-3 ‘ button.
  2. The display shows the hysteresis value previously set.
  3. Press buttons ‘ seitron- TAD022- Taddy- Digital- Room- Thermostat- 2  ‘ and ’ seitron- TAD022- Taddy- Digital- Room- Thermostat-(1) ’ to change the setting (inside 0.0°C..5.0°C interval); every change will be automatically stored in memory.
  4. Push the key ‘ seitron- TAD022- Taddy- Digital- Room- Thermostat-3 ‘ to exit from the settings of the selected parameter. To exit from the programmation of the user parameters, push the key ‘ seitron- TAD022- Taddy- Digital- Room- Thermostat-17 ’ or wait 10 seconds without pushing any key.

HEATING / COOLING SETTING

This setting is used to invert the operating logic of the relay according to which kind of unit is being controlled (heating or air conditioning).

IMPORTANT: The thermostat comes by factory default in heating mode.

To modify the operating logic, perform the following operations:

WARNING
During normal operation, the activation of the relay in Heating mode is shown by the lit icon ‘ ‘ while, on the opposite, the activation of the relay in Cooling mode is shown by the lit icon ‘ ‘.

MINIMUM RELAY ACTIVATION TIME SETUP

This parameter allows to a reduction the number of ON/OFF cycles of the output. This function is useful in case the thermostat drives a pellet stove that cannot be switched ON and OFF for a too short time. Once the relay is switched ON according to a heating (or cooling) need of the room, it will not be switched OFF until the ‘minimum time’ is expired. The parameter can be set in the 2 .. 240 seconds range. The device comes with a factory default with the parameter set to 2 seconds.

To set the minimum relay activation time, perform the following operations:

  1. Select the parameter ‘ t_SA ’ and press the ‘ seitron- TAD022- Taddy- Digital- Room- Thermostat-3 ‘ button.
  2. The display shows the sampling time previously set.
  3. Press buttons ‘ seitron- TAD022- Taddy- Digital- Room- Thermostat- 2  ‘ and ’ seitron- TAD022- Taddy- Digital- Room- Thermostat-(1) ’ to change the setting (between 0 .. 240 seconds); every change will be automatically stored in memory.
  4. Push the key ‘seitron-TA-D022-Digital-Thermostat-Taddy-FIG- (3) ‘ to exit from the settings of the selected parameter.
  5. To exit from the programmation of the user parameters, push the key ‘ seitron- TAD022- Taddy- Digital- Room- Thermostat-17 ’ or wait 10 seconds without pushing any key.

SET DEFAULT DATA

With this parameter it is possible to reset the user parameters in order to bring back all the parameters to factory defaults. Proceed as follows

  1. Select the parameter ’dFLt’ and press ‘ seitron- TAD022- Taddy- Digital- Room- Thermostat-3 ‘; the device automatically sets the default data and the display will show ’-dF-’.
  2. To quit the user parameter settings press the ‘ seitron- TAD022- Taddy- Digital- Room- Thermostat-3 ‘ button or wait 20 seconds without pressing any key.
  3. The display shows the writing ‘ OFF ’.
  4. The thermostat is deactivated; to activate the thermostat push the key ‘ seitron- TAD022- Taddy- Digital- Room- Thermostat-17 ’.

WARNING!
Restoring the Default Data will reset all settings made by the user, such as Heating/Cooling, Set-Points and all other programmable data.

EXTERNAL NTC SENSOR

WARRANTY

In view of the constant development of their products, the manufacturer reserves the right for changing technical data and features without prior notice. The consumer is guaranteed against any lack of conformity according to the European Directive 1999/44/EC as well as to the manufacturer’s document about the warranty policy. The full text of the warranty is available on request from the seller.

REFERENCE

DOWNLOAD MANUAL

seitron TAD022 Taddy Digital Room Thermostat Instruction Manual

seitron logo

seitron TAD022 Taddy Digital Room Thermostat Instruction Manual

Leave a Reply

Your email address will not be published. Required fields are marked *

To respond on your own website, enter the URL of your response which should contain a link to this post's permalink URL. Your response will then appear (possibly after moderation) on this page. Want to update or remove your response? Update or delete your post and re-enter your post's URL again. (Find out more about Webmentions.)