Robertshaw RS9110 Programmable Touchscreen Thermostat
INSTALLATION MANUAL
Thermostat System Types
Gas, Oil, or Electric Heat with Air Conditioning |
Heat Pumps (without auxiliary or emergency heat) |
Heat-Only, including for Floor and Wall-Furnace |
Cool-Only |
750 Millivolt Heating Systems |
IMPORTANT SAFETY INFORMATION WARNING
- Always turn off power at the main power source by unscrewing fuse or switching circuit breaker to the off position before installing, removing, cleaning, or servicing thermostat.
- Read all of the information in this manual before installing or programming this thermostat.
- This is a 24V AC low voltage thermostat. Do not install on voltages higher than 30V AC.
- All wiring must conform to local and national building and electrical codes and ordinances.
- Do not short (jumper) across terminals on the gas valve or at the system control to test installation. This will damage the thermostat and void the warranty.
INSTALLATION LOCATION
Install the thermostat 4 to 5 feet above the floor in an area with good air circulation and average temperature.
For new installations, mount thermostat on an inside wall, 4-5 feet above the floor. Do not install the thermostat in the following locations:
- Behind a Door
- In a Corner
- Near Air Vents
- In Direct Sunlight
- With an Outside Wall Behind the Thermostat
- Near any Heat or Steam Generating Fixtures
- Near any Concealed Pipes or Chimneys
Installation at these locations will affect thermostat operation.
THERMOSTAT QUICK REFERENCE
- LCD Screen
- Fan Switch
- System Switch
- Temperature Set-Point Buttons
- User Buttons
- Easy Change Battery Door
LCD
WALLPLATE INSTALLATION
Caution:
Electrical Hazard
Disconnect power before installing this product. Failure to do so can cause electric shock or equipment damage.
For a vertical mount, put screws on the top and bottom. For a horizontal mount, put screws on the left and the right.
Mercury Notice:
This product is mercury-free. However, if this product is replacing a control that contains mercury, it needs to be disposed of properly. Contact your local waste management authority for instructions regarding recycling and proper disposal of the control.
WIRING
- Turn Off Power to the Heating/Cooling System
- Remove Old Thermostat
Remove old thermostat but leave wallplate with wires attached.
- Label Wires with Tags
Label the wires using the supplied wire labels as you disconnect them.
- Separate Wallplate from New Thermostat
Remove wallplate from the new thermostat and mount onto wall.
- Mount Wallplate for New Thermostat
Mount the new wallplate using the included screws and anchors.
Drill 3/16-in. holes for drywall
Drill 3/16-in. holes for plaster - Connect Wires
Simply match wire labels.
If labels do not match letters on the thermostat, check “Alternate Wiring (Conventional Systems)” on page 9 and connect to terminal as shown (see notes, below).
Alternate Wiring (Conventional Systems)
If labels do not match letters on the thermostat, check the chart below and connect to terminal as shown here (See notes, below).
- If wires will be connected to both RC and RH/R terminals, remove metal jumper.
- If C or X wire is available then you can connect with C terminal. If there is no C or X wire then no need to connect with C terminal.
- If you have a heat pump without auxiliary/backup heat connect O or B, not both. If you do not have a heat pump, do not connect B. Wrap bare end of wire with electrical tape.
Place a jumper (piece of wire) between Y and W if you are using a heat pump without auxiliary/backup heat.
Terminal Designations
- C 24 VAC Common Wire
- O Heat pump reversing valve energized in cooling
- B Heat pump reversing valve energized in heating
- W Heat relay
- RH 24 VAC power for heating
- RC 24 VAC power for cooling
- G Fan relay
- Y Compressor relay
Wiring Notes
- RH & RC Terminals
In a single-transformer system, leave the metal jumper in place between the RH and RC. Remove the metal jumper in two-transformer systems. - Heat Pump Systems (With NO Auxilary or Emergency Heat)
If wiring to a heat pump, use a small piece of wire (not supplied) to connect terminals W (Heat relay) & Y (Compressor relay). - Common wire
The C (common wire) is optional when the thermostat is powered by batteries. - Wire Specifications
Use 18- to 22-gauge thermostat wire. Shielded wire is not required.
Installation Tip: Do not overtighten terminal block screws, as this can damage the terminal block. A damaged terminal block can keep the thermostat from fitting on the subbase correctly or cause system operation issues. Max Torque = 6in/lbs.
- Power supply.
- Factory-installed jumper. Remove only when installing on 2-transformer systems.
- Use either O or B terminals for reversing valve.
- Use a small piece of wire (not supplied) to connect W and Y terminals.
- Set fan operation switch to electric.
- Optional 24 VAC common connection when thermostat is used in battery power mode.
Wiring Diagrams
This thermostat has an installer setup menu for easy configuration. Follow the procedure below to set up the thermostat to match the specific heating/cooling system.
- Press MENU
- Press and hold TECH SET for 3 seconds.
- Configure the installer options as desired using the table below.
Useto change settings and NEW STEP or PREV STEP to move from one option to another. Note: Only press DONE when you want to exit the Installer Setup options.
MOUNTING & BATTERY INSTALLATION
Mounting Thermostat
Align the 4 tabs on the faceplate with the corresponding slots on the back of the thermostat, then push gently until the thermostat snaps into place.
Battery Installation
Battery installation is optional if used with AC power (the C terminal is connected).
During power outages, the batteries will save settings and power the display.
Set Time of Day and Day of Week
- Press MENU.
- Press SET TIME.
- Day of the week will be flashing. Use
to select the current day of the week.
- Press NEXT STEP.
- The current hour will be flashing. Use o
to select the current hour.
- Note the correct a.m. or p.m. indicator is selected.
- Press NEXT STEP.
- The minutes will be flashing. Use
to select the current minutes.
- Press DONE when completed.
PROGRAMMING
Default Program
This thermostat is pre-programmed for energy saving operation. The default program is below:
You can use the table below to plan your customized program schedule.
Custom Programming
This thermostat can be configured to have 7 Day or 5+1+1 programming. If 7 Day is selected, all seven days will need to be programmed individually. If 5+1+1 programming is selected, Monday–Friday will be programmed together and Saturday and Sunday will need to be programmed individually. There are four time periods for each day (WAKE, LEAVE, RETURN, SLEEP).
Follow the steps below to customize your program schedule:
- Select HEAT or COOL. Note: Heat and cool need to be programmed separately.
- Press MENU (If menu does not appear first, press RUN SCHED).
- Press SET SCHED. Note: Monday–Friday (or Monday if in 7 Day mode) will be displayed and the WAKE icon is shown.
- Time will be flashing. Use
to make your time selection for the WAKE time period for Monday–Friday (or Monday if in 7 Day mode).
- Press NEXT STEP.
- The set-point temperature will be flashing. Use
to make your set-point selection for the WAKE time period for Monday–Friday (or Monday if in 7 Day mode).
- Press NEXT STEP.
- Repeat steps 4 through 7 for the LEAVE time period, for the RETURN time period, and for the SLEEP time period for Monday–Friday (or Monday if in 7 Day mode).
- Repeat steps 4 through 8 for the Saturday WAKE, LEAVE, RETURN, and SLEEP time periods, and then again for the Sunday WAKE, LEAVE, RETURN, and SLEEP time periods for the 5+1+1 program schedule, and for each day for the 7-day program schedule.
SPECIFICATIONS
- Temperature Display Range…………….41°F to 95°F (5°C to 35°C)
- Temperature Control Range…………….44°F to 90°F (7°C to 32°C)
- Load Rating…………………………………..1 amp per terminal, 1.5 amp maximum all terminals combined
- Display Accuracy……………………………± 1°F
- Differential……………………………………. Heating is adjustable from 0.2°F to 2.0°F
- Cooling is adjustable from 0.2°F to 2.0°F
- Power Source……………………………….. 18 to 30 VAC, NEC Class II, 50/60 Hz for hardwire (common wire)
- Battery power from 2 AAA Alkaline batteries
- Operating Ambient Temperature………32°F to +105°F (0°C to +41°C)
- Operating Humidity………………………..90% non-condensing maximum
- Dimensions……………………………………4.72”W x 3.86”H x 0.98”D
Technical Service +1.800.445.8299
[email protected]
www.robertshaw.com • 352-00301-001 6Year
Limited Warranty Use Phone to Scan for Warranty Info
Customer Service +1.800.304.6563
Technical Service +1.800.445.8299
[email protected]
www.robertshaw.com • 352-00301-001 6Year
limited warranty
Use to 00306-001 Rev. B Warranty Programming Programming
© 2021 Robertshaw Controls Company.
Robertshaw® is a trademark of Robertshaw Controls Company
REFERENCE:
Other Manual: Robertshaw RS9110 Programmable Touchscreen Thermostat Product Guide
Robertshaw RS9110 Programmable Touchscreen ThermostatOperation Manual
Robertshaw RS9110 Programmable Touchscreen Thermostat Installation Guide
Leave a Reply