Robertshaw-9600-PROGRAMMABLE-THERMOSTAT-featured

Robertshaw 9600 PROGRAMMABLE THERMOSTAT User Manual

Robertshaw logo

Robertshaw 9600 PROGRAMMABLE THERMOSTAT 

Robertshaw-9600-PROGRAMMABLE-THERMOSTAT-product

IMPORTANT SAFETY INFORMATION WARNING

  • Always turn off power at the main power source by unscrewing the fuse or switching the circuit breaker to the off position before installing, removing, cleaning, or servicing the thermostat.
  • Read all of the information in this manual before installing or programming this thermostat.
  • This is a 24V AC low-voltage thermostat. Do not install on voltages higher than 30V AC.
  • All wiring must conform to local and national building and electrical codes and ordinances.
  • Do not short (jumper) across terminals on the gas valve or at the system control to test installation. This will damage the thermostat and void the warranty.

Features

  • Four setpoints for weekday programming—two setpoints for weekend comfort.
  • Two AA ENERGIZER brand batteries retain program memory even during power outages.
  • Low battery indicator.
  • Fahrenheit/Celsius display option.
  • Programmable from 45°F (4°C) to 90°F (32°C).
  • Accuracy within ± 1 degree.
  • Adjustable temperature differential: 1-3 degrees.
  • Maintains summer and winter programming.
  • Low-temperature freeze protection. While in heat mode, the thermostat will mechanically turn on the heat if the temperature drops to 40°F (4°C) -even if batteries are missing or drained.
  • Automatic heating shutdown if the temperature exceeds 90°F (32°C).

Replacing Existing Thermostat

  1. Turn off the power to the heating and cooling system.
  2. Remove the cover of the old thermostat to expose the wires. Do not disconnect wires. (See Figure 1)
  3. Label wires per Table 1.* NOTE: ON SOME OLDER MODELS, THE C TERMINAL CAN BE EITHER THE COOLING CONTROL OR THE COMMON SIDE OF THE TRANSFORMER. CHECK THE FURNACE WIRING DIAGRAM TO VERIFY THE C TERMINAL. IFITISTHE COMMON SIDE OF THE TRANSFORMER, CAP THE WIRE AND TUCK IT INTO THE WALL. IFITISTHE COOLING CONTROL, CONNECT TO THE Y TERMINAL.
  4. After labeling wires, remove wires from terminals.
  5. Remove the existing thermostat base from the wall.
  6.  Refer to the following section for instructions on how to install the thermostat.Robertshaw-9600-PROGRAMMABLE-THERMOSTAT-fig-1

Table 1

Table 1
Old Label New Label Description
M, 4, RH, R5 or R RH Heat Transformer, hot side
V or RC RC Cooling Transformer, hot side
Y or Y6 Y Cooling control
H, W or 4 W Heating control
F or G G Fan control relay
C* Y or None Either cooling control or the common side of transformer

Installing Item 9600 Thermostat
NOTE: FOR NEW INSTALLATIONS, MOUNT THERMOSTAT ON AN INSIDE WALL, 4-5 FEET ABOVE THE FLOOR. DO NOT INSTALL BEHIND A DOOR, IN A CORNER, NEAR AIR VENTS, IN DIRECT SUNLIGHT, OR NEAR ANY HEAT OR STEAM-GENERATING FIXTURES. INSTALLATION AT THESE PLACES WILL AFFECT THERMOSTAT OPERATION.

  1.  Turn the power off to the heating and cooling systems.
  2.  Place COOL-OFF-HEAT in the OFF position.Robertshaw-9600-PROGRAMMABLE-THERMOSTAT-fig-2
  3. Place Robertshaw-9600-PROGRAMMABLE-THERMOSTAT-fig-24AUTO–ON switch into the AUTO position.
  4. Remove the cover using a coin or screwdriver.Robertshaw-9600-PROGRAMMABLE-THERMOSTAT-fig-3
  5. Place the thermostat against the wall at the desired location. Make sure wires will feed through the opening on the base of a thermostat.
  6. Mark placement of mounting holes (see Figure 3). Set base asideRobertshaw-9600-PROGRAMMABLE-THERMOSTAT-fig-4
  7. Drill the marked holes using a 3/16” drill bit. Note: Enclosed plastic anchors do not require a drilled hole for drywall.
  8. Tap plastic anchors into the wall.
  9. Align the base with plastic anchors and feed wires through the opening (see Figure 4).Robertshaw-9600-PROGRAMMABLE-THERMOSTAT-fig-5
  10.  Secure base to wall with supplied screws.
  11.  Connect wires to the terminal strip. Refer to the wiring diagrams on another side of this sheet. Make sure wire connections are secure.
  12.  Place the fan option switches into either the ELEC or GAS position depending on the type of furnace. Refer to Figure 5.Robertshaw-9600-PROGRAMMABLE-THERMOSTAT-fig-6
  13. Install two AA ENERGIZER brand batteries or equivalent into the battery compartment. Be sure to match the positive (+) ends of batteries with positive (+) battery terminals in the battery compartment. The display will show as follows:Robertshaw-9600-PROGRAMMABLE-THERMOSTAT-fig-7
  14.  Replace cover on the thermostat by snapping it into place.
  15.  Turn on the power to the system. Test the thermostat as described in the section To Test Thermostat.

Set Time of Day, Day of Week, Temperature Differential

  1. Press and hold SET. Press PROG/MAN. Release simultaneously.Robertshaw-9600-PROGRAMMABLE-THERMOSTAT-fig-8
  2. Press Robertshaw-9600-PROGRAMMABLE-THERMOSTAT-fig-9 or Robertshaw-9600-PROGRAMMABLE-THERMOSTAT-fig-10 to change the time of day.Robertshaw-9600-PROGRAMMABLE-THERMOSTAT-fig-11Robertshaw-9600-PROGRAMMABLE-THERMOSTAT-fig-12
  3. PressRobertshaw-9600-PROGRAMMABLE-THERMOSTAT-fig-13

THE TEMPERATURE DIFFERENTIAL IS FACTORY PRESET AT 1°. THIS MEANS THAT WHENEVER THE ROOM TEMPERATURE CHANGES BY ONE FULL DEGREE FROM THE TEMPERATURE SETTING, THE SYSTEM WILL TURN ON. IF THE SYSTEM TURNS ON TOO OFTEN, INCREASE THE TEMPERATURE DIFFERENTIAL.

Changing Fahrenheit (F) to Celsius (C)
Press and hold SET.

Robertshaw-9600-PROGRAMMABLE-THERMOSTAT-fig-14

Release both simultaneously.

Setting Daily Programming

Robertshaw-9600-PROGRAMMABLE-THERMOSTAT-fig-15Robertshaw-9600-PROGRAMMABLE-THERMOSTAT-fig-16

NOTE: BOTH SUMMER AND WINTER PROGRAMS USE THE SAME TIME SETTINGS. Your thermostat is now programmed for summer and winter operations. It will follow the four settings (MORN, DAY, EVE, NITE) for weekday operation and two settings (MORN and NITE) for weekend operation. Adjust the program at any time by following the steps outlined above.

Begin Programmed OperationRobertshaw-9600-PROGRAMMABLE-THERMOSTAT-fig-17

Temporary Program Override
To temporarily increase or decrease temperature: Press Robertshaw-9600-PROGRAMMABLE-THERMOSTAT-fig-9 or Robertshaw-9600-PROGRAMMABLE-THERMOSTAT-fig-10

Robertshaw-9600-PROGRAMMABLE-THERMOSTAT-fig-18

The thermostat will automatically return to the program at the next scheduled setting change.

Manual Operation

  1. Press PROG/MAN until the indicator is in the MAN position.Robertshaw-9600-PROGRAMMABLE-THERMOSTAT-fig-19
  2. 2. Press Robertshaw-9600-PROGRAMMABLE-THERMOSTAT-fig-9 or Robertshaw-9600-PROGRAMMABLE-THERMOSTAT-fig-10 to adjust temperature settings.

Reset
To reset the thermostat to factory preprogrammed conditions, press the RESET button located directly to the right of the display.

Robertshaw-9600-PROGRAMMABLE-THERMOSTAT-fig-20

To Test Thermostat
WARNING: DO NOT SHORT (JUMPER) ACROSS TERMINALS OF GAS VALVE OR SYSTEM CONTROL TO TEST OPERATION. THIS WILL DAMAGE THE THERMOSTAT AND VOID YOUR WARRANTY.
CAUTION: DO NOT SWITCH THE SYSTEM TO COOL IF THE TEMPERATURE IS BELOW 50°F (10°C). THIS CAN DAMAGE THE AIR CONDITIONING SYSTEM AND CAUSE PERSONAL INJURY.

  1. Place the COOL-OFF-HEATRobertshaw-9600-PROGRAMMABLE-THERMOSTAT-fig-21
    switch into the COOL position.
  2. Press the Robertshaw-9600-PROGRAMMABLE-THERMOSTAT-fig-9 button until the temperature setting is at least 3 degrees below the room temperature. The air conditioning system should turn on within a few seconds.NOTE: THERE IS A BUILT-IN 5-MINUTE DELAY ON BREAK FOR COMPRESSOR PROTECTION. A SECOND ATTEMPT TO TURN ON THE AIR CONDITIONING WILL RESULT IN A5- MINUTE’S DELAY IN COMPRESSOR ACTIVATION.
  3. Put the COOL-OFF-HEAT switch into the OFF position. The air conditioning system should turn off. The fan may continue to run for a short period of time.
  4. Put the COOL-OFF-HEAT switch into the HEAT position.Robertshaw-9600-PROGRAMMABLE-THERMOSTAT-fig-22
  5. Press the Robertshaw-9600-PROGRAMMABLE-THERMOSTAT-fig-10 button until the temperature setting is at least 3 degrees above room temperature. The heating system should turn on. The fan may not turn on immediately, depending on the fan delay built into the furnace.Robertshaw-9600-PROGRAMMABLE-THERMOSTAT-fig-23
  6. Put the Robertshaw-9600-PROGRAMMABLE-THERMOSTAT-fig-24COOL-OFF-HEAT switch into the OFF position. The heating system should turn off. Once again, the fan may have a delay.
  7. Put the Robertshaw-9600-PROGRAMMABLE-THERMOSTAT-fig-24AUTO–ON switch to the ON position. The blower fan should turn on.
  8. Put the AUTO–ON switch in the AUTO position. The blower fan should turn off.

Troubleshooting

Robertshaw-9600-PROGRAMMABLE-THERMOSTAT-fig-27

If problems with the thermostat cannot be solved, call: Technical Support: at (800) 445-8299
Monday-Friday 7:30-5:30 CST
For after-hours service, a 24-hour automated help line is available.
For warranty returns, send thermostat, shipping prepaid to:
MAPLE CHASE COMPANY
Warranty Department
2820 Thatcher Road
Downers Grove, IL 60515

Wiring Diagrams
The following is just a sample of the most common types of HVAC systems. Refer to your system’s installation manual for wiring information.

Robertshaw-9600-PROGRAMMABLE-THERMOSTAT-fig-25

HEAT/COOL 5-WIRE TWO TRANSFORMER

Robertshaw-9600-PROGRAMMABLE-THERMOSTAT-fig-26

FIVE-YEAR LIMITED WARRANTY

Maple Chase Company warrants to the original contractor installer or to the original consumer user, each new Robertshaw thermostat to be free from defects in materials and workmanship under normal use and service for a period of five (5) years from the date of purchase. This warranty and our liability do not apply to batteries or the merchandise that has been damaged, caused by misuse, neglect, mishandling, alterations, improper installation, or use in a way other than in accordance with Maple Chase Company recommendations and instructions. Maple Chase Company agrees to repair or replace at its option any thermostat under warranty provided it is returned within the warranty period, postage prepaid, with proof of the date of purchase. The cost of thermostat removal or reinstallation is not the responsibility of Maple Chase Company. Repair or replacement as provided under this warranty is the exclusive remedy of the consumer. Maple Chase Company shall not be liable for any incidental or consequential damages for breach of any express or implied warranty on this product, or under any other theory of liability. Except to the extent prohibited by applicable law, any implied warranty of merchantability or fitness for a particular purpose on this product is limited to the duration of this warranty. Some states do not allow the exclusion or limitation of incidental or consequential damages or allow limitations on how long an implied warranty lasts, so the above limitations or exclusions may not apply to you. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
Maple Chase Company 2820 Thatcher Road Downers Grove, Illinois 60515 United States of America

Reference

Download Manual

Robertshaw 9600 PROGRAMMABLE THERMOSTAT User Manual

Robertshaw logo

Robertshaw 9600 PROGRAMMABLE THERMOSTAT User Manual


Posted

in

by

Comments

Leave a Reply

Your email address will not be published. Required fields are marked *