Sauter NRFC413MF111 Fan Coil Thermostat  FEA

Sauter NRFC413MF111 Fan Coil Thermostat Product Data Sheet

Sauter logo

Sauter NRFC413MF111 Fan Coil Thermostat 

Sauter NRFC413MF111 Fan Coil Thermostat-PRODUCT

How energy efficiency is improved

Precise comfort control in individual rooms through precise temperature detection

Features

  • Single-room controller for heating and cooling by means of air conditioning units in commercial and residential buildings
  • For 2- or 4-pipe fan coil units, two-stage heating systems or water-bearing heat pumps
  • Can be integrated into building management systems via Modbus/RTU
  • Large configurable display with backlight
  • Integrated ON/OFF timer
  • Deactivatable button operation for public installations
  • Valve control via 2-point or 0…10 V output
  • Supports 3-speed fans or fans with EC motor
  • Summertime/wintertime change-over in 2-pipe applications
  • Automatic deactivation of internal temperature sensor when using a cable temperature sensor
  • Installation via mounting plate without opening the controller
  • Universal design and low installation height of 14 mm for inconspicuous fitting

Technical data

Technical data
Power supply
Power supply 100…240 V~, 50/60 Hz
Power consumption 5 VA
Ambient conditions
Ambient temperature 0…40 °C
Ambient humidity 10…90% rh, no condensation
Storage and transport temperature -10…60 °C
Inputs/outputs
Inputs Temperature sensor NTC 10k
Digital input closed < 0.3 V= open > 0.7 V=
Analogue input 0…10 V
Outputs Analogue output U 0…10 V (100 kΩ)
Relay output 2.2 A (IR); 3.6 A (IX)

cos φ 0.98 each at 240 V~

Interfaces, communication
RS-485 Communication protocol Modbus/RTU
Connection Screw terminal, 3-pole 0.14. 1.5 mm² rigid

A (D+) / B (D-)

Bus speed 4800, 9600 bit/s (adjustable)
Address range 164
Function codes 01, 03, 04, 06, 16
CRC check CRC-16
Data type u16
Data format 10 bit, 1 start, 8 data, 1 stop, no parity
Indicator/display LCD display with backlight (adjustable)
Buttons 6
Construction
Weight 0.3 kg
Dimensions W × H × D 88 × 88 × 46.2 mm
Housing Upper and lower part white
Housing material Polycarbonate
Fitting On round or square recessed box
Type of protection IP20 (EN 60529)
Protection class II as per IEC 60730
CE conformity according to EMC Directive 2014/30/EU EN 60730-1, EN 60730-2-9

residential premises Type1.C

Low-Voltage Directive 2014/35/EU EN 60730-1, EN 60730-2-9
RoHS Directive 2011/65/EU EN IEC 63000

Inputs/outputs

Type AI DI AO DO
NRFC413MF111 1 × NTC, 1 × 0…10 V 1 1 3 × relay (single-pole normally-open contact)
NRFC422MF111 1 × NTC 1 0 5 × relay (single-pole normally-open contact)
NRFC423MF111 1 × NTC 1 2 3 × relay (single-pole normally-open contact)
NRFC424MF112 1 × NTC 1 2 3 × relay (single-pole normally-open contact)

Overview of types

NRFC413MF111 2-pipe, continuous, with positional feedback signal 3 speeds
NRFC422MF111 2-pipe or 4-pipe, 2-point 3 speeds
NRFC423MF111 2-pipe or 4-pipe, continuous 3 speeds
NRFC424MF112 2-pipe or 4-pipe, 2-point or 2-pipe, continuous EC motor with cut-off function

Description of operation

NRFC4* is a parameterisable single-room controller with Modbus/RTU communication function. With its fixed applications, the NRFC4* is specially designed for use with fan coil units (FCU) and can be used as a zone controller in residential and commercial buildings in combination with a Modbus/RTU network. The single-room controller detects the room temperature with its integrated temperature sensor and compares it with the setpoint temperature. In the event of a deviation, the heating valve is opened in heating mode, and the cooling valve is opened for cooling mode. At the same time, the connected fan is activated depending on the control deviation and the set configuration. A connectable remote sensor can be used either for detecting the room temperature or as a changeover (C/O) sensor in 2- pipe systems. By means of parameterization, the digital input can be assigned the presence signal function, dew point monitor or detection of a fault message in combination with a filter.

NRFC413MF111
The NRFC413MF111 is suitable for use in 2-pipe systems in combination with a valve for dynamic hydronic balancing (PICV) and 0…10 V actuator control. If an analogue feedback signal is available on the actuator, this can be transmitted to the building management system via Modbus for monitoring. A 3-speed fan can be controlled via three integrated relays. In a 2-pipe configuration, summertime/wintertime changeover (auto-changeover) can be automatically detected if an NTC cable temperature sensor is installed on the supply pipe.

NRFC422MF111
The NRFC422MF111 is suitable for 2-pipe or 4-pipe systems. The valve actuator is controlled via 2- point control. A 3-speed fan can be controlled via three integrated relays. In a 2-pipe configuration, summertime/wintertime changeover (auto-changeover) can be automatically detected if an NTC cable temperature sensor is installed on the supply pipe. The configuration for the underfloor heating is 2-step heating. In wintertime mode, the valve for the underfloor heating is activated in the first step. The second step is activated when the temperature difference between the setpoint and the room temperature is greater than the value of the intermediate step, which was set in the configuration. In the second step, the second valve opens and the fan starts. In summertime mode, the single-room controller operates as a 2-pipe system with a cooling register and a 3-speed fan. The valve for the underfloor heating is then not activated. In the configuration with an electrostatic filter (TiO2/ESP)1) this can be activated via the single-room controller. In this case, the digital input can be used to detect a fault in the air purifier

NRFC423MF111
In conjunction with a 3-speed fan, the NRFC423MF111 can be used in 2-pipe and 4-pipe systems with continuous valve actuators for heating and cooling. In a 2-pipe configuration, summertime/wintertime changeover (auto-changeover) can be automatically detected if an NTC cable temperature sensor is installed on the supply pipe.

NRFC424MF112
For fan coil units with EC motor2) the NRFC424MF112 provides a 0…10 V signal to control the motor. This can be limited by means of min. and max. parameters. A relay can be used to interrupt the supply voltage to the motor when the single-room controller is switched off. The single-room controller supports 2-pipe and 4-pipe applications with 2-point actuators as well as 2-pipe applications with 0…10 V actuators. In a 2-pipe configuration, summertime/wintertime changeover (auto-changeover) can be automatically detected if an NTC cable temperature sensor is installed on the supply pipe. The configuration for the underfloor heating is 2-step heating. In winter mode, the valve for the underfloor heating is activated in the first step. The second step is activated when the temperature difference between the setpoint and the room temperature is greater than the value of the intermediate step, which was set in the configuration. In the second step, the second valve opens and the fan starts. In summertime mode, the single-room controller operates as a 2-pipe system with a cooling register and a 3-speed fan. The valve for the underfloor heating is then not activated. In the configuration with an electrostatic filter (TiO2/ESP3), this can be activated via the single-room controller. In this case, the digital input can be used to detect a fault in the air purifier

Intended use
This product is only suitable for the purpose intended by the manufacturer, as described in the “Description of operation” section. All related product regulations must also be adhered to. Modifying or converting the product is not admissible. Only use this single-room controller as a control element. In cases where a failure or malfunction of the single-room controller could result in personal injury or damage to the controlled system or other property, additional precautions must be built into the system. Other devices such as monitoring or alarm systems or safety or limit controls that are intended to warn or protect against failure or malfunction of the single-room controller must be integrated into the system and maintained.

Engineering notes

The NRFC4* is a single-room controller suitable for indoor installation. The most suitable place of installation is approx. 1.5 m above the floor and must be protected from direct sunlight, draughts and  sources of heat or cold. The installation is carried out on recessed junction boxes with a minimum diameter of 60 mm.

Fitting and installation

The following conditions must be met or observed during the installation:

  • Connection may only be performed when the system is disconnected from the electrical supply.
  • The unit must be protected against contact.
  • There must be an external primary isolating facility.
  • The connection to terminal MM may not be interrupted by switching elements.
  • The device must not be installed in vibrating systems (e.g. means of transport such as ships) because the vibrations can cause micro-interruptions in the relays.
  • In series to terminal L (power supply 230 V~), a suitable external fuse (5 A slow-blow) must be installed in accordance with applicable installation regulations.
  • The plant devices are connected via screw terminals with the appropriate torques (see fitting instructions).
  •  For terminals on the terminal block for the signal low voltage, the permissible conductor crosssection is min. 0.14 mm2 and max. 1.5 mm2.
  • For the terminals on the terminal block for the mains power supply and relays, the permissible conductor cross-section is min. 1.0 mm2 and max. 1.5 mm2.
  • Remove the plastic cover of the LCD before use.

Special standards such as IEC/EN 61508, IEC/EN 61511, IEC/EN 61131-1 and -2 and similar were not taken into account. Local requirements regarding installation, usage, access, access rights, accident prevention, safety, dismantling and disposal must be taken into account. Furthermore, installation standards EN 50178, 50310, 50110, 50274, 61140 and similar must be observed. The communication wiring (RS‑485) must be isolated from current-carrying and live installations.

Note

  • When installing on a recessed junction box, make sure that if the cable is routed through an installation pipe, this is protected against draughts. Otherwise, temperature measurement errors may occur.
  • Terminals in the connection area that are not labelled must not be used.
  • Do not install the device in environments with condensation or which are wet or humid. Humidity can cause damage to the single-room controller.
  • Do not remove the printed circuit board from the housing cover. Removing the PCB from the housing cover will void the product warranty.
  • Do not use chemicals aggressive to polycarbonate or sharp and pointed objects to clean the surfaces.
  • For further safety instructions, information and guidelines, see fitting instructions P100019338.

Power supply
The device is suitable for operation at 100…240 V~.

Commissioning

  • After commissioning, it may take up to one hour for a thermal balance to be set in the single-room controller and for the measured values to be stable.
  • When installing on a recessed junction box, make sure that if the cable is routed through an installation pipe, this is protected against draughts. Otherwise, temperature measurement errors may occur. In the event of a measurement deviation, this can be compensated.

Operation

All devices have the same number of buttons and operating logic

  1. ON/OFF. The NRFC can be switched off with the ON/OFF button. When switching off, the power supply to the fan and the valve is interrupted
  2. Selection of operating mode: Auto/Heat/Cool/Ventilate. In a 2-pipe application, this button can be used to switch between heating, cooling and ventilation only. In a 4-pipe application, this can be used to switch between heating, cooling and AUTO operating modes
  3. Activate TiO2/ESP filter relay output (press for 1 second), program ON/OFF timer (press for 3 seconds). The Timer ON/OFF function allows the user to activate a delay for the room controller to switch off. A delay time of up to 24 hours in 30 minute increments is possible. A start-up delay for the device can also be defined. The electrostatic filter (TiO2/ESP) can be switched on/off with button (3). Alternatively, the filter operation is defined to work in parallel with the fan. In this configuration, one of the relays will then be used to operate the  filter unit
  4. Fan speed selection: low, medium, high and automatic
  5. Up button: Increases a value, e.g. the setpoint
  6. Down button: Decreases a value, e.g. the setpoint

Sauter NRFC413MF111 Fan Coil Thermostat  1

Button lock
To prevent unwanted or improper operation in public areas, the buttons can be disabled. The following button combinations can be disabled:

  • All buttons,
  • All buttons except fan and setpoint,
  • On/Off only and clock functions.

When a button lock is active, pressing the fan button for 5 seconds will temporarily unlock it. The button lock can be activated or deactivated via parameter input on the display or by setting a Modbus parameter.

Display functions

  1. Cooling mode
  2. Heating mode
  3. Automatic mode if the changeover is set to Auto
  4. Fan speed: low, medium, high, automatic
  5. Filter alarm flashes when active
  6. Error or dew point alarm
  7. Keys locked
  8. Valve open
  9. Remote sensor connected
  10. Flashes when Modbus communication is lost
  11.  Temperature unit; Celsius or Fahrenheit
  12. Timer ON/OFF indicates next activation in hh:mm
  13. Temperature setpoint and actual value display
  14.  SET is activated when setpoint is displayed
  15.  Status indicator: occupied / not occupiedSauter NRFC413MF111 Fan Coil Thermostat  2

Backlight
The NRFC4* has a backlight that makes the display easy to read. The backlight switches on when a key is pressed and switches off automatically after a parameterised time

Service parameters
To activate the service menu, when the NRFC4* is switched off, press the v and ▲ keys simultaneously for 5 seconds. The code 01 is displayed. Pressing the operating mode selector activates the next code. The parameter value can be set using the ▲ and ▼ keys. Set parameters are automatically adopted. The available parameters depend on the model installed (see parameter table).

Code Parameter Default Function NRFC 423MF111 NRFC 424MF112 NRFC 422MF111 NRFC 413MF111
01 Max. setpoint limit 35 °C Setting range 0…40 °C (36…99 °F)
02 Min. setpoint limit 5 °C Setting range 0…38 °C (32…95 °F)
03 Application 00: 2-pipe ON/OFF valve 01: 4-pipe ON/OFF valve

02: 2-pipe ON/OFF 3-point valve

03: 2-pipe ON/OFF valve with TiO2/ESP relay 04: 2-pipe ON/OFF valve with underfloor heating 05: Water heat pump

06: 2-pipe proportional valve

 

 

 

03 Application 00: 2-pipe proportional valve 01: 4-pipe proportional valve
03 Application 00: 2-pipe ON/OFF valve 01: 4-pipe ON/OFF valve

02: 2-pipe ON/OFF 3-point valve

03: 2-Pipe ON/OFF valve with TiO2/ESP relay 04: 2-pipe ON/OFF valve with underfloor heating 05: Water heat pump

 

 

 

04 Cooling setpoint not occu- pied 26 °C Setting range 22…32 °C (72…90 °F)
05 Heating setpoint not occu- pied 18 °C Setting range 10…21 °C (50…70 °F)
06 Frost protection 00: ON

01: OFF

07 Frost protection setpoint 5 °C Setting range 0…20 °C (32…68 °F)
08 Fan speed in AUTO mode as soon as the controller is in the dead zone (room temperature reaches set- point) 01 00: Fan off

01: LOW

 

 

 

 

 

 

 

 

09 Fan speed not occupied 00 00: LOW

01: Fan speed manually adjustable

10 ECM min. voltage 3 V Min. voltage below which the fan output is 0%. Adjust- able range 0…10 V (0.5 V increments)
11 ECM max. voltage 10 V Max. voltage above which the fan output is 100%. Ad- justable range 0…10 V (0.5 V increments)
12 ECM relay (F-ON) 00 00: Deactivated

01: Activated

13 Operation after return of power supply 00: Last status

01: ON

02: OFF

 

 

 

 

14 Keys locked 00 00: No keys locked 01: Lock all keys

02: Lock all keys except fan speed and setpoint entry 03: Lock ON/OFF and ON/OFF timer

04: Lock all keys except ON/OFF key

 

 

 

 

 

 

 

 

15 Display 00 00: Room temperature

01: Room setpoint

16 Automatic changeover 00 00: Deactivated

01: Activated (2-pipe systems require 10k NTC instal- led on the pipe)

 

 

 

 

Code Parameter Default Function NRFC 423MF111 NRFC 424MF112 NRFC 422MF111 NRFC 413MF111
17 Function of digital input (OCC) 00 00: open → occupied, closed → not occupied (setpoint decrease)

01: closed → occupied, open → not occupied (setpoint decrease)

02: closed → dew point reached, open → dew point not reached

03: open → dew point reached, closed → dew point not reached

04: open → occupied, closed → not occupied (fan off, valve closed)

05: closed → filter alarm

06: open → filter alarm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

18 Temperature unit 00 00: Degrees Celsius (°C) 01: Degrees Fahrenheit (°F)
19 Sensor compensation 0 Setting range -5…5 °C (-9…9 °F)
20 Fan speed limitation (not available with ECM fan in AUTO mode) 00 00: 3-speed

01: 2-speed (wiring MED, LOW) 02: 1-speed (wiring LOW)

03: Fan deactivated

 

 

 

 

 

 

 

 

21 Language 01 00: Chinese

01: English

22 Operating modes 00 00: Heating/cooling/ventilation

01: Cooling only

02: Heating only

 

 

 

 

23 Display backlight 30 Setting range 0…60 seconds; backlight is deactivated after set time
25 Remote sensor 01 00: Third-party 10k NTC 01: SAUTER 10k NTC
26 Modbus address 1 1…64
27 Baud rate 00 00: 9600

01: 4800

28 Scan time 10 Setting range 1…99 seconds (floating point num- ber *10)
29 Dead zone 1 Setting range 0…10 °C (32…50 °F)
30 KP (PB = 100/KP) 10 Setting range 1…99
31 KI (integral gain) 01 Setting range 1…99
32 TiO2/ESP control 00 00: Separate control (briefly press timer button to acti- vate)

01: Common control with fan-coil controller

 

 

33 Switching difference for un- derfloor heating 3 Setting range 0…10 °C (32…50 °F)
34 Number of switch positions for underfloor heating 00 00: 2-position

01: 1-position

37 Timer for fan switch-off (set- ting of time delay for fan switch-off) 00 0…99 seconds  

 

 

 

Error messages

Error message on the display The following errors are displayed instead of the temperature when they occur

Error code Meaning
E1 Warning: Internal sensor short-circuited. Valve and fan are switched off.
E2 Warning: Internal sensor is open. Valve and fan are switched off.
HI Warning: High temperature. Room temperature > 55 °C
LO Warning: Low temperature. Room temperature < 0 °C
E3 Remote sensor short-circuited. Active only with 2-pipe application and auto changeover.
E4 Remote sensor is interrupted. Active only with 2-pipe application and auto changeover.
E5 Warning: Dew point risk. Valve and fan are switched off.
Symbol flashes when Modbus connection is interrupted.
Error code Meaning
Symbol flashes when a filter alarm is active.
Symbol active when an error has been detected and/or a dew point alarm is active.

Error message via Modbus

The following error messages can be read out via Modbus

Function code Address Description
03 + 04 4 01: Warning: Internal sensor short-circuited. Valve and fan are switched off 02: Warning: Internal sensor is open. Valve and fan are switched off

03: Warning: High temperature. Room temperature > 55 °C. Warning: Low temperature. Room temperature < 0 °C

04: Remote sensor short-circuited. Active only with 2-pipe application and auto changeover 05: Remote sensor is interrupted. Active only with 2-pipe application and auto changeover

06: Warning: Dew point risk. Valve and fan are now switched off

Modbus/RTU
All NRFC4** have Modbus/RTU communication, which can be used to transfer information to a higher-level building automation system. Up to 32 single-room controllers can be addressed on a bus.

The following states can be read out, or commands sent, via Modbus:

  • Switch single-room controller on/off
  • Read out room temperature
  • Change the setpoint of the room temperature
  • Determine fan speed
  • Set occupied or unoccupied status with corresponding setpoint reduction
  • Lock the keypad
  • Change the application

The following function codes are supported:

Function code
01 Read Coil
03 Read Holding Registers
04 Read Input Registers
06 Write Single Holding Register
16 Write Multiple Holding Registers

Modbus – parameter list

Function code Address Description Value
01 1 Relay 4 0: OFF

1: ON

01 2 Relay 5 0: OFF

1: ON

01 3 Relay 1 0: OFF

1: ON

01 4 Relay 2 0: OFF

1: ON

01 5 Relay 3 0: OFF

1: ON

04 1 Device type Device type and application4)
04 2 Room temperature Room temperature (0…99 °C)5)
04 3 Occupancy status 00: Not occupied

01: Occupied

Function code Address Description Value
04 4 Error messages 01: Warning: Internal sensor short-circuited. Valve and fan are switched off 02: Warning: Internal sensor is open. Valve and fan are switched off

03: Warning: High temperature. Room temperature > 55 °C Warning: Low temperature. Room temperature < 0 °C

04: Remote sensor short-circuited. Active only with 2-pipe application and auto changeover 05: Remote sensor is interrupted. Active only with 2-pipe application and auto changeover

06: Warning: Dew point risk. Valve and fan are now switched off

03 + 06 + 16 1 Device type Device type and application6)
03 + 06 + 16 2 Room temperature Room temperature (0…99 °C)7)
03 + 06 + 16 3 Occupancy status 00: Not occupied

01: Occupied

03 + 06 + 16 4 Error messages 01: Warning: Internal sensor short-circuited. Valve and fan are switched off 02: Warning: Internal sensor is open. Valve and fan are switched off

03: Warning: High temperature. Room temperature > 55 °C Warning: Low temperature. Room temperature < 0 °C

04: Remote sensor short-circuited. Active only with 2-pipe application and auto changeover 05: Remote sensor is interrupted. Active only with 2-pipe application and auto changeover

06: Warning: Dew point risk. Valve and fan are now switched off

03 + 06 + 16 5 Power 0: OFF

1: ON

03 + 06 + 16 6 Operating mode 0: Cooling

1: Heating

2: Ventilation

03 + 06 + 16 7 Setpoint Room temperature setpoint (0…99 °C)8)
03 + 06 + 16 8 Fan speed 00: Low

01: Medium

02: High

03: Auto

03 + 06 + 16 9 Max. setpoint limit Setting range 0…40 °C8)
03 + 06 + 16 10 Min. setpoint limit Setting range 0…38 °C8)
03 + 06 + 16 11 Cooling setpoint not occupied Setting range 22…32 °C8)
03 + 06 + 16 12 Heating setpoint not occupied Setting range 10…21 °C8)
03 + 06 + 16 13 Frost protection 0: OFF

1: ON

03 + 06 + 16 14 Frost protection setpoint Setting range 0…20 °C8)
03 + 06 + 16 15 Fan dead zone 00: OFF

01: LOW

03 + 06 + 16 16 Fan speed not occupied 00: LOW

01: Fan speed manually adjustable

03 + 06 + 16 17 Operation after return of power supply 00: Last status

01: ON

02: OFF

03 + 06 + 16 18 Keys locked 00: No keys locked 01: Lock all keys

02: Lock all keys except fan speed and setpoint entry 03: Lock ON/OFF and ON/OFF timer

04: Lock all keys except ON/OFF key

03 + 06 + 16 19 Display 00: Room temperature

01: Room setpoint

03 + 06 + 16 20 Function of digital input 00: Open → occupied, closed → not occupied (setpoint decrease) 01: Closed → occupied, open → not occupied (setpoint decrease) 02: Closed → dew point reached, open → dew point not reached 03: Open → dew point reached, closed → dew point not reached 04: Open → occupied, closed → not occupied (fan off, valve closed) 05: Closed → filter alarm

06: Open → filter alarm

03 + 06 + 16 21 Temperature unit 00: Degrees Celsius (°C) 01: Degrees Fahrenheit (°F)
03 + 06 + 16 22 Sensor compensation Setting range -5…5 °C8)
Function code Address Description Value
03 + 06 + 16 23 Limitation of fan speed 00: 3-speed

01: 2-speed

02: 1-speed

03: Fan deactivated

03 + 06 + 16 24 Language 00: Chinese

01: English

03 + 06 + 16 25 Operating modes 00: Heating/cooling/ventilation

01: Cooling only

02: Heating only

03 + 06 + 16 26 Display backlight Setting range 0…60 seconds; backlight is deactivated after set time
03 + 06 + 16 28 Remote sensor 00: Third-party 10k NTC 01: SAUTER 10k NTC
03 + 06 + 16 29 Dead zone Setting range 0…10 °C9)
03 + 06 + 16 30 Automatic changeover 00: Deactivated

01: Activated

03 + 06 + 16 31 ECM min. voltage Min. voltage below which the fan output is 0%. Adjustable range 0…10 V (0.5 V increments)10)
03 + 06 + 16 32 ECM max. voltage Max. voltage above which the fan output is 100%. Adjustable range 0…10 V (0.5 V incre-

ments)10)

03 + 06 + 16 33 ECM relay 00: Deactivated

01: Activated

03 + 06 + 16 34 Scan time Setting range 1…99 seconds10)
03 + 06 + 16 35 P band Setting range 1…9910)
03 + 06 + 16 36 Integral gain Setting range 1…9910)
03 + 06 + 16 37 Switching difference for under- floor heating Setting range 0…10 °C9)

Switching between level 1 and level 2

03 + 06 + 16 38 Number of switch positions for underfloor heating 00: 2-position

01: 1-position

03 + 06 + 16 39 TiO2/ESP control 00: Separate control

01: Common control with fan-coil controller

03 + 06 + 16 43 TiO2/ESP relay 00: OFF

01: ON

03 + 06 + 16 44 AO1 PWM switch-on time 0…100%
03 + 06 + 16 45 AO2/AI AO → PWM switch-on time 0…100%

AI → 0…10 V (0…100%)9)

Additional information
Fitting instructions P100019338

Disposal
When disposing of the product, observe the currently applicable local laws. More information on materials can be found in the Declaration on materials and the environment for this product.

RS-485 bus wiring
The RS‑485 network for field bus protocols must be implemented as per ANSI/TIA/EIA-485-A [half duplex (A (D+)/ B (D−)), galvanically isolated (COM reference), network resistors with Pull-Up (PU), Pull-Down (PD), line-end resistors (EOL: End of Line Termination)]. The devices do not have internal terminating resistors. Therefore, a terminating resistor of 120 Ω (0.25 W) must be connected at the start and end of the bus line, parallel to the A (D+) / B (D−) data lines. It is recommended to use a shielded, twisted cable (1×2+1-wire, 2×2-wire) specifically for RS‑485. It is also possible to use JY( ST)Y cables taking into account the cable impedance of 100…120 Ω and sufficient diameter (0.8 mm or 0.5 mm2). The cable routing must be carried out in line topology. The cable shield of the entire bus line must be connected continuously, and connected to protective earth as directly as possible at one location. The shielding is to be earthed in the plant as follows:

  • Shielding earthed at one end is suitable for protection from electrical interference (from overhead power lines, static charges etc.)
  • Shielding earthed at both ends is suitable for protection from electromagnetic interference (from frequency converters, electric motors, coils etc.)
  • The maximum cable length is 1000 m and depends on the cable type used and the correct termination. The length of the bus wiring is limited by the following parameters:
  • Number of connected devices
  • Cross-section of cable used
  • The baud rate can be 4800 or 9600 bit/s.

Sauter NRFC413MF111 Fan Coil Thermostat  3

Connection diagramsSauter NRFC413MF111 Fan Coil Thermostat  4 Sauter NRFC413MF111 Fan Coil Thermostat  5 Sauter NRFC413MF111 Fan Coil Thermostat  6 Sauter NRFC413MF111 Fan Coil Thermostat  7 Sauter NRFC413MF111 Fan Coil Thermostat  8

Dimension drawing
All dimensions in mm.

Sauter NRFC413MF111 Fan Coil Thermostat  9

Sauter

Reference

Download Manual:

Sauter NRFC413MF111 Fan Coil Thermostat Product Data Sheet

Other Manual:

Sauter NRFC413MF111 Digital Thermostat Instruction Manuals

Sauter logo

Sauter NRFC413MF111 Fan Coil Thermostat Product Data Sheet

Comments

Leave a Reply

Your email address will not be published. Required fields are marked *

To respond on your own website, enter the URL of your response which should contain a link to this post’s permalink URL. Your response will then appear (possibly after moderation) on this page. Want to update or remove your response? Update or delete your post and re-enter your post’s URL again. (Find out more about Webmentions.)