Robertshaw 9560 NON-PROGRAMMABLE THERMOSTAT
Application
The Robertshaw 8425 is a multi-stage thermostat designed to control 24 VAC heat pump systems.
Features
- Multi-stage control
- Auto changeover [deadband adjustable from 2°F to 8°F (1.0°C – 4.5°C)]
- Large back lit display
- Adjustable 1ST and 2ND stage temperature differential
- Compressor short cycle protection
- Adjustable fan delay on cooling
- LED indication of system status
- Zone system compatible as a master thermostat
- Battery-free EEPROM memory retention
- Optional temperature limiting settings
- Fahrenheit/Celsius display option
- Adjustable from 45°F to 90°F (7°C – 32°C)
- Quick wire terminal block
WARNING:
- Always turn off power at main fuse or circuit breaker panel before installing, removing, cleaning, or servicing thermostat.
- Read all the information in this manual before installing this thermostat.
- DO NOT CONNECT TO 120 VAC. This is a 24 VAC low-voltage thermostat. Do not install on voltages higher than 30 VAC.
- All wiring must conform to local and national building and electrical codes and ordinances.
- Do not short (jumper) across terminals on the gas valve or at the system control to test installation. This will damage the thermostat and void the warranty.
- Do not connect ground to any terminal in this unit.
Step 1: Replacing Existing Thermostat
- Turn off power to heating and cooling system.
- Remove cover from old thermostat to expose wires (Figure 1).
- Disconnect wires one at a time from existing terminals. Use enclosed labels to mark existing wires. Refer to cross references in the Wiring Table if existing wiring does not directly match the labels.
Old Terminal | New Label | Description |
R, V-VR or VR-R | R | 24VAC, return |
Y, Y1, M | Y1 | Compressor relay (Stage 1) |
O or R | O | Reversing valve (cool active) |
B | B | Reversing valve (heat active) |
F or G | G | Fan control relay |
Y2 | Y2 | 2nd stage cooling circuit |
W2, W-U or E | W2/E | 2nd stage heating control or emergency heating for heat pumps |
C, X or B | C | 24 VAC, transformer common side |
L or X | L | System monitor |
W or W1 | W1 | 1st stage heat – non heat pump |
Step 2: Installing Model 9560 Thermostat
- Turn power off to the heating and cooling systems.
- Place EMER-HEAT-OFF-COOL in OFF position .
- Place AUTO-ON switch into AUTO position
- Remove the cover using a coin or screwdriver Set aside
- Place the thermostat against the wall at desired location. Make sure wires will feed through opening (Figure 4) on base of thermostat.
- Mark placement of mounting holes Set base aside.
- If mounting on drywall, tap plastic anchors into wall.
- NOTE: Enclosed plastic anchors do not require a drilled hole for drywall.
- If mounting on a surface other than drywall, drill the marked holes using a 3/16″ (5mm) drill bit.
- Align base with plastic anchors and feed wires through opening.
- Secure base to wall with supplied screws. NOTE: The thermostat will mount horizontally on a single gang junction box.
- Strip end of wires 5/16” (8mm) if needed.
- Terminal screws are already loose and ready for wire insertion.
- Insert wires into terminal strip (Figure 4) matching the label to the corresponding terminal (see Wiring Diagrams). Tighten screws.
- Make sure wire connections are secure.
- Push excess wire back through opening
Wiring Diagram for 9560
TERMINAL LEGEND
TERMINALLEGEND – 9560 | |||
TERM | EQUIPMENT TOCONNECT | REQ? | TERMINALFUNCTION |
C | 24VAC common connection | Yes | For input of 24VAC common side of transformer |
L | System fault indicator connection | No | For input of system fault indicator (if present) |
R | 24VAC hot connection | Yes | For input of 24VAC hot side of transformer |
Y2 | Second stage cooling connection | No | Energizes on a call for second stage cooling |
Y1 | First stage compressor connection | Yes | Energizes on a call for first stage heating or cooling |
E | Emergency heat connection | No* | Energizes on a call for heat in the EM mode only |
G | Indoor fan connection | Yes | Energizes with E, Y1, Y2 and W2 terminals or with FAN option switched to the
ON position |
W2 | Second stage heat connection | No* | Energizes on a call for second stage heating (auxiliary heat) |
O | Cool active reversing valve connection | Yes** | Energizes when in the in COOL mode |
B | Heat active reversing valve connection | Yes** | Energizes when in the HEAT or EM modes |
- A temperature limiting jumper has been included in this thermostat.
- Cutting this jumper (J3) limits the heating setpoint to no greater than 72°F and the cooling setpoint to no lower than 78°F (Figure 7).
- Replace thermostat cover by snapping into place.
Testing the Thermostat
- Place the AUTO-HEAT-OFF-COOL switch into the COOL position.
- Press the button until the temperature setting is at least 3 degrees below the room temperature.
- The air conditioning system should turn on within a few seconds.
- Put the AUTO-HEAT-OFF-COOL switch into the OFF position. The air conditioning system should turn off.
- Put the AUTO-HEAT-OFF-COOL switch into the HEAT position.
- Press the button until the temperature setting is at least 3 degrees above room temperature. The heating system should turn on. The fan may not turn on immediately, depending on the fan delay built into the furnace.
- Put the AUTO-HEAT-OFF-COOL switch into the OFF position. The heating system should turn off. The fan may continue to run for a short period of time.
- Put the ON-AUTO switch into the ON position. The blower fan should turn on.
- put the ON-AUTO switch into the AUTO position. The blower fan should turn off.
Customizing the Thermostat
- Cool: The thermostat controls the cooling.
- Off: The heating and cooling systems are off.
- Heat: The thermostat controls the heat.
- Emer:The thermostat controls the second stage emergency heat. Use only when the primary stage of heat is not functioning or requires service.
- The display will show CHECK HP when the heat pump requires service
Fan
- Auto: Equipment controls the fan.
- On: The fan operates continuously.
The temperature differential is factory set at 1°F (0.5°C) for the 1ST stage differential and 2°F (1.0°C) for the 2ND stage. This means that whenever the room temperature changes by one degree Fahrenheit from the temperature setting, the system will turn on. If the system turns on too often, increase the temperature differential. The 2ND stage will turn on when the room temperature changes from the desired temperature by the sum of the 1ST and 2ND stage differential settings. The 2ND stage will also turn on if the temperature has not increased (or decreased in the event of cooling) for a period of twenty minutes. Although programmed at the same time as the temperature differentials, the deadband is used only during the AUTO mode. In the AUTO mode, the thermostat will automatically cycle either the heating or cooling system to maintain optimal comfort. The deadband is the minimum allowable temperature which must occur to switch to the opposite mode. For example, if the deadband is set at 3°F and the setpoint is set at 70°F, the thermostat will switch to cooling mode when the temperature reaches 73°F.
- The thermostat is preset to display the temperature in degrees Fahrenheit (U.S. models) or degrees Celsius (Canadian models).
- The temperature display can be changed. Press and hold both the or A buttons for three seconds. The display will read F or C. Release the buttons.
- Press either the button to change the display.
- After three seconds, the display will switch to the differential settings. The display will read DIFFERENTIAL 1ST.
- the temperature differential is factory set at 1°F (0.5°C) for the first stage.
- Press either the button to adjust the 1ST stage differential between 0.5°F – 3°F. 4. Either wait three seconds or press the button.
- The display will indicate: DIFFERENTIAL 2ND.
- The 2nd stage differential is factory set at 2°F (1.5°C). Press either the button to adjust the 2nd stage temperature differential between 1°F – 6°F (1°C – 3°C).
- press the button to adjust the 2nd stage timed differential between 5 to 40 minutes.
- Either wait 5 seconds or press the button.
- Either wait three seconds or press the button. The display will indicate: AUTOCHANGE DEADBAND.
- Press either the button to adjust the deadband between 2°F – 8°F (1.0°C – 4.5°C). 9. Either wait three seconds or press the button.
- The fan icon and ON will be displayed.
- Press either the button to adjust the residual cool fan delay between 0, 30, 60, or 90 seconds.
- The display will return to the original room temperature display after a few seconds.
LED Indicators
The Robertshaw 9560 uses three LED indicators (in addition to icons on the LCD display) to indicate functionality of the thermostat. When illuminated, the right red LED indicates that the thermostat is calling for emergency heat. The left green LED indicates a call for auxiliary cool. When the middle amber LED is illuminated, the system is not functioning. Call your local HVACR service contractor.
Backlit Display
This thermostat is equipped with a backlight to make nighttime temperature adjustments quick and easy. Press the button to activate the backlight. The backlight will turn off after about 15 seconds of inactivity.
Emergency Heat
The Emergency Heat switch is located on the bottom right corner. To activate emergency heat, slide switch from NORMAL to EMER HEAT.
Reset
To reset the thermostat to factory preprogrammed conditions, press the RESET button located beneath the lower left corner of the display.
Troubleshooting
Symptom | Remedy |
Thermostat does not turn on system. | Check wiring (see Installation
section). |
Thermostat turns system on and off too frequently. | Increase temperature differential (see Changing the Temperature Differential section). |
CHECK LED is lighted | Monitors system status. Call your local HVAC service provider. |
Thermostat does not display proper room temperature. | Check Fahrenheit (F) / Celsius (C) settings (see Changing Fahrenheit
(F) to Celsius (C) section). |
Er on display | If error occurs after turning on EMERGENCY HEAT, make sure the system switch is in HEAT also. If
Er is still on display, call technical service. |
- Technical Support: (800) 445-8299
- Monday-Friday 7:30 AM – 5:30 PM CST
- For after hours service, a 24-hour automated help line is available
Warranty
- Invensys Controls Americas
- Warranty Claims Department
- 515 S. Promenade
- Corona, CA 92879-1736
- 191 E. North Avenue
- Carol Stream, Illinois 60188
- United States of America
REFERENCE
DOWNLOAD MANUAL
Leave a Reply